Medium voltage indoor circuit breakers ANSI/IEC solutions

Table of contents

Introduction ............................................................................................................................................................................ 3 ADVAC .................................................................................................................................................................................... 4 AMVAC .................................................................................................................................................................................... 6 Vmax ....................................................................................................................................................................................... 8 VD4 ....................................................................................................................................................................................... 10 VM1 ....................................................................................................................................................................................... 14 eVD4 ..................................................................................................................................................................................... 16 HD4 ....................................................................................................................................................................................... 18 V-Contact VSC ...................................................................................................................................................................... 22

2 Medium voltage indoor circuit breakers | Descriptive bulletin

Introduction

ABB’s portfolio of medium voltage indoor circuit breakers offers the complete spectrum of solutions. The leading technologies and solutions offered by these breakers include magnetic and spring charged actuators, encapsulated and embedded poles, SF6 or vacuum encapsulated interrupters, integrated protection and control sensors, small footprint designs, and IEC and ANSI standards. The constant improvements and attention to customer feedback has driven ABB to further accelerate the technology of the medium voltage indoor breaker market. With millions of these breakers currently in service, ABB has a proven track record that quality and reliability are the most important aspect of any product. Feature

ADVAC

AMVAC

Reduced footprint (with lower ratings) Ratings

Interrupting

VMAX

VD4

VM1

eVD4

HD4

VSC Contactor

X

X

X

X

X

X

X

Max rating 40 kA and below

X

X

X

X

Max rating 50 kA

X

X

X

X

Max rating 63 kA

X

ANSI tested

X

X

X2

UL approved

X

X

X2

UR - fixed mount only

X

X

X2

Drawout

X

X

X

X

X

X

X

X

Direct ROF (option)

X

X

Fixed

X

X

X

X

X

X

X

X

Vacuum

X

X

X

X

X

X

IEC tested

Breaker Type

The ABB OEM program is founded on a commitment to outstanding customer service and the best reputation in the industry for long-term product support. Our OEM Sales and Marketing Team is here to help, and we are committed to the success of your business.

X

X1 X

X

X

Encapsulated interrupter in pole

X

Spring actuator

X

Available with breaker compart-

X X4

X X

Magnetic actuator Enclosures

X

X1

SF6 Actuator

X X

X

X X

X

X

X X

X X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

ment kit Available with L-Frame or PB/F

X

X

X

Available with ANSI compart-

X

X

X

X

X

X3

X

ment Available with IEC compartment Available with UR compartment

X

Integrated sensors & relay Warranty - five year

X

X X3

X X

1

VM1 drawout only 15 kV, 1200 A or 2000 A, 25 kA or 31.5 kA (withdrawable only) VMAX only 15 kV, 1200 A, 25 kA or 31.5 kA 3 Contact ABB for more information 4 Fixed VSC/A Only VSC Contactor will be available with ANSI compartment as part of the model 4 MV MCC 2

Descriptive bulletin | Medium voltage indoor circuit breakers 3

ADVAC

ANSI

The ADVAC series is a complete line of ANSI-rated vacuum circuit breakers with a spring charged mechanism offering power distribution system customers the advantages of the latest technology with a modular design that is easily maintainable. This technology reduces ownership costs through improved reliability and maintainability. (ANSI C37.04-C37.06-C37.09) Summary of benefits: − High duty breaker 1,200 A to 3,000 A continuous current and 25 kA to 63 kA interrupting − The ADVAC utilizes the ABB EL spring mechanism used on various ANSI and IEC breakers to provide up to 20,000 mechanical operations in a compact, modular design that is readily accessible and easily maintained to reduce down time − A modular Smart coil assembly used in multiple ABB breakers, provide close, open, and under voltage actuation; all in one simple assembly. This single assembly of 3 coils is replaceable in one minute by removing one screw − The motor assembly is designed to reduce down time with simple replacement by removing one screw − First developed by ABB over 20 years ago, completely embedded vacuum interrupters in a solid insulation material provide superior protection against dust, dirt, condensation, and are less susceptible to failure due to contamination, tracking or partial discharge − Designed with safety as a priority: standard built in mechanical anti-pumping device, Kirk Key, padlocking, and push button cover provisions and closed-door racking − The racking mechanism (truck) is integrated into the breaker and designed to 180 ft∙lb torque rating to provide increased reliability and reduced maintenance costs

1 Spring actuated EL Mechanism found in ADVAC, VD4, Vmax, and eVD4 breakers | 2 Modular Smart Coil used to preform all tripping applications on medium voltage breakers with EL mechanisms 1

4 Medium voltage indoor circuit breakers | Descriptive bulletin

2

ADVAC

ANSI

Circuit breaker

ADVAC

ADVAC

ADVAC

Standard

ANSI

ANSI

ANSI

Rated and insulation voltage

kV

4.76

8.25

15

Withstand voltage at 60 Hz

kV

19

36

36

Impulse withstand voltage (BIL)

kV

60

95

95

Rated frequency

Hz

50-60

50-60

50-60

Utilization

Kit/L-Frame/Module/Switchgear

Kit/L-Frame/Module/Switchgear

Kit/L-Frame/Module/Switchgear

Rated current

A

1200

2000

3000

1200

2000

3000

1200

2000

3000

Rated breaking capacity and short-time

kA

25

25

25

-

-

-

25

25

25

31.5

31.5

31.5

-

-

-

31.5

31.5

31.5

40

40

40

40

40

40

40

40

40

50

50

50

-

-

-

50

50

50

-

-

-

-

-

-

63

63

63

65

65

65

-

-

-

65

65

65

82

82

82

-

-

-

82

82

82

104

104

104

104

104

104

104

104

104

130

130

130

-

-

-

130

130

130

-

-

-

-

-

-

164

164

164

withstand current

Making capacity

kA

Operation sequence Opening time

O - 0.3 s - CO - 3 min - CO ms

Closing Time

ms

25 kA…31.5 kA

23…34

-

23…39

40 kA…50 kA

58…71

26…34

23…39

25 kA…31.5 kA

30…60

40 kA…50 kA

50…80

Total interruption time

cycles

Type H

P P

L H L

D

D P

Weight Technical catalog 1

31 Fixed

Overall dimensions

50…80

-

30…60

50…80

50…80

3 Withdrawable

50…80

3

Fixed

Withdrawable

Fixed

Withdrawable

mm

658

708

658

708

658

708…721

inch

25.9

27.9

25.9

27.9

25.9

27.9…28.4

mm

772

790

772

790

772

790

inch

30.4

31.1

30.4

31.1

30.4

31.1

mm

430

614

430

614

430

614

inch

16.9

24.2

16.9

24.2

16.9

24.2

mm

275

275

275

275

275

275

inch

10.8

10.8

10.8

10.8

10.8

10.8

kg

108…181

136…209

137…167

166…195

108…181

136…209

lbs

238…398

300…460

303…368

365…430

238…398

300…460

No.

1VAL057485

1200 A, 40 kA…50 kA; 2000 A, 50 kA; and 3000 A, 50 kA models are 5 cycle

Descriptive bulletin | Medium voltage indoor circuit breakers 5

AMVAC

ANSI

The AMVAC is truly the next generation medium voltage vacuum circuit breaker, utilizing magnetic actuation technology to provide a more reliable and longer lasting solution to the industry. This is made possible by the simplicity of the magnetic actuators design features such as one moving part and built in safety features. (ANSI C37.04-C37.06-C37.09) Summary of benefits: − High duty breaker 1,200 A to 3,000 A continuous current and 25 kA to 50 kA interrupting − Proven design since 2003 using a magnetic actuator operating mechanism with one moving part, built in open/close coils and no maintenance on the operating mechanism. − Switching operations are achieved by exciting one of the two coils which shifts the flux density and causes a force that exceeds the retaining force of the permanent magnets − Current to the actuator open and close coils is time limited to approximately 45ms, thus eliminating the possibility to burn up coils common in spring actuated mechanisms. − Capacitor charging, switching, anti-pumping, interlocking, under voltage release, and armature position details incorporated by an electronic controller − First developed by ABB over 20 years ago, the vacuum interrupters are fully embedded in solid insulation material to provide superior protection against dust, dirt, and condensation, while being less susceptible to failure due to contamination, tracking, or partial discharge. − Reduced ownership costs through minimal maintenance, reduced downtime, smaller battery banks, lower parts inventory, and a standard 5-year warranty − The increased maintenance cycle associated with magnetic actuation increases safety as a result of less time for personnel in switchgear compartments. − The racking mechanism (truck) is integrated into the breaker and designed to 180 ft∙lb torque rating to provide increased reliability and reduced maintenance costs.

Revolutionary magnetic actuator that drives the AMVAC and VM1 breakers

6 Medium voltage indoor circuit breakers | Descriptive bulletin

AMVAC

ANSI

Circuit breaker

AMVAC

AMVAC

AMVAC

AMVAC

Standard

ANSI

ANSI

ANSI

ANSI

Rated and insulation voltage

kV

4.76

8.25

15

27

Withstand voltage at 60 Hz

kV

19

36

36

60

Impulse withstand voltage (BIL)

kV

60

95

95

125

Rated frequency

Hz

50-60

50-60

50-60

50-60

Kit/L-Frame/Module/

Kit/L-Frame/Module/

Kit/L-Frame/Module/Swith-

Kit/L-Frame/Module

Switchgear

Switchgear

gear

Utilization Rated current

A

1200

2000

3000

1200

2000

3000

1200

2000

3000

1200

2000

Rated breaking capacity and

kA

-

-

-

-

-

-

-

-

-

16

16

25

25

25

-

-

-

25

25

25

25

25

31.5

31.5

31.5

-

-

-

31.5

31.5

31.5

-

-

40

40

40

40

40

40

40

40

40

-

-

50

50

50

-

-

-

50

50

50

-

-

-

-

-

-

-

-

-

-

-

42

42

65

65

65

-

-

-

65

65

65

65

65

82

82

82

-

-

-

82

82

82

-

-

104

104

104

104

104

104

104

104

104

-

-

130

130

130

-

-

-

130

130

130

-

-

63…73

33…43

50…80

50…57

short-time withstand current

Making capacity

kA

Operation sequence Opening time

ms

O - 0.3 s - CO - 3 min -CO 16 kA…31.5

12…33

63…73

-

12…33

63…73

63…74

50…80

-

30…60

50…80

50…80

5

5

31

kA Closing time

ms

40 kA…50 kA

63…73

16 kA…31.5

30…60

-

kA 40 kA…50 kA Total interruption time

cyc-

50…80 31

5

5

les Type

Fixed

Withdra-

Fixed

wable Overall dimensions P P

Technical catalog 1

Withdrawa-

Fixed

ble

Withdrawable

657

708

657

708

657

708…721

652

708

inch

25.9

27.9

25.9

27.9

25.9

27.9…28.4

25.7

27.9

mm

772

790

772

790

772

790

772

790

inch

30.4

31.1

30.4

31.1

30.4

31.1

30.4

31.1

D

mm

430

614

430

614

430

614

430

614

inch

16.9

24.2

16.9

24.2

16.9

24.2

16.9

24.2

P

mm

275

275

275

275

275

275

275

275

inch

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

kg

133…181

161…209

158…181

186…209

135…190

163…218

158…162

186…191

lbs

293…398

355…460

348…398

410…460

298…418

360…480

348…358

410…420

No.

1VAL056482

D

Weight

Fixed

mm

L

H L

H

Withdrawable

40 kA…50 kA Models are 5 cycle

Descriptive bulletin | Medium voltage indoor circuit breakers 7

Vmax

IEC

ANSI

The Vmax circuit breaker is the synthesis of ABB’s affirmed technology in designing and constructing vacuum interrupters and their excellence in design, engineering, and production of circuit breakers. The simplistic, small footprint design and universal modular concept translates into greater reliability, flexibility, and maintainability of the breaker and its components. Similar to the VD4 in design, the Vmax circuit breaker differs by targeting lower kA applications. (IEC 62271-100, ANSI/IEEE C37.04-C37.09-C37.54-C37.55)

Rear view of the Vmax breaker with free standing vacuum interrupters

8 Medium voltage indoor circuit breakers | Descriptive bulletin

Summary of benefits: − Low duty breaker 630 A to 1,250 A continuous current and 16 kA to 31.5 kA interrupting − Tested to ANSI standards at 15 kV, 1,200 A continuous current and 25 kA and 31.5 kA interrupting − Small footprint design ideal for applications where space is at a premium with widths as low as 16.4 in (416 mm) for fixed breakers and 24 in (600 mm) for withdrawable breakers within a Powercube module − The Vmax utilizes the ABB EL spring mechanism used on various ANSI and IEC breakers to provide up to 10,000 mechanical operations in a compact, modular design that is readily accessible to easily maintain and reduce down time. − A modular Smart coil assembly used in multiple ABB breakers provides close, open, and under voltage actuation; all in one simple assembly. This single assembly of 3 coils is replaceable in one minute by removing one screw − The motor assembly is designed to reduce down time by being able to be replaced by removing one screw − First developed by ABB over 20 years ago, the vacuum interrupters are fully embedded in solid insulation material to provide superior protection against dust, dirt, and condensation, while being less susceptible to failure due to contamination, tracking, or partial discharge − Designed with safety as a priority: standard built in mechanical anti-pumping device; Kirk Key, padlocking, and push button cover provisions and closed-door racking − Modular design with common parts across ABB Low & Medium Voltage, high & low duty, and ANSI & IEC breakers allows for greater reliability and maintainability

Vmax

IEC

Circuit breaker

VMAX/L/W 12

VMAX/W 15

VMAX/L/W 17

Standard

IEC

ANSI

IEC 17.5

Rated and insulation voltage

kV

12

15

Withstand voltage (1 min) at 50 Hz

kV

28

36 (60 Hz)

38

Impulse withstand voltage (BIL)

kV

75

95

95

Rated frequency

Hz

50-60

Utilization

ANSI

50-60

60

Fixed/UniGear/Powercube

Fixed/Powercube

Fixed/UniGear/Powercube

Rated current

A (40 °C)

630

1250

1200

630

1250

Rated breaking capacity and short-time

kA

16

16

-

16

16

20

20

-

20

20

25

25

251

25

25

31.5

31.5

31.51

31.5

31.5

40

40

-

40

40

50

50

-

50

50

63

63

65

63

63

80

80

82

80

80

withstand current (3 s)

Making capacity

kA

Operation sequence

O - 0.3 s - CO - 15 s - CO

2

Opening time

ms

33.5…60

27…32.5

33.5…60

Arc time

ms

10…15

10…17.5

10…15

Total interruption time

ms

43.5…75

<50

43.5…75

Closing time

ms

45…80

45…80

45…80

Overall dimensions

H

P P

L

H

D L

D

P Weight

Fixed Withdrawable

Technical catalog

mm

496…655

534…665

534…665

inch

19.5…25.8

21…25.8

21…25.8

mm

416…503

416…503

416…503

inch

16.4…19.8

16.4…19.8

16.4…19.8

mm

421…665

456…662

456…665

inch

16.6…25.8

18…26

18…26.2

mm

133…150

133…150

133…150

inch

5.2…5.9

5.2…5.9

5.2…5.9

kg

77

77

77

lbs

169.8

169.8

169.8

kg

98

98

98

lbs

216.1

216.1

216.1

No.

1VCP000408

1

3 Cycles 2 Operation for VMAX ANSI is O - 0.3 s - CO - 3 min - CO

Descriptive bulletin | Medium voltage indoor circuit breakers 9

VD4

IEC

The VD4 circuit breakers are the synthesis of ABB’s affirmed technology in designing and constructing vacuum interrupters and their excellence in design, engineering, and production of circuit breakers. Similar to the VMAX in design, the VD4 circuit breaker differs by targeting higher duty applications. (IEC 62271-100) Summary of benefits: − High duty breaker 630 A to 4,000 A continuous current and 16 kA to 50 kA interrupting − Small footprint design ideal for applications where space is at a premium with widths as low as 17.7 in (450 mm) for fixed breakers and 24 in (600 mm) for withdrawable breakers within a Powercube module − The VD4 utilizes the ABB EL spring mechanism used on various ANSI and IEC breakers to provide up to 20,000 mechanical operations in a compact, modular design that is readily accessible and easily maintained to reduce down time − A modular Smart coil assembly used in multiple ABB breakers provides close, open, and under voltage actuation; all in one simple assembly. This single assembly of 3 coils is replaceable in one minute by removing one screw − The motor assembly is designed to reduce down time with simple replacement by removing one screw − First developed by ABB over 20 years ago, completely embedded vacuum interrupters in a solid insulation material provide superior protection against dust, dirt, and condensation, while being less susceptible to failure due to contamination, tracking, or partial discharge − Designed with safety as a priority: standard built in mechanical anti-pumping device, key locking, padlocking, and push button cover provisions and closed-door racking − Modular design with common parts across ABB Low & Medium Voltage, high & low duty, and ANSI & IEC breakers allows for greater reliability and maintainability

1 Spring actuated EL Mechanism found in ADVAC, VD4, Vmax, and eVD4 breakers | 2 Modular Smart Coil used to preform all tripping applications on medium voltage breakers with EL mechanisms 1

10 Medium voltage indoor circuit breakers | Descriptive bulletin

2

VD4

IEC

Circuit breaker

VD4 12

VD4 17

Standard

IEC

IEC

Rated and insulation voltage

kV

12

17.5

Withstand voltage (1 min)

kV (50Hz)

28

38

Impulse withstand voltage

kV

75

95

Rated frequency

Hz

50-60

50-60

Utilization Rated current

A (40 °C)

Rated breaking capacity and short-time

kA

withstand current (3 s)

Making capacity

kA

Fixed/UniGear/PowerCube/

UniGear/Power-

Fixed/UniGear/PowerCube/

ZS8.4 1

Cube

ZS8.41 40002

630

1250 1600 2000 2500 3150

1250

1600 2000 2500 3150

16

16











16

16











20

20

20

20

20

20

20

20

20

20

20

20

20

20

25

25

25

25

25

25

25

25

25

25

25

25

25

31.5 31.5

31.5 31.5 31.5 31.5

31.5

31.5 31.5 31.5 31.5 31.5 31.5

31.5



40

40

40

40

40

40



40

40

40

40

40

40



50

50

50

50

50

50



50

50

50

50

50

50

40

40











40

40











50

50

50

50

50

50

50

50

50

50

50

50

50

50

63

63

63

63

63

63

63

63

63

63

63

63

63

63

80

80

80

80

80

80

80

80

80

80

80

80

80

80



100

100

100

100

100

100



100

100

100

100

100

100



125

125

125

125

125

125



125

125

125

125

125

125

Opening time

ms

33 ... 60

33 ... 60

Arc time

ms

10 ... 15

10 ... 15

Total interruption time

ms

43 ... 75

43 ... 75

Closing time

ms H mm inch

P P

L mm (fixed version)

inch

H

D mm L

D

inch P mm

Fixed Weight Withdrawable Technical catalogue

40002

630

25

O-0.3s-CO-15s-CO3

Operation sequence

Overall dimensions

UniGear/PowerCube

60 ... 80

60 ... 80

461…691

635…742

461…691

18.1…27.2

25…29.2

18.1…27.2

635…742 25…29.2

450…853

700…853

450…853

700…853

17.7…33.6

27.6…33.6

17.7…33.6

27.6…33.6

424…662

424…643

424…664

424…643

16.7…26.1

16.7…25.3

16.7…26.1

16.7…25.3

150…275

275

150…275

275

inch

5.9…10.8

10.8

5.9…10.8

10.8

kg

73…163

140…177

73…163

140…177

lbs

160.9…359.4

308.6…390.2

160.9…359.4

308.6…390.2

kg

116…225

221…240

116…225

221…240

lbs

255.7…496

487.2…529.1

255.7…496

487.2…529.1

No.

1VCP000001

1

ZS8.4 switchgear up to 1250 A and 25 kA 2 In ABB switchgear with forced ventilation, withdrawable only 3 For high performances, please ask representative VD4/R maximum ratings 24 kV, 1250 A, 25 kA

Descriptive bulletin | Medium voltage indoor circuit breakers 11

VD4

IEC

Circuit breaker

VD4 24

VD4 36

VD4 40.5

Standard

IEC

IEC

IEC

Rated and insulation voltage kV

24

36

40.5

Withstand voltage (1 min)

50

70

85 185

kV (50Hz)

Impulse withstand voltage

kV

125

170

Rated frequency

Hz

50-60

50-60

50-60

Fixed/UniGear/PowerCube/ZS8.41

Powercube (PB6)/ZS2

Powerbloc/ZS3.2

Utilization Rated current

A (40 °C) 630

Rated breaking capacity and short-time

kA

withstand current (3 s)

Making capacity

kA

Operation sequence

1250

1600

2000

2500

31502 1250

1600

2000

2500

31502 1250

1600

16







-



















20

20

20



-



















25

25

25

25

25

-

25

25

25

25

25

25

25

25

25











31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5











-

40

40

40

40

40



















-





















40







-



















50

50

50



-





















63

63

63

63

63

-

63

63

63

63

63

63

63

63

63

63











80

80

80

80

80

80

80

80

80

80

80











-

100

100

100

100

100





















-





















3

33 ... 60

40 … 60

40 … 60

10 ... 15

10 … 15

10 … 15

Total interruption time

ms

43 ... 75

50 … 75

50 … 75

Closing time

ms

60 ... 80

60 … 80

60 … 80

H mm

631…838

564…973

1575

inch

24.8…33

22.2…38.3

62

L mm

570…853

778…842

895

inch L

D

Fixed Weight Withdrawable Technical catalogue

inch



50

O-0.3s-CO-15s-CO

D mm

31.5

40

ms

H

– 25



Arc time

P P

31502 –

16

ms

(fixed version)

2500

20

Opening time

Overall dimensions

2000

22.4…33.6

30.6…33.1

32.5

424…802

468…788

686 27

16.7…31.6

18.4…31

P mm

210…275

275

inch

8.3…10.8

10.8

kg

100…110

150…170



lbs

220.5…242.5

330.7…374.8

– 290 … 350

kg

140…277

230

lbs

308.6…610.7

507.1

No.

1VCP000001

1

ZS8.4 switchgear up to 1250 A and 25 kA 2 In ABB switchgear with forced ventilation, withdrawable only 3 For high performances, please ask representative VD4/R maximum ratings 24 kV, 1250 A, 25 kA

12 Medium voltage indoor circuit breakers | Descriptive bulletin

Descriptive bulletin | Medium voltage indoor circuit breakers 13

VM1

IEC

ANSI

The VM1 is truly the next generation small footprint medium voltage vacuum circuit breaker, utilizing magnetic actuation technology to provide a more reliable and longer lasting solution to the industry. This is made possible by the simplicity of the magnetic actuators design features such as one moving part and built in safety features. The VM1 provides a smaller footprint solution for magnetic actuation type circuit breakers. (IEC 62271-100, ANSI/IEEE C37.04-C37.09-C37.54-C37.55)

Revolutionary magnetic actuator that drives the AMVAC and VM1 breakers

14 Medium voltage indoor circuit breakers | Descriptive bulletin

Summary of benefits: − High duty breaker 630 A to 3,150 A continuous current and 16 kA to 31.5 kA interrupting − Available in ANSI markets at 15 kV, 1,200 A and 2,000 A continuous current and 25 kA and 31.5 kA interrupting − Small footprint design ideal for industries where space is at a premium with widths as low as 17.7 in (450 mm) for fixed breakers and 24 in (600 mm) for withdrawable breakers within a Powercube module − Proven design since 2003 using a magnetic actuator operating mechanism with one moving part, built in open/close coils and no maintenance on the operating mechanism. − Switching operations are achieved by exciting one of the two coils, which shifts the flux density, and causes a force that exceeds the retaining force of the permanent magnets − Current to the actuator open and close coils is time limited to approximately 45ms, thus eliminating the possibility to burn up coils common in spring charge mechanisms. − Capacitor charging, switching, anti-pumping, interlocking, under voltage release, and armature position details incorporated by an electronic controller − First developed by ABB over 20 years ago, the vacuum interrupters are fully embedded in solid insulation material to provide superior protection against dust, dirt, and condensation, while being less susceptible to failure due to contamination, tracking, or partial discharge. − Reduced ownership costs through minimal maintenance, reduced downtime, smaller battery banks, and lower parts inventory − The increased maintenance cycle associated with magnetic actuation increases safety as a result of less time for personnel in switchgear compartments. − The racking mechanism (truck) is integrated into the breaker and designed to 180 ft∙lb torque rating to provide increased reliability and reduced maintenance costs

VM1

IEC

Circuit breaker

VM1 12

VM1/A/P

VM1 17

Standard

IEC

ANSI

IEC

IEC

kV

12

15

17.5

24

kV

28

36 (60 Hz)

38

50

kV

75

95

95

125

Rated and insulation

ANSI

VM1 24

voltage Withstand voltage (1 min) at 50 Hz Impulse withstand voltage (BIL) Rated frequency

Hz

Utilization

50-60 Fixed/UniGear/Powercube

Rated current

A (40

50-60

50-60

Uni-

Powercube

Fixed/UniGear/Powercube

50-60

Gear

PB1/PB2

Uni-

Fixed/UniGear/Powercube

Gear

630

1250 1600 2000 2500 3150 1200 2000 630

1250 1600 2000 2500 3150 630

1250 1600 2000 2500

°C) Rated breaking ca-

16

16

-

-

-

-

-

-

16

16

-

-

-

-

16

16

16

16

pacity and short-time

20

20

20

20

20

20

-

-

20

20

20

20

20

20

20

20

20

20

20

withstand current

25

25

25

25

25

25

251

251

25

25

25

25

25

25

25

25

25

25

25

(3 s)

31.5 31.5 31.5 31.5 31.5 31.5

31.5 1 31.5 1 31.5 31.5 31.5 31.5 31.5 31.5 -

-

-

-

-

-

-

-

-

-

40

-

-

-

-

-

-

-

40

-

-

-

-

-

-

-

-

-

-

50

-

-

-

-

-

-

-

-

-

-

-

-

-

40

40

-

-

-

-

-

-

40

40

-

-

-

-

40

40

40

40

-

50

50

50

50

50

50

-

-

50

50

50

50

50

50

50

50

50

50

50

63

63

63

63

63

63

63

63

63

63

63

63

63

63

63

63

63

63

63

Making capacity

kA

kA

Operation sequence

80

80

80

80

80

80

80

80

80

80

80

80

80

-

-

-

-

-

-

-

-

-

-

100

-

-

-

-

-

-

-

100

-

-

-

-

-

-

-

-

-

-

125

-

-

-

-

-

-

-

-

-

-

-

-

-

O - 0.3 s - CO - 3 min - CO ms

35…45

40…70

35…45

Arc time

ms

10…15

8…13

10…15

10…15

Total interruption time ms

45…60

45…60≤83

45…60

45…60

Closing time

ms

50…60

Overall

mm

475…834

dimensions

L P P

D

L

Weight

D

834

35…45

45…80

50…60

50…60

628…691

475…834

631…834

inch

18.7…32.8

32.8

24.7…27.2

18.7…32.8

24.8…32.8

mm

450…853

853

503…653

450…853

570…853

inch

17.7…33.6

33.6

19.8…25.7

17.7…33.6

22.4…33.6

mm

424…790

790

503…642

424…790

424…802

inch

16.7…31.1

31.1

19.8…25.3

16.7….31.1

16.7…31.6

mm

150…275

275

150…210

150…275

210…275

inch

5.9…10.8

10.8

5.9…8.3

5.9…10.8

8.3…10.8

kg

94…135

-

-

94…135

108…137

lbs

207.2…297.6

-

-

207.2…297.6

238.1…302

Withdra-

kg

137…255

148

137…192

137…255

wable

lbs

302…562.2

326.3 302…423.3 302…562.2

No.

1VCP000157

H

P Fixed

Technical catalog 1

80

Opening time

H

-

148…275 326.3…606.3

5 Cycles

Descriptive bulletin | Medium voltage indoor circuit breakers 15

eVD4

IEC

The eVD4 circuit breaker is a complete packaged medium voltage electrical plant protection system. It is the evolution of the traditional concept of a circuit breaker providing breaking, measurement, protection, control, and communication functions in a single device. The eVD4 circuit breaker also integrates combined current and voltage sensors reducing the amount of compartments required in a switchgear line-up. This makes eVD4 the ideal solution for all installations where a high degree of continuity of service is required, along with low footprint requirements. (IEC 62271-100) Summary of benefits: − High duty breaker 630 A to 2,500 A continuous current and 16 kA to 40 kA interrupting − eVD4 is mechanically interchangeable with the VD4, VMax, and VM1 series circuit breakers − Less time required for engineering, wiring in the low voltage compartments, and for the final testing procedures due to the built in protection and control unit that includes current and voltage sensors − Combined with RBX615 relay from the Relion family, the eVD4 system takes advantage of the most reliable technologies − Mean Time to Repair of systems incorporating eVD4 is much shorter than systems with conventional breakers − First developed by ABB over 20 years ago, the vacuum interrupters are fully embedded in solid insulation material to provide superior protection against dust, dirt, and condensation, while being less susceptible to failure due to contamination, tracking or partial discharge. − Modular design with common parts across ABB Low & Medium Voltage, high & low duty, and ANSI & IEC breakers allows for greater reliability and maintainability

1 Combined current and voltage sensors attached directly to the rear of the eVD4 | 2 RBX615 relay mounted behind the front cover of the eVD4 communicates with the included HMI 1

16 Medium voltage indoor circuit breakers | Descriptive bulletin

2

eVD4

IEC

Circuit breaker

eVD4/P 12

eVD4/P 17

Standard

IEC

IEC

Rated and insulation voltage

kV

12

17.5

Withstand voltage (1 min) at 50 Hz

kV

42

42

Impulse withstand voltage (BIL)

kV

75

95

Rated frequency

Hz

50-60

50-60

Utilization

Fixed/UniGear/Powercube

Fixed/UniGear/Powercube

Rated current

A (40 °C)

630

1250

1600

Rated breaking capacity and short-time

kA

16

16

-

-

-

16

16

-

-

-

20

20

20

20

20

20

20

20

20

20

withstand current (3 s)

Making capacity

kA

Operation sequence

2000

2500

630

1250

25

25

25

25

25

25

25

25

25

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

-

40

40

40

40

-

40

40

40

40

40

40

-

-

-

40

40

-

-

-

50

50

50

50

50

50

50

50

50

50

63

63

63

63

63

63

63

63

63

63

80

80

80

80

80

80

80

80

80

80

-

100

100

100

100

-

100

100

100

100

O - 0.3 s - CO - 15 s - CO 40…60

40…60

Arc time

ms

10…15

10…15

Total interruption time

ms

50…75

50…75

Closing time

ms

50…70

50…70

mm

461…691

461…691

inch

18.1…27.2

18.1…27.2

mm

450…853

450…853

inch

17.7…33.6

17.7…33.6

mm

464…662

464…662

inch

18.3…26.1

18.3…26.1

mm

150…275

150…275

inch

5.9…10.8

5.9…10.8

kg

73…160

73…160

lbs

160.9…352.7

160.9…352.7

kg

116…221

116…221

lbs

255.7…487.2

255.7…487.2

No.

1VCP000281

H L

H

D L

D

P Weight

Fixed Withdrawable

Technical catalog

2500

31.5

ms

P P

2000

25

Opening time

Overall dimensions

1600

Descriptive bulletin | Medium voltage indoor circuit breakers 17

HD4

IEC

HD4 medium voltage circuit breakers use SF6 gas to extinguish the electric arc and as the insulating medium. Interrupting in SF6 gas takes place without any arc chopping or generation of overvoltages. These characteristics ensure long electrical life of the circuit breaker and limited dynamic, dielectric, and thermal stresses on the installation. Not to mention, the light and compact structure of the circuit breaker ensures great sturdiness and excellent mechanical reliability at a great value. (IEC 62271-100) Summary of benefits: − High duty breaker 630 A to 4,000 A continuous current and 16 kA to 50 kA interrupting − Autopuffer breaking technique used in high voltage breakers minimizes arc times − Soft quenching technique eliminates chopping currents and is free of re-strike and re-ignition − Mechanical and electrical safety locks prevent incorrect operations, while increasing safety − Spring charged ESH mechanical operating mechanism with standard anti-pumping device − Maintenance-free epoxy embedded poles sealed for life and tested with Helium to ensure no possibility of SF6 leakage

1 Rear view of the HD4, SF6 Gas Insulated Poles utilizing the soft quenching technique | 2 HD4 with cover removed to show the ESH mechanical operating mechanism and tripping coils 1

18 Medium voltage indoor circuit breakers | Descriptive bulletin

2

HD4

IEC

Circuit breaker

HD4 12

HD4 17.5

Standard

IEC

IEC

Rated and insulation voltage

kV

12

17.5

Withstand voltage (1 min) at 50 Hz

kV

28

38

Impulse withstand voltage (BIL)

kV

75

95

Rated frequency

Hz

50-60

50-60

Utilization

Fixed/ZS1/Powercube

Fixed/ZS1/Powercube

Rated current

A (40 °C)

630

1250

1600

2000

2500

3150

36001

630

1250

1600

2000

2500

3150

36001

Rated breaking capacity and short-

kA

16

16

16

16

-

-

-

16

16

16

16

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

25

25

25

25

25

25

25

25

25

25

25

25

25

25

time withstand current (3 s)

Making capacity

kA

Operation sequence

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

-

40

40

40

40

40

40

-

40

40

40

40

40

40

-

50

50

50

50

50

50

-

50

50

50

50

50

50

40

40

40

40

-

-

-

40

40

40

40

-

-

-

50

50

50

-

-

-

-

50

50

50

-

-

-

-

63

63

63

63

63

63

63

63

63

63

63

63

63

63

80

80

80

80

80

80

80

80

80

80

80

80

80

80

-

100

100

100

100

100

100

-

100

100

100

100

100

100

-

125

125

125

125

125

125

-

125

125

125

125

125

125

O - 0.3 s - CO - 15 s - CO

Opening time

ms

45

45

Arc time

ms

10…15

10…15

Total interruption time

ms

55…60

55…60

Closing time

ms

80

80

Overall dimensions

H mm

P P

L

H

628…746

24.7…29.4

24.7…29.4

mm

493…882

532…882

inch

19.4…34.7

20.9…34.7

D mm L

D

P Weight

628…746

inch

Fixed Withdrawable

496…659

496…659

inch

19.5…25.9

19.5…25.9

mm

150…275

150…275

inch

5.9…10.8

5.9…10.8

kg

114…165

114…165

lbs

251.3…363.8

251.3…363.8

kg

120…230

120…230

lbs

264.6…507.1

264.6…507.1 380

Nominal Gas Pressure

kPa

380

Technical catalog

No.

1VCP000004

1

Rated current higher than 3150 A with forced ventillation -HD4/R maximum ratings 36 kV, 1250 A, 25 kA

Descriptive bulletin | Medium voltage indoor circuit breakers 19

HD4

IEC

Circuit breaker

HD4 24

HD4 36

HD4/Z 40.5

Standard

IEC

IEC

IEC

Rated and insulation voltage

kV

24

36

40.5

Withstand voltage (1 min) at

kV

50

70

95

kV

125

170

185

Hz

50-60

50-60

50-60

50 Hz Impulse withstand voltage (BIL) Rated frequency Utilization

Fixed/ZS1/Powercube

Rated current

A (40

Fixed/ZS2/Powercube (PB6)

630

1250

1600

2000

2500

3150

36001 630

1250

1600

2000

Powerbloc/ZS3.2 2500

1250

1600

2000

2500

°C) 16

16

16

16

16

-

-

16

16

16

-

-

-

-

-

-

short-time withstand current

20

20

20

20

20

-

-

20

20

20

20

20

-

-

-

-

(3 s)

25

25

25

25

25

25

25

-

25

25

25

25

25

25

25

25

-

31.5

31.5

31.5

31.5

31.5

31.5

-

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

-

40

40

40

40

40

40

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

40

40

40

40

40

-

-

40

40

40

-

-

-

-

-

-

50

50

50

50

50

-

-

50

50

50

50

50

-

-

-

-

63

63

63

63

63

63

63

-

63

63

63

63

63

63

63

63

-

80

80

80

80

80

80

-

80

80

80

80

80

80

80

80

-

100

100

100

100

100

100

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Rated breaking capacity and

Making capacity

kA

kA

Operation sequence

O - 0.3 s - CO - 15 s - CO

Opening time

ms

45

45

45

Arc time

ms

10…15

10…15

10…15

Total interruption time

ms

55…60

55…60

55…60

Closing time

ms

80

80

80

Overall dimensions P P

Weight

mm

655…821

730…1123

1575

inch

25.8…32.3

28.7…44.2

62

mm

618…842

748…955

850

inch

24.3…33.1

29.4…37.6

33.5

D

mm

496…799

695…833

686

inch

19.5…31.5

27.4…32.8

27

I

mm

210…275

275…350

280

inch

8.3…10.8

10.8…13.8

11

kg

119…165

124…190

-

lbs

262.4…363.8

273.4…418.9

-

L

H L

H

D

Fixed Withdrawable

kg

123…220

130…270

280

lbs

271.2…485

286.6…595.2

617.3

380…450

550

Nominal Gas Pressure

kPa

380

Technical catalog

No.

1VCP000004

1 Rated current higher than 3150 A with forced ventillation -HD4/R maximum ratings 36 kV, 1250 A, 25 kA

20 Medium voltage indoor circuit breakers | Descriptive bulletin

Descriptive bulletin | Medium voltage indoor circuit breakers 21

V-Contact VSC

IEC

The VSC Contactor is ideal for low duty, high number of operation applications. Employing ABB’s world leading magnetic actuation technology and vacuum encapsulated interrupters, the VSC contactor is highly reliable and nearly maintenancefree. (IEC 62271-106) Summary of benefits: − Contactor up to 400 A continuous current − Reliable operating mechanism with one moving part, built in open/close coils and no maintenance − Capacitor charging, switching, anti-pumping, interlocking, and armature position details incorporated by an electronic controller − Free standing vacuum encapsulated poles offer reliable interrupting technology in a wide variety of environments − Available with SCO, Single Command Operated (comparable to single electrical latching function), and DCO, Double Command Operated (comparable to double mechanical latching function) − Long life span with 100,000 electrical operations and 1,000,000 mechanical operation

1 internal view of the VSC Contactor that uses magnetic actuation and free standing vacuum interrupting technologies | 2 Revolutionary magnetic actuator that drives the contactor, a compact version of the same technology in AMVAC and VM1 1

22 Medium voltage indoor circuit breakers | Descriptive bulletin

2

V-Contact VSC

IEC

Contactor

VSC/S 7

VSC/S 12

Standard

IEC

IEC

Rated Voltage

kV

7.2

12

Withstand voltage at 50 HZ

kV

23

282

Impulse withstand voltage (BIL)

kV

60

75

Rated frequency

Hz

50-60

50-60

Utilization Rated service current

A

Fixed/UniGear/Powercube

Fixed/UniGear/Powercube

400

400

Rated short-time withstand current (1s)

A

6,000

6,000

Rated peak current

kA

15

15

Rated short-circuit time (tk)

s

1

1

Nominal number of

SCO function

Op./hr

900

900

operations

DCO function

Op./hr

900

900

kA

4,000

4,000

Rated load and overload characteristics in category of utilization: (AC4 Category) 100 closing operations

kA

4,000

4,000

Normal Current

(AC4 Category) 25 closing operations

A

400

400

Electrical life (AC1 category) (operations)3

No.

100,000

100,000

Mechanical life (operations)4

No.

2,000,000

2,000,000

Short-circuit breaking capacity1

A

6,000

4,000

Short-circuit making capacity1

A

15,000

8,000

Opening time

ms

20…30

20…30

Closing time

ms

35…50

Type Overall dimensions

H mm L H L

Weight Technical catalog

D

35…50

Fixed

Withdrawable

Fixed

Withdrawable

371…494

636…653

424…532

636…653

inch

14.6…19.4

25…25.7

16.7…20.9

25…25.7

mm

350…466

350…531

350…466

350…531

inch

13.8…18.3

13.8…20.9

13.8…18.3

13.8…20.9

215…622

657…673

215…702

657…673

D mm inch

8.5…24.5

25.9…26.5

8.5…27.6

25.9…26.5

P mm

115…150

115…150

115…150

115…150

inch

4.5…5.9

4.5…5.9

4.5…5.9

4.5…5.9

kg

20…35

52…54

20…35

52…54

lbs

44.1…77.2

114.6…119

44.1…77.2

114.6…119

No.

1VCP000165

1

O - 3 min - CO - 3 min - CO single operation sequence Version for 42 kV - 50 Hz x 1 minute between phases and between phase and earth available on request (only fixed contactors or for UniGear switchgear) 3 Electrical life obtainable by following the maintenance program given in the installation manual 4 One mechanical operation is considered one open or one close 2

Descriptive bulletin | Medium voltage indoor circuit breakers 23

ABB Inc. Medium Voltage OEM Apparatus 655 Century Point Lake Mary, FL 32746 Phone: +1 407 732 2000 Customer service: +1 800 929 7947 ext. 5 +1 407 732 2000 ext. 2510 E-Mail: [email protected]

www.abb.com/mediumvoltage www.abb.us/mvservice

1VAL0501-DB Rev B April 2014

Contact us

Medium voltage products

VD4 Medium voltage vacuum circuit-breakers 12...36 kV - 630...3150 A - 16...50 kA

Index

4

1. Description

1 2

2. Selection and ordering

6 4

3. Specific product characteristics

6 8

4. Overall dimensions

9 5

5. Electric circuit diagram

3

1. Description

The new VD4 are a synthesis of renowned technology in designing and constructing vacuum interrupters embedded in poles, and excellency in design, engineering and production of circuit-breakers. The VD4 medium voltage circuit-breakers use vacuum interrupters embedded in the poles. This construction technique makes the circuit-breaker poles particularly sturdy and protects the interrupter from impacts, dust deposits and humidity. The vacuum interrupter houses the contacts and makes up the interrupting chamber.

1 2 3 4

5 6 7

8 9 10



1 2 3 4 5 6 7 8

Upper terminal Vacuum interrupter Housing/pole Stem of moving contact Lower terminal Flexible connection Tie-rod spring fork Tie-rod

9 Pole fixing 10 Connection to operating mechanism

Vacuum interrupter embedded in the pole

4

Current interruption in vacuum The vacuum circuit-breaker does not require an interrupting and insulating medium. In fact, the interrupters do not contain ionisable material. In any case, on separation of the contacts an electric arc is generated made up exclusively of melted and vaporised contact material. The electric arc remains supported by the external energy until the current is cancelled in the vicinity of natural zero. At that instant, the rapid reduction in the load density carried and the rapid condensation of the metallic vapour, leads to extremely rapid recovery of the dielectric characteristics. The vacuum interrupter therefore recovers the insulating capacity and the capacity to withstand the transient recovery voltage, definitively extinguishing the arc. Since high dielectric strength can be reached in the vacuum,

• Vacuum interruption technique • Vacuum contacts protected against oxidation and contamination • Vacuum interrupter embedded in the pole • Interrupter protected against shocks, dust and humidity • Operation under different climatic conditions • Limited switching energy • Stored energy operating mechanism with anti-pumping device supplied as standard • Simple customisation with a complete range of accessories • Fixed and withdrawable version • Compact dimensions • Sealed-for-life poles • Sturdiness and reliability • Limited maintenance • Circuit-breaker racking in and racking out with door closed • Incorrect and hazardous operations are prevented thanks to special locks in the operating mechanism and in the truck • High environmental compatibility

even with minimum distances, interruption of the circuit is also guaranteed when separation of the contacts takes place a few milliseconds before passage of the current through natural zero. The special geometry of the contacts and the material used, as well as the limited duration and low voltage of the arc, guarantee minimum contact wear and long life. Furthermore, the vacuum prevents their oxidation and contamination. Operating mechanism The low speed of the contacts, together with the reduced run and low mass, limit the energy required for the operation and therefore guarantee extremely limited wear of the system. The circuit-breaker therefore only requires limited maintenance. The VD4 circuit-breakers use a mechanical operating

mechanism, with stored energy and free trip. These characteristics allow opening and closing operations independent of the operator. The operating mechanism is of simple conception and use and can be customised with a wide range of accessories which are easy and rapid to install. This simplicity converts into greater reliability of the apparatus. The structure The operating mechanism and the poles are fixed to a metal frame which is also the support for the fixed version of the circuit-breaker. The compact structure ensures sturdiness and mechanical reliability. Apart from the isolating contacts and the cord with plug for connection of the auxiliary circuits, the withdrawable version is completed with the truck for racking it into and out of the switchgear or enclosure with the door closed.

5

1. Description

Quenching principle of ABB interrupters In a vacuum interrupter, the electric arc starts at the moment of contact separation and is maintained until zero current and can be influenced by magnetic fields. Vacuum arc – diffuse or contracted Following contact separation, single melting points form over the entire surface of the cathode, producing metal vapours which support the arc. The diffuse vacuum arc is characterised by expansion over the contact surface and by an even distribution of thermal stress on the contact surfaces.

At the rated current of the vacuum interrupter, the electric arc is always of the diffuse type. Contact erosion is very limited and the number of current interruptions very high. As the interrupted current value increases (above the rated value), the electric arc tends to be transformed from the diffuse into the contracted type, due to the Hall effect. Starting at the anode, the arc contracts and as the current rises further it tends to become sharply defined. Near the area involved there is an increase in temperature with consequent thermal stress on the contact. To prevent overheating and erosion of the contacts, the arc is kept rotating. With arc rotation it becomes similar to a moving conductor which the current passes through.

1 2 3 4 5 6 7 8 9 10



1 Stem/terminal 2 Twist protection 3 Bellows 4 Interrupter housing 5 Shield 6 Ceramic insulator

Vacuum interrupter

6

7 Shield 8 Contacts 9 Terminal 10 Interrupter housing

Diffuse arc.

Contraction over anode.

Contraction over anode and cathode.

Schematic diagram of the transition from a diffuse arc to a contracted arc in a vacuum interrupter.

The spiral geometry of ABB vacuum interrupter contacts The special geometry of the spiral contacts generates a radial magnetic field in all areas of the arc column, concentrated over the contact circumferences. An electromagnetic force is self-generated and this acts tangentially, causing rapid arc rotation around the contact axis. This means the arc is forced to rotate and to involve a wider surface than that of a fixed contracted arc.

Apart from minimising thermal stress on the contacts, all this makes contact erosion negligible and, above all, allows the interruption process to be controlled even with very high short-circuits. ABB vacuum interrupters are zero-current interrupters and are free of any re-striking. Rapid reduction in the current charge and rapid condensation of the metal vapours simultaneously with the zero current, allows maximum dielectric strength to be restored between the interrupter contacts within microseconds.

Corrent, Voltage

Short-circuit current Arc voltage System voltage

Short-circuit current interruption

Time Contact separation Recovery voltage (system frequency) Transient recovery voltage (TRV) (high frequency)

Radial magnetic field contact arrangement with a rotating vacuum arc.

Development of current and voltage trends during a single phase vacuum interruption process.

7

1. Description

Versions available The VD4 circuit-breakers are available in the fixed and withdrawable version with front operating mechanism. The withdrawable version is available for UniGear ZS1, ZS8.2 and UniSec switchgear and for PowerCube and Powerbloc enclosures.

Fields of application The VD4 circuit-breakers are used in power distribution for control and protection of cables, overhead lines, transformer and distribution substations, motors, transformers, generators and capacitor banks.

Standards The VD4 circuit-breakers comply with the IEC 62271-100, VDE 0671-part. 100, CEI EN 62271-100 file 7642 (20055) Standards and with those of the major industrialised countries. The VD4 circuit-breakers have undergone the tests indicated below and guarantee the safety and reliability of the apparatus in service in any installation. • Type tests: heating, withstand insulation at power frequency, withstand insulation at lightning impulse, short-time and peak withstand current, mechanical life, short-circuit current making and breaking capacity. • Individual tests: insulation of the main circuits with voltage at power frequency, auxiliary circuit and operating mechanism insulation, measurement of the main circuit resistance, mechanical and electrical operation.

Service safety Thanks to the complete range of mechanical and electrical locks (available on request), it is possible to construct safe distribution switchgear with the VD4 circuit-breakers. The locking devices have been studied to prevent incorrect operations and to inspect the installations whilst guaranteeing maximum operator safety. Key locks or padlock devices enable opening and closing operations and/or racking in and racking out. The racking-out device with the door closed allows the circuitbreaker to be racked into or out of the switchgear only with the door closed. Anti-racking-in locks prevent circuit-breakers with different rated currents from being racked in, and the racking-in and racking out operation with the circuit-breaker closed.

8

• Highly reliable operating mechanisms thanks to a low number of components which are manufactured using production systems for large quantities • Extremely limited and simple maintenance • Accessories common to the entire range • Electrical accessories that can be easily and quickly installed or replaced thanks to wiring pre-engineered with plug-socket connectors • Mechanical anti-pumping device is supplied as standard • Built-in closing spring charging lever • Key lock with circuit-breaker open • Protective covering over the opening and closing pushbuttons to be operated using a special tool • Padlock device on the operating pushbuttons

Accessories The VD4 circuit-breakers have a complete range of accessories to satisfy all installation requirements. The operating mechanism has a standardised range of accessories and spare parts which are easy to identify and order. The accessories are installed conveniently from the front of the circuit-breaker. Electrical connection is carried out with plug-socket connectors. Use, maintenance and service of the apparatus are simple and require limited use of resources.

O

N

M L I H G

F

A

Circuit-breaker operating mechanism A Open/closed auxiliary contacts B Geared motor for closing spring charging C Built-in closing spring charging lever D Mechanical signalling device for circuit-breaker open/closed E Mechanical operation counter F Plug-socket connectors of electrical accessories in the truck

B

C

D

E

P

G Signalling device for closing springs charged/discharged H Service releases I Closing pushbutton L Opening pushbutton M Operating mechanism locking electromagnet N Additional shunt opening release O Transient contact P Contacts for signalling spring charged/discharged

9

1. Description

General characteristics of the complete VD4 series (*) The VD4 series of vacuum circuit-breakers conform to the specifications of the following standards: • VDE 00670, part 1000 IEC 62271-1 • VDE 00671, part 100 IEC 62271-100 • CEI EN 62271-100 File 7642 (2005-5) (*) For information about the 12 kV • 1250 ... 4000 A • 50/63 kA and 36/40.5 kV • 630 ... 2500 A • 16 ... 40 kA circuit-breakers, please see technical catalogue GCBA520PO102.

Rated voltage

(1)

Rated frequency Rated normal current

kV

12

Hz

50 - 60

A

630 . . . 4000 (2)

Short-time withstand current and breaking capacity

kA

16 ... 31.5

40

50

Making capacity

kA

40 ... 80

100

125

Short-time withstand current

s

63 (3)

158

3

3

3

3

•/•

•/•

•/•

•/–

d (mm)

150 - 275

210 - 275

210 - 275

275

H (mm)

205 - 310

310

310

310

a (mm)

450 - 700

570 - 700

600 - 750

750

b (mm)

424

424

459

459

c (mm)

461 - 599

kg

73 - 105

94 - 180

147 - 260

Embedded poles







-

Assembled poles

-

-

-



Fixed / withdrawable version

Maximum overall dimensions (fixed version)

H c

d a

Weight

Technical documentation

10

b

599

(5)

608

(7)

677 260

To go into technical and application aspects of the VD4 circuitbreakers in depth, please ask us for the following publications: – PowerCube modules code 1VCP000091 – Powerbloc modules code BA441/03E – UniGear ZS1 switchgear code 1VCP000138 – ZS8.4 switchgear code L2288 – REF542plus unit code 1VTA100001 – PR512 protection unit code 1VCP000055

17.5

24

36

40,5

50 - 60

50 - 60

50-60

50-60

630 … 3150

630 … 3150

630 . . . 4000

630 . . . 3150

(2)

(2)

16 ... 31.5

40 ... 50

16 ... 31.5

16 ... 31.5

16 … 40

40 ... 80

100 ... 125

40 ... 80

40 ... 80

40 … 100

3

3

3

3

4

•/•

•/•

•/•

•/•

•/•

150 - 275

210 - 275

210 - 275

275

205 - 310

310

310

328 / 280

(6)

450 - 700

570 - 700

570 - 700

786 / 853

(6)

424

424

424

492 / 789

(6)

631 - 661

876 / 973

(6)

461 - 599

(5)

599

(5) (7)

280 - 360

(4)

328 895

(6)

- 1000

555 - 686

(6)

1575

73 - 105

94 - 180

100 - 110

170 / 210

290 - 350











-

-

-





Test voltage according to IEC 622711 Standards table 1a, VDE 0670, - part 1000, list 2 (2) With forced ventilation (3) Higher values on request (4) 360 mm for fixed version, 280 mm for withdrawable version (5) Circuit-breaker with eat sink 616 mm (2500 A) (6) Withdrawable version (7) Circuit-breaker with eat sink 634 mm (3150 A) (1)

Quality System Complies with ISO 9001 Standards, certified by an independent organisation.

Environmental Management System Complies with ISO 14001 Standards, certified by an independent organisation.

Test Laboratory Complies with UNI CEI EN ISO/IEC 17025 Standards, accredited by an independent organisation.

Health and Safety Management System Complies with OHSAS 18001 Standards, certified by an independent organisation.

11

2. Selection and ordering Withdrawable circuit-breakers

Fixed VD4 circuit-breaker (12 kV)

Circuit-breaker

VD4 12 (1) IEC 62271-100 •

Standards

VDE 0671; CEI EN 62271-100- File 7642 •

Rated voltage

Ur [kV] 12

Rated insulation voltage

Us [kV] 12

Withstand voltage at 50 Hz

Ud (1 min) [kV] 28

Impulse withstand voltage

Up [kV] 75

Rated frequency

fr [Hz] 50-60

Rated normal current (40 °C)

Ir [A] 630

Rated breaking capacity (rated short-circuit breaking current symmetrical)

Isc [kA]

Rated short-time withstand current (3s)

Ik [kA]

Making capacity

Ip [kA]

Operation sequence

630

630

1250

1250

1250

1250

1250

1250

1250

16

16

16

16

16

16









20

20

20

20

20

20









25

25

25

25

25

25









31.5

31.5

31.5

31.5

31.5

31.5





















40

40





















50

50

16

16

16

16

16

16









20

20

20

20

20

20









25

25

25

25

25

25









31.5

31.5

31.5

31.5

31.5

31.5





















40

40





















50

50

40

40

40

40

40

40









50

50

50

50

50

50









63

63

63

63

63

63









80

80

80

80

80

80





















100

100





















125

125



















610

[O - 0.3 s - CO - 15 s - CO] •

Opening time

[ms] 33 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 43 ... 75

Closing time

[ms] 60 ... 80 P P

Maximum overall dimensions

H W

D

461

461

461

589

589

610

700

450

570

700

570

700

600

750

D [mm] 424

424

424

424

424

424

424

424

459

459

TN 7405 1VCD —

Operating temperature

210

275

150

210

275

210

275

210

275

75

79

73

75

79

84

84

146

158

7406



7405

7406













000051 —



000051 003282 003285 003440 003441

[°C] - 5 ... + 40 IEC: 60068-2-30, 60721-2-1 • IEC: 62271-1 •

(1) Circuit-breakers up to 1250 A and 31.5 kA have polyamide poles.

12

461

570

[kg] 73

Standardised table of dimensions

Electromagnetic compatibility

461

W [mm] 450 Pole distance P [mm] 150

Weight

Tropicalization

H [mm] 461

• • 12 12 28 75 50-60 1600

1600

1600

1600

1600

1600

1600

2000

2000

2000

2000

2500

2500

2500

3150

3150

































20

20

20









20

20





20

20



20



25

25

25









25

25





25

25



25



31.5

31.5

31.5









31.5

31.5





31,5

31.5



31.5









40

40





40

40







40



40













50

50





50

50





50



50

































20

20

20









20

20





20

20



20



25

25

25









25

25





25

25



25



31.5

31.5

31.5









31.5

31.5





31.5

31.5



31.5









40

40





40

40







40



40













50

50





50

50





50



50

































50

50

50









50

50





50

50



50



63

63

63









63

63





63

63



63



80

80

80









80

80





80

80



80









100

100





100

100







100



100













125

125





125

125





125



125

































599

599

599

589

589

610

610

599

599

610

610

599

599

610

635

636

450

570

700

570

700

600

750

570

700

600

750

570

700

750

700

750

424

424

424

424

424

459

459

424

424

459

459

424

424

459

424

459

150

210

275

210

275

210

275

210

275

210

275

210

275

275

275

275

93

98

105

84

84

146

158

98

105

146

158

98

105

163

140

177



7407

7408









7407

7408





7407

7408









003282 003285 003440 003441 —



003440 003441 —



003441 000149 003443

33 ... 60 10 ... 15 43 ... 75 60 ... 80

000050 — - 5 ... + 40 • •

13

2. Selection and ordering Withdrawable circuit-breakers

Fixed VD4 circuit-breaker (17.5 kV)

Circuit-breaker

VD4 17 (1) IEC 62271-100 •

Standards

VDE 0671; CEI EN 62271-100- File 7642 •

Rated voltage

Ur [kV] 17.5

Rated insulation voltage

Us [kV] 17.5

Withstand voltage at 50 Hz

Ud (1 min) [kV] 38

Impulse withstand voltage

Up [kV] 95

Rated frequency

fr [Hz] 50-60

Rated normal current (40 °C)

Ir [A] 630

Rated breaking capacity (rated short-circuit breaking current symmetrical)

Isc [kA]

Rated short-time withstand current (3s)

Ik [kA]

Making capacity

Ip [kA]

Operation sequence

630

630

1250

1250

1250

1250

1250

1250

1250

16

16

16

16

16

16









20

20

20

20

20

20









25

25

25

25

25

25









31.5

31.5

31.5

31.5

31.5

31.5





















40

40





















50

50

16

16

16

16

16

16









20

20

20

20

20

20









25

25

25

25

25

25









31.5

31.5

31.5

31.5

31.5

31.5





















40

40





















50

50

40

40

40

40

40

40









50

50

50

50

50

50









63

63

63

63

63

63









80

80

80

80

80

80





















100

100





















125

125



















610

[O - 0.3 s - CO - 15 s - CO] •

Opening time

[ms] 33 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 43 ... 75

Closing time

[ms] 60 ... 80 P P

Maximum overall dimensions

H W

D

461

461

461

589

589

610

700

450

570

700

570

700

600

750

D [mm] 424

424

424

424

424

424

424

424

459

459

TN 7405 1VCD —

Operating temperature

210

275

150

210

275

210

275

210

275

75

79

73

75

79

84

84

146

158

7406



7405

7406













000051 —



000051 003282 003285 003440 003441

[°C] - 5 ... + 40 IEC: 60068-2-30, 60721-2-1 • IEC: 62271-1 •

(1) Circuit-breakers up to 1250 A and 31.5 kA have polyamide poles.

14

461

570

[kg] 73

Standardised table of dimensions

Tropicalization

461

W [mm] 450 Pole distance P [mm] 150

Weight

Electromagnetic compatibility

H [mm] 461

• • 17.5 17.5 38 95 50-60 1600

1600

1600

1600

1600

1600

2000

2000

2000

2000

2500

2500

2500

3150

3150































20

20









20

20





20

20



20



25

25









25

25





25

25



25



31.5

31.5









31.5

31.5





31.5

31.5



31.5







40

40





40

40







40



40











50

50





50

50





50



50































20

20









20

20





20

20



20



25

25









25

25





25

25



25



31.5

31.5









31.5

31.5





31.5

31.5



31.5







40

40





40

40







40



40











50

50





50

50





50



50































50

50









50

50





50

50



50



63

63









63

63





63

63



63



80

80









80

80





80

80



80







100

100





100

100







100



100











125

125





125

125





125



125































599

599

589

589

610

610

599

599

610

610

599

599

610

635

636

570

700

570

700

600

750

570

700

600

750

570

700

750

700

750

424

424

424

424

459

459

424

424

459

459

424

424

459

424

459

210

275

210

275

210

275

210

275

210

275

210

275

275

275

275

98

105

84

84

146

158

98

105

146

158

98

105

163

140

177

7407

7408









7407

7408





7407

7408











003282

003285

003440

003441





003440

003441





003441

000149

003443

33 ... 60 10 ... 15 43 ... 75 60 ... 80

- 5 ... + 40 • •

15

2. Selection and ordering Withdrawable circuit-breakers

Fixed VD4 circuit-breaker (24 kV)

Circuit-breaker

VD4 24 IEC 62271-100 •

Standards

VDE 0671; CEI EN 62271-100- File 7642 •

Rated voltage

Ur [kV] 24

Rated insulation voltage

Us [kV] 24

Withstand voltage at 50 Hz

Ud (1 min) [kV] 50

Impulse withstand voltage

Up [kV] 125

Rated frequency

fr [Hz] 50-60

Rated normal current (40 °C)

Ir [A] 630

630

1250

1250

1600

2000

2500

16

16

16

16

16

16



20

20

20

20

20

20



25

25

25

25

25

25

25





31.5



31.5

31.5

31.5

16

16

16

16

16

16



20

20

20

20

20

20



25

25

25

25

25

25

25





31.5



31.5

31.5

31.5

40

40

40

40

40

40



50

50

50

50

50

50



63

63

63

63

63

63

63





80



80

80

80

[O - 0.3 s - CO - 15 s - CO] •













H [mm] 631

631

631

631

642

642

642

W [mm] 570

700

570

700

700

700

700

D [mm] 424

424

424

424

424

424

424

Pole distance P [mm] 210

275

210

275

275

275

275

[kg] 100

104

110

110

110

7410

7411

7411

7411









Rated breaking capacity (rated short-circuit breaking current symmetrical)

Rated short-time withstand current (3s)

Making capacity

Isc [kA]

Ik [kA]

Ip [kA]

Operation sequence Opening time

[ms] 33 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 43 ... 75

Closing time

[ms] 60 ... 80 P P

Maximum overall dimensions

H W

D

Weight Standardised table of dimensions Operating temperature Tropicalization Electromagnetic compatibility (1) 31.5 kA version.

16

TN 7409 1VCD – [°C] - 5 ... + 40 IEC: 60068-2-30, 60721-2-1 • IEC: 62271-1 •

104

100/106

7410

7409



000172

(1)

(1)

Fixed VD4 circuit-breaker (36 kV)

Circuit-breaker

VD4 36 IEC 62271-100 •

Standards

VDE 0671; CEI EN 62271-100- File 7642 •

Rated voltage

Ur [kV] 36

Rated insulation voltage

Us [kV] 36

Withstand voltage at 50 Hz

Ud (1 min) [kV] 70

Impulse withstand voltage

Up [kV] 170

Rated frequency

fr [Hz] 50-60

Rated normal current (40 °C)

Ir [A] 1250

Rated breaking capacity (rated short-circuit breaking current symmetrical)

Rated short-time withstand current (3s)

Making capacity Operation sequence

1600

2000

2500 (*)







31,5

31,5

31,5

















— Isc [kA] 31,5

Ik [kA] 31,5

31,5

31,5

31,5

















Ip [kA] 80

80

80

80















H [mm] 564

564

564



W [mm] 778

778

778

­—

D [mm] 468

468

468



Pole distance P [mm] 275

275

275



[kg] 150

150

170



1VYN300901-LT

1VYN300901-LT



[O - 0.3 s - CO - 15 s - CO] •

Opening time

[ms] 35 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 45 ... 75

Closing time

[ms] 60 ... 80 P P

Maximum overall dimensions

H W

D

Weight Standardised table of dimensions Operating temperature Tropicalization Electromagnetic compatibility

TN 1VYN300901-LT [°C] - 5 ... + 40 IEC: 60068-2-30, 60721-2-1 • IEC: 62271-1 •

(*) Contact ABB.

17

2. Selection and ordering Withdrawable circuit-breakers

Types of fixed version circuit-breakers available Complete the circuit-breaker selected with the optional accessories indicated on the following pages.

VD4 fixed circuit-breaker without bottom and top terminals (12 kV) Ur

kV

Isc

kA

Rated uninterrupted current (40°C) [A] H=461

H=589

H=599

H=610

H=636

D=424

D=424

D=424

D=459

D=459

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

l/g=217.5

l/g=238

l/g=237.5

l/g=237

l/g=237

P=150

P=210

P=275

P=210

P=275

P=150

P=210

P=275

P=210

P=275

P=275

W=450

W=570

W=700

W=570

W=700

W=450

W=570

W=700

W=600

W=750

W=750

16

630

VD4 12.06.16 p150

20

630

VD4 12.06.20 p150

25

630

VD4 12.06.25 p150

31.5

630

VD4 12.06.32 p150

16

1250

VD4 12.12.16 p150

20

1250

VD4 12.12.20 p150

25

1250

VD4 12.12.25 p150

31.5

1250

VD4 12.12.32 p150

20

1600

VD4 12.16.20 p150

25

1600

VD4 12.16.25 p150

31.5 16

12

1600

VD4 12.16.32 p150

630

VD4 12.06.16 p210

20

630

VD4 12.06.20 p210

25

630

VD4 12.06.25 p210

31.5

630

VD4 12.06.32 p210

16

1250

VD4 12.12.16 p210

20

1250

VD4 12.12.20 p210

25

1250

VD4 12.12.25 p210

31.5

1250

40

VD4 12.12.32 p210 1250

VD4 12.12.40 p210

50

1250

VD4 12.12.50 p210

20

1600

VD4 12.16.20 p210

25

1600

VD4 12.16.25 p210

31.5

1600

VD4 12.16.32 p210

40

1600

VD4 12.16.40 p210

50

1600

VD4 12.16.50 p210

20

2000

VD4 12.20.20 p210

25

2000

VD4 12.20.25 p210

31.5

2000

VD4 12.20.32 p210

40

2000

50

VD4 12.20.40 p210 2000

VD4 12.20.50 p210

20

2500

VD4 12.25.20 p210

25

2500

VD4 12.25.25 p210

31.5

2500

VD4 12.25.32 p210

H

= Height of the circuit-breaker.

W

= Width of the circuit-breaker.

D

= Depth of the circuit-breaker.

u/l

= Distance between bottom and top terminal.

l/g

= Distance between the bottom terminal and the resting surface of the circuit-breaker.

P

= Pole horizontal centre distance.

18

Circuit-breaker type

VD4 fixed circuit-breaker without bottom and top terminals (12 kV) Ur

kV

Isc

kA

Rated uninterrupted current (40°C) [A] H=461

H=589

H=599

H=610

H=636

D=424

D=424

D=424

D=459

D=459

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

l/g=217.5

l/g=238

l/g=237.5

l/g=237

l/g=237

P=150

P=210

P=275

P=210

P=275

P=150

P=210

P=275

P=210

P=275

P=275

W=450

W=570

W=700

W=570

W=700

W=450

W=570

W=700

W=600

W=750

W=750

16

630

VD4 12.06.16 p275

20

630

VD4 12.06.20 p275

25

630

VD4 12.06.25 p275

31.5

630

VD4 12.06.32 p275

16

1250

VD4 12.12.16 p275

20

1250

VD4 12.12.20 p275

25

1250

VD4 12.12.25 p275

31.5

1250

40

VD4 12.12.32 p275 1250

VD4 12.12.40 p275

50

1250

VD4 12.12.50 p275

20

1600

VD4 12.16.20 p275

25

1600

VD4 12.16.25 p275

31.5

1600

VD4 12.16.32 p275

40

12

Circuit-breaker type

1600

VD4 12.16.40 p275

50

1600

VD4 12.16.50 p275

20

2000

VD4 12.20.20 p275

25

2000

VD4 12.20.25 p275

31.5

2000

VD4 12.20.32 p275

40

2000

50

VD4 12.20.40 p275 2000

VD4 12.20.50 p275

20

2500

VD4 12.25.20 p275

25

2500

VD4 12.25.25 p275

31.5

2500

VD4 12.25.32 p275

40

2500

50

VD4 12.25.40 p275 2500

VD4 12.25.50 p275

20

3150

VD4 12.32.20 p275

25

3150

VD4 12.32.25 p275

31.5

3150

VD4 12.32.32 p275

40

3150

VD4 12.32.40 p275

50

3150

VD4 12.32.50 p275

H

= Height of the circuit-breaker.

W

= Width of the circuit-breaker.

D

= Depth of the circuit-breaker.

u/l

= Distance between bottom and top terminal.

l/g

= Distance between the bottom terminal and the resting surface of the circuit-breaker.

P

= Pole horizontal centre distance.

19

2. Selection and ordering Withdrawable circuit-breakers

VD4 fixed circuit-breaker without bottom and top terminals (17.5 kV) Ur

Isc

kV

kA

17.5

Rated uninterrupted current (40 °C) [A] H=461

H=589

H=599

H=610

H=635

D=424

D=424

D=424

D=459

D=459

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

l/g=217.5

l/g=238

l/g=237.5

l/g=237

l/g=237.5

P=150

P=210

P=275

P=210

P=275

P=150

P=210

P=275

P=210

P=275

P=275

W=450

W=570

W=700

W=570

W=700

W=450

W=570

W=700

W=600

W=750

W=750

16

630

VD4 17.06.16 p150

20

630

VD4 17.06.20 p150

25

630

VD4 17.06.25 p150

31.5

630

VD4 17.06.32 p150

16

1250

VD4 17.12.16 p150

20

1250

VD4 17.12.20 p150

25

1250

VD4 17.12.25 p150

31.5

1250

VD4 17.12.32 p150

16

630

VD4 17.06.16 p210

20

630

VD4 17.06.20 p210

25

630

VD4 17.06.25 p210

31.5

630

VD4 17.06.32 p210

16

1250

VD4 17.12.16 p210

20

1250

VD4 17.12.20 p210

25

1250

VD4 17.12.25 p210

31.5

1250

40

VD4 17.12.32 p210 1250

VD4 17.12.40 p210

50

1250

VD4 17.12.50 p210

20

1600

VD4 17.16.20 p210

25

1600

VD4 17.16.25 p210

31.5

1600

VD4 17.16.32 p210

40

1600

VD4 17.16.40 p210

50

1600

VD4 17.16.50 p210

20

2000

VD4 17.20.20 p210

25

2000

VD4 17.20.25 p210

31.5

2000

VD4 17.20.32 p210

40

2000

50

VD4 17.20.40 p210 2000

VD4 17.20.50 p210

20

2500

VD4 17.25.20 p210

25

2500

VD4 17.25.25 p210

31.5

2500

VD4 17.25.32 p210

H

= Height of the circuit-breaker.

W

= Width of the circuit-breaker.

D

= Depth of the circuit-breaker.

u/l

= Distance between bottom and top terminal.

l/g

= Distance between the bottom terminal and the resting surface of the circuit-breaker.

P

= Pole horizontal centre distance.

20

Circuit-breaker type

VD4 fixed circuit-breaker without bottom and top terminals (17.5 kV) Ur

Isc

kV

kA

Rated uninterrupted current (40 °C) [A] H=461

H=589

H=599

H=610

H=635

D=424

D=424

D=424

D=459

D=459

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

l/g=217.5

l/g=238

l/g=237.5

l/g=237

l/g=237.5

P=150

P=210

P=275

P=210

P=275

P=150

P=210

P=275

P=210

P=275

P=275

W=450

W=570

W=700

W=570

W=700

W=450

W=570

W=700

W=600

W=750

W=750

16

630

VD4 17.06.16 p275

20

630

VD4 17.06.20 p275

25

630

VD4 17.06.25 p275

31.5

630

VD4 17.06.32 p275

16

1250

VD4 17.12.16 p275

20

1250

VD4 17.12.20 p275

25

1250

VD4 17.12.25 p275

31.5

1250

40

VD4 17.12.32 p275 1250

VD4 17.12.40 p275

50

1250

VD4 17.12.50 p275

20

1600

VD4 17.16.20 p275

25

1600

VD4 17.16.25 p275

31.5

1600

VD4 17.16.32 p275

40

17.5

Circuit-breaker type

1600

VD4 17.16.40 p275

50

1600

VD4 17.16.50 p275

20

2000

VD4 17.20.20 p275

25

2000

VD4 17.20.25 p275

31.5

2000

VD4 17.20.32 p275

40

2000

50

VD4 17.20.40 p275 2000

VD4 17.20.50 p275

20

2500

VD4 17.25.20 p275

25

2500

VD4 17.25.25 p275

31.5

2500

VD4 17.25.32 p275

40

2500

50

VD4 17.25.40 p275 2500

VD4 17.25.50 p275

20

3150

VD4 17.32.20 p275

25

3150

VD4 17.32.25 p275

31.5

3150

VD4 17.32.32 p275

40

3150

VD4 17.32.40 p275

50

3150

VD4 17.32.50 p275

H

= Height of the circuit-breaker.

W

= Width of the circuit-breaker.

D

= Depth of the circuit-breaker.

u/l

= Distance between bottom and top terminal.

l/g

= Distance between the bottom terminal and the resting surface of the circuit-breaker.

P

= Pole horizontal centre distance.

21

2. Selection and ordering Withdrawable circuit-breakers

VD4 fixed circuit-breaker without bottom and top terminals (24 kV) Ur

Isc

kV

kA

24

H W D u/l l/g P

22

= = = = = =

Rated uninterrupted current (40 °C) [A] H=631

H=642

D=424

D=424

u/l=310

u/l=310

l/g=282.5

Circuit-breaker type

l/g=282.5

P=210

P=275

P=275

W=570

W=700

W=700

16

630

VD4 24.06.16 p210

20

630

VD4 24.06.20 p210

25

630

VD4 24.06.25 p210

16

1250

VD4 24.12.16 p210

20

1250

VD4 24.12.20 p210

25

1250

VD4 24.12.25 p210

31.5

1250

VD4 24.12.32 p210

16

630

VD4 24.06.16 p275

20

630

VD4 24.06.20 p275

25

630

VD4 24.06.25 p275

16

1250

VD4 24.12.16 p275

20

1250

VD4 24.12.20 p275

25

1250

VD4 24.12.25 p275

16

1600

VD4 24.16.16 p275

20

1600

VD4 24.16.20 p275

25

1600

VD4 24.16.25 p275

31.5

1600

VD4 24.16.32 p275

16

2000

VD4 24.20.16 p275

20

2000

VD4 24.20.20 p275

25

2000

VD4 24.20.25 p275

31.5

2000

VD4 24.20.32 p275

25

2500

VD4 24.25.25 p275

31.5

2500

VD4 24.25.32 p275

Height of the circuit-breaker. Width of the circuit-breaker. Depth of the circuit-breaker. Distance between bottom and top terminal. Distance between the bottom terminal and the resting surface of the circuit-breaker. Pole horizontal centre distance.

VD4 fixed circuit-breaker without bottom and top terminals (36 kV) Ur

Isc

Rated uninterrupted current (40 °C) [A] H=876 D=478.5

kV

kA

u/l=328 l/g=428.5

Circuit-breaker type

P=275 W=786

36

H W D u/l l/g P (*)

31.5

= = = = = = =

1250 A

VD4 36.12.32 p275

1600 A

VD4 36.16.32 p275

2000 A

VD4 36.20.32 p275

2500 A (* )

VD4 36.25.32 p275

Height of the circuit-breaker. Width of the circuit-breaker. Depth of the circuit-breaker. Distance between bottom and top terminal. Distance between the bottom terminal and the resting surface of the circuit-breaker. Pole horizontal centre distance. Contact ABB.

Standard fittings of fixed circuit-breakers The basic versions of the fixed circuit-breakers are three-pole and fitted with: – EL type manual operating mechanism – mechanical signalling device for closing springs charged/ discharged – mechanical signalling device for circuit-breaker open/closed – closing pushbutton, opening pushbutton and operation counter – set of ten auxiliary circuit-breaker break/make contacts Note: with the group of ten auxiliary contacts supplied as standard and the maximum number of electrical applications, three break contacts (signalling circuit-breaker open) and five make contacts (signalling circuit-breaker closed) are available.

– lever for manually charging the closing springs – auxiliary circuit support terminal board. VD4 - up to 24 kV

VD4 - 36 kV

23

2. Selection and ordering Withdrawable circuit-breakers

Withdrawable version circuit-breakers for UniGear ZS1 switchgear (12 kV)

Circuit-breaker

VD4/P 12 (3) IEC 62271-100 •

Standards

VDE 0671; CEI EN 62271-100- File 7642 •

Rated voltage

Ur [kV] 12

Rated insulation voltage

Us [kV] 12

Withstand voltage at 50 Hz

Ud (1 min) [kV] 28

Impulse withstand voltage

Up [kV] 75

Rated frequency

fr [Hz] 50-60

Rated normal current (40 °C)

Ir [A] 630

(1)

Rated breaking capacity (rated short-circuit breaking current symmetrical)

Rated short-time withstand current (3s)

Making capacity

Isc [kA]

Ik [kA]

Ip [kA]

Operation sequence

1250

1250

1250

1250

1600

1600

16

16











20

20







20

20

25

25







25

25

31.5

31.5







31.5

31.5





40

40















50





16

16











20

20







20

20

25

25







25

25

31.5

31.5







31.5

31.5





40

40















50





40

40











50

50







50

50

63

63







63

63

80

80







80

80





100

100















125

















628

691

691

691

691

691

[ O - 0.3 s - CO - 15 s - CO ] •

Opening time

[ms] 33 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 43 ... 75

Closing time

[ms] 60 ... 80 P P

Maximum overall dimensions

H [mm] 628

H W

D

Weight Standardised table of dimensions Operating temperature Tropicalization Electromagnetic compatibility

W [mm] 503

503

653

853

681

653

853

D [mm] 662

662

641

642

643

642

642

Pole distance P [mm] 150

150

210

275

210

210

275

[kg] 116

116

174

176

180

160

166

7412







7415

7416



003284

003286

003444





TN 7412 1VCD — [°C] - 5 ... + 40 IEC: 60068-2-30, 60721-2-1 • IEC: 62271-1 •

(1) Rated current guaranteed with circuit-breaker installed in UniGear ZS1 switchgear and with 40 °C ambient temperature. (2) Up to 4000 A with forced ventilation. (3) Circuit-breakers up to 1250 A and 31.5 kA have polyamide poles.

24

• • 12 12 28 75 50-60 1600

1600

1600

1600

2000

2000

2000

2000

2500

2500

3150

































20

20





20



20











25

25





25



25











31.5

31.5





31.5



31.5



40

40





40

40





40



40







50

50





50

50



50



50

































20

20





20



20











25

25





25



25











31.5

31.5





31.5



31.5



40

40





40

40





40



40







50

50





50

50



50



50

































50

50





50



50











63

63





63



63











80

80





80



80



100

100





100

100





100



100







125

125





125

125



125



125

























691

691

691

691

691

691

691

691

691

691

730

742

653

853

681

853

653

853

681

853

853

853

853

853

641

642

643

643

642

642

643

643

640

643

640

643

210

275

210

275

210

275

210

275

275

275

275

275

174

176

180

193

160

166

190

205

186

225

221

240









7415

7416





7417







003284

003286

003444

003445





003444

003445



003446

000153

003447

(2)

3150

(2)

33 ... 60 10 ... 15 43 ... 75 60 ... 80

- 5 ... + 40 • •

25

2. Selection and ordering Withdrawable circuit-breakers

Withdrawable version circuit-breakers for UniGear ZS1 switchgear (17.5 kV)

Circuit-breaker

VD4/P 17 (3) IEC 62271-100 •

Standards

VDE 0671; CEI EN 62271-100- File 7642 •

Rated voltage

Ur [kV] 17.5

Rated insulation voltage

Us [kV] 17.5

Withstand voltage at 50 Hz

Ud (1 min) [kV] 38

Impulse withstand voltage

Up [kV] 95

Rated frequency

fr [Hz] 50-60

Rated normal current (40 °C)

Ir [A] 630

(1)

Rated breaking capacity (rated short-circuit breaking current symmetrical)

Rated short-time withstand current (3s)

Making capacity

Isc [kA]

Ik [kA]

Ip [kA]

Operation sequence

1250

1250

1250

1250

1600

1600

16

16











20

20







20

20

25

25







25

25

31.5

31.5







31.5

31.5





40

40















50





16

16











20

20







20

20

25

25







25

25

31.5

31.5







31.5

31.5





40

40















50





40

40











50

50







50

50

63

63







63

63

80

80







80

80





100

100















125

















632

691

691

691

691

691

[O - 0.3 s - CO - 15 s - CO] •

Opening time

[ms] 33 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 43 ... 75

Closing time

[ms] 60 ... 80 P P

Maximum overall dimensions

H [mm] 632

H W

D

Weight Standardised table of dimensions Operating temperature Tropicalization Electromagnetic compatibility

W [mm] 503

503

653

853

681

653

853

D [mm] 664

664

641

642

643

642

642

Pole distance P [mm] 150

150

210

275

210

210

275

[kg] 116

116

174

176

180

160

166

7412







7415

7416



003284

003286

003444





TN 7412 1VCD — [°C] - 5 ... + 40 IEC: 60068-2-30, 60721-2-1 • IEC: 62271-1 •

(1) Rated current guaranteed with circuit-breaker installed in UniGear ZS1 switchgear and with 40 °C ambient temperature. (2) Up to 4000 A with forced ventilation. (3) Circuit-breakers up to 1250 A and 31.5 kA have polyamide poles.

26

• • 17,5 17,5 38 95 50-60 1600

1600

1600

1600

2000

2000

2000

2000

2500

2500

3150

































20

20





20



20











25

25





25



25











31,5

31,5





31,5



31,5



40

40





40

40





40



40







50

50





50

50



50



50

































20

20





20



20











25

25





25



25











31,5

31,5





31,5



31,5



40

40





40

40





40



40







50

50





50

50



50



50

































50

50





50



50











63

63





63



63











80

80





80



80



100

100





100

100





100



100







125

125





125

125



125



125

























691

691

691

691

691

691

691

691

691

691

730

742

653

853

681

853

653

853

681

853

853

853

853

853

641

642

643

643

642

642

643

643

640

643

640

643

210

275

210

275

210

275

210

275

275

275

275

275

174

176

180

193

160

166

190

205

186

225

221

240









7415

7416





7417







003284

003286

003444

003445





003444

003445



003446

000153

003447

(2)

3150

(2)

33 ... 60 10 ... 15 43 ... 75 60 ... 80

- 5 ... + 40 • •

27

2. Selection and ordering Withdrawable circuit-breakers

Withdrawable version circuit-breakers for UniGear ZS1 switchgear (24 kV)

Circuit-breaker Standards

VD4/P 24 IEC 62271-100 • VDE 0671; CEI EN 62271-100- File 7642 •

Rated voltage

Ur [kV] 24

Rated insulation voltage

Us [kV] 24

Withstand voltage at 50 Hz

Ud (1 min) [kV] 50

Impulse withstand voltage

Up [kV] 125

Rated frequency

fr [Hz] 50-60

Rated normal current (40 °C)

Ir [A] 630

(1)

Rated breaking capacity (rated short-circuit breaking current symmetrical)

Isc [kA]

Rated short-time withstand current (3s)

Making capacity

Ik [kA]

Ip [kA]

Operation sequence

1600

2000

2500

(2)

3150

16

16

16

16

16

16



20

20

20

20

20

20



25

25

25

25

25

25

25







31.5



31.5

31.5

31.5

31.5

16

16

16

16

16

16

16



20

20

20

20

20

20

20



25

25

25

25

25

25

25







31.5



31.5

31.5

31.5

31.5

40

40

40

40

40

40

40



50

50

50

50

50

50

50



63

63

63

63

63

63

63







80



80

80

80

80

[O - 0.3 s - CO - 15 s - CO] •















Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 43 ... 75

Closing time

(3)

[ms] 60 ... 80 P P

H W

D

Weight Standardised table of dimensions Operating temperature Tropicalization Electromagnetic compatibility

28

1250

16

[ms] 33 ... 60

(1) (2) (3) (4)

1250

20

Opening time

Maximum overall dimensions

630

H [mm] 794

794

794

794

838

838

838

838

W [mm] 653

853

653

853

853

853

853

853

D [mm] 802

802

802

802

790

790

790

790

Pole distance P [mm] 210

275

210

275

275

275

275

275

[kg] 140

148

140/146

7414

7413



000173

TN 7413 1VCD –

(4)

(4)

148

228

228

228

277

7414

7418

7418

7418











000177

[°C] - 5 ... + 40 IEC: 60068-2-30, 60721-2-1 • IEC: 62271-1 •

Rated current guaranteed with circuit-breaker installed in UniGear ZS1 switchgear and with 40 °C ambient temperature. 2300 A rated current guaranteed with natural ventilation; 2500 A rated current guaranteed with forced ventilation. 2700 A rated current guaranteed with natural ventilation; 3150 A rated current guaranteed with forced ventilation. 31.5 kA version.

General characteristics of withdrawable circuit-breakers for UniGear ZS2 and PowerCube modules (36 kV)

Circuit-breaker

VD4/W 36 IEC 62271-100 •

Standards

VDE 0671; CEI EN 62271-100- File 7642 •

Rated voltage

Ur [kV] 36

Rated insulation voltage

Us [kV] 36

Withstand voltage at 50 Hz

Ud (1 min) [kV] 70

Impulse withstand voltage

Up [kV] 170

Rated frequency

fr [Hz] 50-60

Rated normal current (40 °C)

Ir [A] 1250

(1)

Rated breaking capacity (rated short-circuit breaking current symmetrical)

Rated short-time withstand current (3s)

Making capacity Operation sequence

1600

2000

2500 (*)







31,5

31,5

31,5

















31,5

31,5

31,5

















Ip [kA] 80

80

80

80















— Isc [kA] 31,5

Ik [kA] 31,5

[O - 0.3 s - CO - 15 s - CO] •

Opening time

[ms] 33 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 45 ... 75

Closing time

[ms] 60 ... 80 P P

Maximum overall dimensions

H W

D

Weight Standardised table of dimensions Operating temperature Tropicalization Electromagnetic compatibility

H [mm] 973

973

973

973

W [mm] 842

842

842

842

D [mm] 788

788

788

788

Pole distance P [mm] 275

275

275

275

[kg] 230

230

230



1VYN300901-KG

1VYN300901-KG



TN 1VYN300901-KG [°C] - 5 ... + 40 IEC: 60068-2-30, 60721-2-1 • IEC: 62271-1 •

(*) Ask ABB

29

2. Selection and ordering Withdrawable circuit-breakers

Types of withdrawable version circuit-breakers available for UniGear ZS1 switchgear Complete the circuit-breaker selected with the optional accessories indicated on the following pages.

VD4 (12 kV) withdrawable circuit-breaker Ur

kV

12

W = P = u/l = ø =

30

Isc

kA

Rated uninterrupted current (40 °C) [A] W=650

W=800

W=1000

W=1000

W=1000

P=150

P=210

P=275

P=275

P=275

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

ø=35

ø=79

ø=79

ø=109

ø=109

Circuit-breaker type

16

630

VD4/P 12.06.16 p150

20

630

VD4/P 12.06.20 p150

25

630

VD4/P 12.06.25 p150

31.5

630

VD4/P 12.06.32 p150

16

1250

VD4/P 12.12.16 p150

20

1250

VD4/P 12.12.20 p150

25

1250

VD4/P 12.12.25 p150

31.5

1250

VD4/P 12.12.32 p150

40

1250

VD4/P 12.12.40 p210

50

1250

VD4/P 12.12.50 p210

20

1600

VD4/P 12.16.20 p210

25

1600

VD4/P 12.16.25 p210

31.5

1600

VD4/P 12.16.32 p210

40

1600

VD4/P 12.16.40 p210

50

1600

VD4/P 12.16.50 p210

20

2000

VD4/P 12.20.20 p210

25

2000

VD4/P 12.20.25 p210

31.5

2000

VD4/P 12.20.32 p210

40

2000

VD4/P 12.20.40 p210

50

2000

VD4/P 12.20.50 p210

40

1250

VD4/P 12.12.40 p275

20

1600

VD4/P 12.16.20 p275

25

1600

VD4/P 12.16.25 p275

31.5

1600

VD4/P 12.16.32 p275

40

1600

VD4/P 12.16.40 p275

50

1600

VD4/P 12.16.50 p275

20

2000

VD4/P 12.20.20 p275

25

2000

VD4/P 12.20.25 p275

31.5

2000

VD4/P 12.20.32 p275

40

2000

VD4/P 12.20.40 p275

50

2000

VD4/P 12.20.50 p275

Width of the circuit-breaker. Pole horizontal centre distance. Distance between bottom and top terminal. Diameter of the isolating contact.

VD4 (12 kV) withdrawable circuit-breaker Ur

kV

12

Isc

kA

Rated uninterrupted current (40 °C) [A] W=650

W=800

W=1000

W=1000

W=1000

P=150

P=210

P=275

P=275

P=275

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

ø=35

ø=79

ø=79

ø=109

ø=109

Circuit-breaker type

20

2500

VD4/P 12.25.20 p275

25

2500

VD4/P 12.25.25 p275

31,5

2500

VD4/P 12.25.32 p275

40

2500

VD4/P 12.25.40 p275

50

2500

VD4/P 12.25.50 p275

20

3150 (1)

VD4/P 12.32.20 p275

25

3150

(1)

VD4/P 12.32.25 p275

31,5

3150

(1)

VD4/P 12.32.32 p275

40

3150

(1)

VD4/P 12.32.40 p275

50

3150

(1)

VD4/P 12.32.50 p275

W = Width of the circuit-breaker. P = Pole horizontal centre distance. u/l = Distance between bottom and top terminal. ø = Diameter of the isolating contact. (1) Up to 4000 A with forced ventilation.

31

2. Selection and ordering Withdrawable circuit-breakers

VD4 (17.5 kV) withdrawable circuit-breaker for UniGear ZS1 switchboard Ur

kV

17.5

W = P = u/l = ø =

32

Isc

kA

Rated uninterrupted current (40 °C) [A] W=650

W=800

W=1000

W=1000

W=1000

P=150

P=210

P=275

P=275

P=275

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

ø=35

ø=79

ø=79

ø=109

ø=109

Circuit-breaker type

16

630

VD4/P 17.06.16 p150

20

630

VD4/P 17.06.20 p150

25

630

VD4/P 17.06.25 p150

31.5

630

VD4/P 17.06.32 p150

16

1250

VD4/P 17.12.16 p150

20

1250

VD4/P 17.12.20 p150

25

1250

VD4/P 17.12.25 p150

31.5

1250

VD4/P 17.12.32 p150

40

1250

VD4/P 17.12.40 p210

50

1250

VD4/P 17.12.50 p210

20

1600

VD4/P 17.16.20 p210

25

1600

VD4/P 17.16.25 p210

31.5

1600

VD4/P 17.16.32 p210

40

1600

VD4/P 17.16.40 p210

50

1600

VD4/P 17.16.50 p210

20

2000

VD4/P 17.20.20 p210

25

2000

VD4/P 17.20.25 p210

31.5

2000

VD4/P 17.20.32 p210

40

2000

VD4/P 17.20.40 p210

50

2000

VD4/P 17.20.50 p210

40

1250

VD4/P 17.12.40 p275

20

1600

VD4/P 17.16.20 p275

25

1600

VD4/P 17.16.25 p275

31.5

1600

VD4/P 17.16.32 p275

40

1600

VD4/P 17.16.40 p275

50

1600

VD4/P 17.16.50 p275

20

2000

VD4/P 17.20.20 p275

25

2000

VD4/P 17.20.25 p275

31.5

2000

VD4/P 17.20.32 p275

40

2000

VD4/P 17.20.40 p275

50

2000

VD4/P 17.20.50 p275

Width of the circuit-breaker. Pole horizontal centre distance. Distance between bottom and top terminal. Diameter of the isolating contact.

VD4 (17.5 kV) withdrawable circuit-breaker for UniGear ZS1 switchboard Ur

kV

17.5

Isc

kA

Rated uninterrupted current (40 °C) [A] W=650

W=800

W=1000

W=1000

W=1000

P=150

P=210

P=275

P=275

P=275

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

ø=35

ø=79

ø=79

ø=109

ø=109

Circuit-breaker type

20

2500

VD4/P 17.25.20 p275

25

2500

VD4/P 17.25.25 p275

31.5

2500

VD4/P 17.25.32 p275

40

2500

VD4/P 17.25.40 p275

50

2500

VD4/P 17.25.50 p275

20

3150

(1)

VD4/P 17.32.20 p275

25

3150

(1)

VD4/P 17.32.25 p275

31.5

3150

(1)

VD4/P 17.32.32 p275

40

3150

(1)

VD4/P 17.32.40 p275

50

3150

(1)

VD4/P 17.32.50 p275

W = Width of the circuit-breaker. P = Pole horizontal centre distance. u/l = Distance between bottom and top terminal. ø = Diameter of the isolating contact. (1) Up to 4000 A with forced ventilation.

33

2. Selection and ordering Withdrawable circuit-breakers

VD4 (24 kV) withdrawable circuit-breaker for UniGear ZS1 switchboard Ur

kV

Isc

kA

W=800

W=1000

W=1000

W=1000

P=210

P=275

P=275

P=275

u/l=310

u/l=310

u/l=310

u/l=310

ø=35

ø=35

ø=79

ø=109

630

VD4/P 24.06.16 p210

20

630

VD4/P 24.06.20 p210

25

630

VD4/P 24.06.25 p210

16

1250

VD4/P 24.12.16 p210

20

1250

VD4/P 24.12.20 p210

25

1250

VD4/P 24.12.25 p210

31.5

1250

VD4/P 24.12.32 p210 630

VD4/P 24.06.16 p275

20

630

VD4/P 24.06.20 p275

25

630

VD4/P 24.06.25 p275

16

1250

VD4/P 24.12.16 p275

20

1250

VD4/P 24.12.20 p275

25

1250

VD4/P 24.12.25 p275

16

1600

VD4/P 24.16.16 p275

20

1600

VD4/P 24.16.20 p275

25

1600

VD4/P 24.16.25 p275

31.5

1600

VD4/P 24.16.32 p275

16

2000

VD4/P 24.20.16 p275

20

2000

VD4/P 24.20.20 p275

25

2000

VD4/P 24.20.25 p275

31.5

2000

VD4/P 24.20.32 p275

16

2300

(1)

VD4/P 24.25.16 p275

20

2300

(1)

VD4/P 24.25.20 p275

25

2300

(1)

VD4/P 24.25.25 p275

31.5

2300

(1)

31.5 W = Width of the switchgear. P = Pole horizontal centre distance. u/l = Distance between bottom and top terminal. ø = Diameter of the isolating contact. (1) 2500 A rated current guaranteed with forced ventilation. (2) 3150 A rated current guaranteed with forced ventilation.

34

Circuit-breaker type

16

16

24

Rated uninterrupted current (40 °C) [A]

VD4/P 24.25.32 p275 2700

(2)

VD4/P 24.32.32 p275

VD4 (36 kV) withdrawable circuit-breaker Ur

Isc

Rated uninterrupted current (40 °C) [A] H=951 D=788

kV

kA

u/l=380

Circuit-breaker type

ø=399 P=275 W=778

31.5

36

1250 A

VD4/W 36.12.32 p275

1600 A

VD4/W 36.16.32 p275

2000 A

VD4/W 36.20.32 p275

2500 A *

( )

H D u/l ø P W (*)

= = = = = = =

VD4/W 36.25.32 p275

Height of the circuit-breaker. Depth of the circuit-breaker. Distance between bottom and top terminal. Diameter of the isolating contact. Pole horizontal centre distance. Width of the circuit-breaker. Contact ABB.

Standard fittings of withdrawable circuit-breakers for UniGear ZS1, ZS2 switchgear and similar panels The basic versions of the withdrawable circuit-breakers are three-pole and fitted with: – EL type manual operating mechanism – mechanical signalling device for closing springs charged/ discharged – mechanical signalling device for circuit-breaker open/closed – closing pushbutton – opening pushbutton – operation counter – set of ten circuit-breaker open/closed auxiliary contacts

– locking electromagnet in the truck (compulsory for ABB switchgear). This device prevents racking the circuit-breaker into the switchgear with the auxiliary circuits disconnected (plug not inserted in the socket) – door interlock (compulsory for ABB switchgear); this device prevents racking the circuit-breaker into the switchgear when the switchgear door is open.

Note: with the group of ten auxiliary contacts supplied as standard and the maximum number of electrical applications, three break contacts (signalling circuit-breaker open) and four make contacts (signalling circuit-breaker closed) are available.

– lever for manually charging the closing springs – isolating contacts – cord with connector (plug only) for auxiliary circuits, with striker pins which does not allow the plug to be inserted into the socket if the rated current of the circuit-breaker is lower than the rated current of the panel – racking-out/in lever (the quantity must be defined according to the number of pieces of apparatus ordered)

VD4 – up to 24 kV

VD4 - 36 kV

35

2. Selection and ordering Withdrawable circuit-breakers

Withdrawable version circuit-breakers for PowerCube modules (12 kV)

Circuit-breaker

VD4/P 12 ( 3)

VD4/W 12 (3)

PowerCube module PB1

PB2

IEC 62271-100 •

Standards



VDE 0671; CEI EN 62271-100- File 7642 •

Rated voltage Rated insulation voltage Withstand voltage at 50 Hz Impulse withstand voltage Rated frequency



Ur [kV] 12

12

Us [kV] 12

12

Ud (1 min) [kV] 28

28

Up [kV] 75

75

fr [Hz] 50-60

Rated normal current (40 °C)

Ir [A] 630

(1)

Rated breaking capacity (rated short-circuit breaking current symmetrical)

Isc [kA]

Rated short-time withstand current (3s)

Ik [kA]

Making capacity

Ip [kA]

Operation sequence

50-60 1250

630

1250

16

16

16

16

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

















16

16

16

16

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

















40

40

40

40

50

50

50

50

63

63

63

63

80

80

80

80

















[O - 0.3 s - CO - 15 s - CO] •



Opening time

[ms] 33 ... 60

33 ... 60

Arcing time

[ms] 10 ... 15

10 ... 15

Total breaking time

[ms] 43 ... 75

43 ... 75

Closing time

[ms] 60 ... 80 P P

Maximum overall dimensions

H W

D

Weight Standardised table of dimensions Operating temperature Tropicalization Electromagnetic compatibility

60 ... 80

H [mm] 628

628

691

691

W [mm] 503

503

653

853

D [mm] 662

662

642

642

Pole distance P [mm] 150

150

210

210

[kg] 116

116

135

135

7412

7420

7420







TN 7412 1VCD — [°C] - 5 ... + 40 IEC: 60068-2-30, 60721-2-1 •



IEC: 62271-1 •



(1) Rated current guaranteed with circuit-breaker installed in PowerCube enclosure and with 40 °C ambient temperature (2) Up to 4000 A with forced ventilation. (3) Circuit-breakers up to 1250 A and 31.5 kA have polyamide poles.

36

- 5 ... + 40

VD4/P 12

VD4/W 12

PB2

PB3

PB3













12

12

12

12

12

12

28

28

28

75

75

75

50-60

50-60

50-60

1250

1250

1600

1600

1600

2000

2000

2500

2500

3150



























20





20



20



20







25





25



25



25







31.5





31.5



31.5



31.5



40





40



40



40



40





50





50



50



50



50



























20





20



20



20







25





25



25



25







31.5





31.5



31.5



31.5



40





40



40



40



40





50





50



50



50



50



























50





50



50



50







63





63



63



63







80





80



80



80



100





100



100



100



100





125





125



125



125



125







33 ... 60

33 ... 60

33 ... 60

10 ... 15

10 ... 15

10 ... 15

43 ... 75

43 ... 75

43 ... 75

60 ... 80

60 ... 80

60 ... 80

(2)

3150 (2)

691

691

691

691

691

690

691

691

691

730

691

653

681

653

653

681

653

681

853

853

853

853

641

643

642

641

643

642

643

640

643

640

643

210

210

210

210

210

210

210

275

275

275

275

174

180

160

174

180

160

190

186

225

221

240





7415





7415



7417







003284

003444



003284

003444



003444



003445

000152

003596

- 5 ... + 40

- 5 ... + 40

- 5 ... + 40













37

2. Selection and ordering Withdrawable circuit-breakers

Withdrawable version circuit-breakers for PowerCube modules (17.5 kV)

Circuit-breaker

VD4/P 17 ( 3)

VD4/W 17 (3)

PowerCube module PB1

PB2

IEC 62271-100 •

Standards



VDE 0671; CEI EN 62271-100- File 7642 •

Rated voltage Rated insulation voltage Withstand voltage at 50 Hz Impulse withstand voltage Rated frequency



Ur [kV] 17.5

17.5

Us [kV] 17.5

17.5

Ud (1 min) [kV] 38

38

Up [kV] 95

95

fr [Hz] 50-60

Rated normal current (40 °C)

Ir [A] 630

(1)

Rated breaking capacity (rated short-circuit breaking current symmetrical)

Isc [kA]

Rated short-time withstand current (3s)

Ik [kA]

Making capacity

Ip [kA]

Operation sequence

50-60 1250

630

1250

16

16

16

16

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

















16

16

16

16

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

















40

40

40

40

50

50

50

50

63

63

63

63

80

80

80

80

















[O - 0.3 s - CO - 15 s - CO] •



Opening time

[ms] 33 ... 60

33 ... 60

Arcing time

[ms] 10 ... 15

10 ... 15

Total breaking time

[ms] 43 ... 75

43 ... 75

Closing time

[ms] 60 ... 80 P P

Maximum overall dimensions

H W

Weight Standardised table of dimensions Operating temperature Tropicalization Electromagnetic compatibility

D

60 ... 80

H [mm] 628

628

691

W [mm] 503

503

653

853

D [mm] 662

662

642

642

Pole distance P [mm] 150

150

210

210

[kg] 116

116

135

135

7412

7420

7420







TN 7412 1VCD — [°C] - 5 ... + 40

- 5 ... + 40

IEC: 60068-2-30, 60721-2-1 •



IEC: 62271-1 •



(1) Rated current guaranteed with circuit-breaker installed in PowerCube enclosure and with 40 °C ambient temperature. (2) Up to 4000 A with forced ventilation. (3) Circuit-breakers up to 1250 A and 31.5 kA have polyamide poles.

38

691

VD4/P 17

VD4/W 17

PB2

PB3

PB3













17,5

17,5

17,5

17,5

17,5

17,5

38

38

38

95

95

95

50-60

50-60

50-60

1250

1250

1600

1600

1600

2000

2000

2500

2500

3150



























20





20



20





20





25





25



25





25





31.5





31.5



31.5





31.5

40





40



40



40





40



50





50



50



50

50





























20





20



20





20





25





25



25





25





31.5





31.5



31.5





31.5

40





40



40



40





40



50





50



50



50

50





























50





50



50





50





63





63



63





63





80





80



80





80

100





100



100



100





100



125





125



125



125

125



(2)







33 ... 60

33 ... 60

33 ... 60

10 ... 15

10 ... 15

10 ... 15

43 ... 75

43 ... 75

43 ... 75

60 ... 80

60 ... 80

3150

(2)

60 ... 80

691

691

691

691

691

690

691

691

691

691

730

653

681

653

653

681

653

681

853

853

853

853

641

643

642

641

643

642

643

640

643

643

640

210

210

210

210

210

210

210

275

275

275

275

174

180

160

174

180

160

190

186

225

240

221





7415





7415



7417







003284

003444



003284

003444



003444



003445

003596

000152

- 5 ... + 40

- 5 ... + 40

- 5 ... + 40













39

2. Selection and ordering Withdrawable circuit-breakers

Withdrawable version circuit-breakers for PowerCube modules (24 kV)

Circuit-breaker

VD4/P 24 PowerCube module PB4

Standards

PB5

IEC 62271-100 •



VDE 0671; CEI EN 62271-100- File 7642 •



Rated voltage Rated insulation voltage Withstand voltage at 50 Hz Impulse withstand voltage

Ur [kV] 24

24

Us [kV] 24

24

Ud (1 min) [kV] 50

50

Up [kV] 125

Rated frequency

125

fr [Hz] 50-60

Rated normal current (40 °C)

Ir [A] 630

(1)

Rated breaking capacity (rated short-circuit breaking current symmetrical)

Isc [kA]

Rated short-time withstand current (3s)

Ik [kA]

Making capacity

Ip [kA]

1600

16

16

16

16

20

20

20

20

25

25

25

25

25



31.5

31.5

31.5

31.5

16

16

16

16

16

20

20

20

20

20

25

25

25

25

25



31.5

31.5

31.5

31.5

40

40

40

40

40

50

50

50

50

50

63

63

63

63

63

80

80

80

80









Opening time

[ms] 33 ... 60

33 ... 60

Arcing time

[ms] 10 ... 15

10 ... 15

Total breaking time

[ms] 43 ... 75

43 ... 75

Closing time

[ms] 60 ... 80

Maximum overall dimensions

H W

D

Weight Standardised table of dimensions Operating temperature Tropicalization Electromagnetic compatibility

60 ... 80

H [mm] 794

794

838

838

838

W [mm] 653

653

853

853

853

D [mm] 802

802

790

790

790

275

275

275

228

228

228

7418

7418

7418







Pole distance P [mm] 210 [kg] 140 TN 7413 1VCD –

210 140/146

(3)

7413 000173

(3)

[°C] - 5 ... + 40 IEC: 60068-2-30, 60721-2-1 • IEC: 62271-1 •

(1) Rated current guaranteed with circuit-breaker installed in PowerCube enclosure and with 40 °C ambient temperature. (2) 2300 A rated uninterrupted current guaranteed with natural ventilation; 2500 A rated current guaranteed with forced ventilation. (3) 31.5 kA version.

40

2500

16

[O - 0.3 s - CO - 15 s - CO] •

P P

2000

20

– Operation sequence

50-60 1250

(2)

Types of withdrawable version circuit-breakers available for PowerCube modules Complete the circuit-breaker selected with the optional accessories indicated on the following pages. VD4 withdrawable circuit-breaker (12 kV) Ur

kV

12

Isc

kA

Rated uninterrupted current (40 °C) [A] W=650

W=800

W=1000

W=1000

W=1000

P=150

P=210

P=275

P=275

P=275

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

ø=35

ø=79

ø=79

ø=109

ø=109

Circuit-breaker type

16

630

VD4/P 12.06.16 p150

20

630

VD4/P 12.06.20 p150

25

630

VD4/P 12.06.25 p150

31.5

630

VD4/P 12.06.32 p150

16

1250

VD4/P 12.12.16 p150

20

1250

VD4/P 12.12.20 p150

25

1250

VD4/P 12.12.25 p150

31.5

1250

VD4/P 12.12.32 p150

16

630

VD4/W 12.06.16 p210

20

630

VD4/W 12.06.20 p210

25

630

VD4/W 12.06.25 p210

31.5

630

VD4/W 12.06.32 p210

16

1250

VD4/W 12.12.16 p210

20

1250

VD4/W 12.12.20 p210

25

1250

VD4/W 12.12.25 p210

31.5

1250

VD4/W 12.12.32 p210

40

1250

VD4/P 12.12.40 p210

50

1250

VD4/P 12.12.50 p210

20

1600

VD4/P 12.16.20 p210

25

1600

VD4/P 12.16.25 p210

31.5

1600

VD4/P 12.16.32 p210

40

1600

VD4/P 12.16.40 p210

50

1600

VD4/P 12.16.50 p210

20

2000

VD4/P 12.20.20 p210

25

2000

VD4/P 12.20.25 p210

31.5

2000

VD4/P 12.20.32 p210

40

2000

VD4/P 12.20.40 p210

50

2000

VD4/P 12.20.50 p210

20

2500

VD4/P 12.25.20 p275

25

2500

VD4/P 12.25.25 p275

31.5

2500

VD4/P 12.25.32 p275

40

2500

VD4/P 12.25.40 p275

50

2500

VD4/P 12.25.50 p275

20

3150 (1)

VD4/W 12.32.20 p275

25

3150

(1)

VD4/W 12.32.25 p275

31.5

3150

(1)

VD4/W 12.32.32 p275

40

3150

(1)

VD4/W 12.32.40 p275

50

3150

(1)

VD4/W 12.32.50 p275

W = Width of the switchgear. P = Pole horizontal centre distance. u/l = Distance between bottom and top terminal. ø = Diameter of the isolating contact. (1) Up to 4000 A with forced ventilation.

41

2. Selection and ordering Withdrawable circuit-breakers

VD4 withdrawable circuit-breaker (17.5 kV) Ur

kV

17,5

Isc

kA

Rated uninterrupted current (40 °C) [A] W=650

W=800

W=1000

W=1000

W=1000

P=150

P=210

P=275

P=275

P=275

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

ø=35

ø=79

ø=79

ø=109

ø=109

16

630

VD4/P 17.06.16 p150

20

630

VD4/P 17.06.20 p150

25

630

VD4/P 17.06.25 p150

31.5

630

VD4/P 17.06.32 p150

16

1250

VD4/P 17.12.16 p150

20

1250

VD4/P 17.12.20 p150

25

1250

VD4/P 17.12.25 p150

31.5

1250

VD4/P 17.12.32 p150

16

630

VD4/W 17.06.16 p210

20

630

VD4/W 17.06.20 p210

25

630

VD4/W 17.06.25 p210

31.5

630

VD4/W 17.06.32 p210

16

1250

VD4/W 17.12.16 p210

20

1250

VD4/W 17.12.20 p210

25

1250

VD4/W 17.12.25 p210

31.5

1250

VD4/W 17.12.32 p210

40

1250

VD4/P 17.12.40 p210

50

1250

VD4/P 17.12.50 p210

20

1600

VD4/P 17.16.20 p210

25

1600

VD4/P 17.16.25 p210

31.5

1600

VD4/P 17.16.32 p210

40

1600

VD4/P 17.16.40 p210

50

1600

VD4/P 17.16.50 p210

20

2000

VD4/P 17.20.20 p210

25

2000

VD4/P 17.20.25 p210

31.5

2000

VD4/P 17.20.32 p210

40

2000

VD4/P 17.20.40 p210

50

2000

VD4/P 17.20.50 p210

20

2500

VD4/P 17.25.20 p275

25

2500

VD4/P 17.25.25 p275

31.5

2500

VD4/P 17.25.32 p275

40

2500

VD4/P 17.25.40 p275

50

2500

VD4/P 17.25.50 p275

20

3150

(1)

25

3150

(1)

VD4/W 17.32.25 p275

31.5

3150

(1)

VD4/W 17.32.32 p275

40

3150

(1)

VD4/W 17.32.40 p275

50

3150

(1)

VD4/W 17.32.50 p275

W = Width of the switchgear. P = Pole horizontal centre distance. u/l = Distance between bottom and top terminal. ø = Diameter of the isolating contact. (1) Up to 4000 A with forced ventilation.

42

Circuit-breaker type

VD4/W 17.32.20 p275

VD4 withdrawable circuit-breaker (24 kV) Ur

kV

Isc

kA

W=800

W=1000

P=210

P=275

u/l=310

u/l=310

ø=35

ø=79

Circuit-breaker type

16

630

VD4/P 24.06.16 p210

20

630

VD4/P 24.06.20 p210

25

630

VD4/P 24.06.25 p210

16

1250

VD4/P 24.12.16 p210

20

1250

VD4/P 24.12.20 p210

25

1250

VD4/P 24.12.25 p210

31.5

1250

16 24

Rated uninterrupted current (40 °C) [A]

VD4/P 24.12.32 p210 1600

VD4/P 24.16.16 p275

20

1600

VD4/P 24.16.20 p275

25

1600

VD4/P 24.16.25 p275

31.5

1600

VD4/P 24.16.32 p275

16

2000

VD4/P 24.20.16 p275

20

2000

VD4/P 24.20.20 p275

25

2000

VD4/P 24.20.25 p275

31.5

2000

16

2300

(1)

VD4/P 24.20.32 p275 VD4/P 24.25.16 p275

20

2300

(1)

VD4/P 24.25.20 p275

25

2300

(1)

VD4/P 24.25.25 p275

31.5

2300

(1)

VD4/P 24.25.32 p275

W = Width of the switchgear. P = Pole horizontal centre distance. u/l = Distance between bottom and top terminal. ø = Diameter of the isolating contact. (1) Up to 2500 A rated current guaranteed with forced ventilation.

Standard fittings of withdrawable circuit-breakers for PowerCube modules The basic versions of the withdrawable circuit-breakers are always three-pole and fitted with: – EL type manual operating mechanism – mechanical signalling device for closing springs charged/ discharged – mechanical signalling device for circuit-breaker open/closed – closing pushbutton – opening pushbutton – operation counter – set of ten circuit-breaker open/closed auxiliary contacts

– racking-in/out lever (the quantity must be defined according to the number of pieces of apparatus ordered) – locking electromagnet in the truck. This prevents the circuit-breaker being racked into the panel with the auxiliary circuits disconnected (plug not inserted in the socket). – door interlock (compulsory for ABB switchgear); this device prevents racking the circuit-breaker into the switchgear when the switchgear door is open.

Note: with the group of ten auxiliary contacts supplied as standard and the maximum number of electrical applications, three break contacts (signalling circuit-breaker open) and four make contacts (signalling circuit-breaker closed) are available.

– lever for manually charging the closing springs – isolating contacts – cord with connector (plug only) for auxiliary circuits, with striker pin which does not allow the plug to be inserted into the socket if the rated current of the circuit-breaker is different from the rated current of the panel

43

2. Selection and ordering Withdrawable circuit-breakers

Withdrawable circuit-breakers for ZS8.4 type switchgear (12 - 17.5 - 24 kV)

Circuit-breaker

VD4/Z8 Panel without partitions • Panel with partitions — Preussen Elektra - EON

(2)



Width [mm] 650

650

650

650

800

800

Depth [mm] 1000

1000

1000

1000

1200

1200

IEC 62271-100 •

Standards

VDE 0671 •

Rated voltage

Ur [kV] 12

12

17.5

17.5

24

24

Rated insulation voltage

Us [kV] 12

12

17.5

17.5

24

24

Withstand voltage at 50 Hz Impulse withstand voltage Rated frequency

Ud (1 min) [kV] 28

28

38

38

50

50

Up [kV] 75

75

95

95

125

125 1250

fr [Hz] 50-60

Rated normal current (40 °C)

(1)

Rated breaking capacity (rated symmetrical short-circuit current) Rated short-time withstand current(3 s)

Making capacity Operation sequence

Ir [A] 630

1250

630

1250

630









16

16

Isc [kA] 20

20

20

20

20

20

25

25

25

25

25

25









16

16

Ik [kA] 20

20

20

20

20

20

25

25

25

25

25

25









40

40

Ip [kA] 50

50

50

50

50

50

63

63

63

63

63

63

[O-0.3s-CO-15s-CO] •

Opening time

[ms] 33...60

Arcing time

[ms] 10...15

Total breaking time

[ms] 43...75

Closing time

[ms] 60...80 P P

Maximum overall dimensions

H W

D

Weight Standardised table of dimensions Operating temperature Tropicalisation Electromagnetic compatibility

H [mm] 579

579

579

579

680

680

W [mm] 503

503

503

503

653

653

D [mm] 548

548

548

548

646

646

Pole distance P [mm] 150

150

150

150

210

210

[kg] 116

116

116

116

140

140

000137

000137

000137

000089

000138

1VCD 000092 [°C] – 5 ... + 40 IEC 60068-2-30 • IEC 60721-2-1 • IEC 62271-1 •

(1) Rated current guaranteed with circuit-breaker installed in switchgear with 40 °C ambient temperature. (2) Special type with device for charging the closing spring by means of a rotary handle outside the operating mechanism.

44

VD4/ZT8

VD4/ZS8













650

650

650

650

800

800

650

650

800

800

1200

1200

1200

1200

1200

1200

1200

1200

1200

1200









12

12

17.5

17.5

24

24

12

12

24

24

12

12

17.5

17.5

24

24

12

12

24

24

28

28

38

38

50

50

28

28

50

50

75

75

95

95

125

125

75

75

125

125

50-60

50-60

630

1250

630

1250

630

1250

630

1250

630

1250









16

16





16

16

20

20

20

20

20

20

20

20

20

20

25

25

25

25

25

25

25

25

25

25









16

16





16

16

20

20

20

20

20

20

20

20

20

20

25

25

25

25

25

25

25

25

25

25









40

40





40

40

50

50

50

50

50

50

50

50

50

50

63

63

63

63

63

63

63

63

63

63





33...60

40...60

10...15

10...15

43...75

50...75

60...80

60...80

579

579

579

579

680

680

579

579

680

680

503

503

503

503

653

653

503

503

653

653

638

638

638

638

646

646

638

638

646

646

150

150

150

150

210

210

150

150

210

210

116

116

116

116

140

140

116

116

140

140

000093

000134

000134

000134

000090

000136

000091

000133

000088

000135

– 5 ... + 40

– 5 ... + 40













45

2. Selection and ordering Withdrawable circuit-breakers

VD4/ZS8 - VD4/ZT8 - VD4/Z8 withdrawable circuit-breaker for ZS8.4 switchgear Ur

kV

12

17.5

Isc

kA

Rated uninterrupted current (40°C) [A] Panel without partition

Panel with partition

Special panel EON

W = 650

W = 800

W = 650

W = 800

W = 650

W = 800

P = 150

P = 210

P = 150

P = 210

P = 150

P = 210

u/l = 205

u/l = 310

u/l = 205

u/l = 310

u/l = 205

u/l = 310

ø = 35

ø = 35

ø = 35

ø = 35

ø = 35

ø = 35

20

630

VD4/Z8 12.06.20 p150

25

630

VD4/Z8 12.06.25 p150

20

1250

VD4/Z8 12.12.20 p150

25

1250

VD4/Z8 12.12.25 p150

20

630

VD4/ZT8 12.06.20 p150

25

630

VD4/ZT8 12.06.25 p150

20

1250

VD4/ZT8 12.12.20 p150

25

1250

VD4/ZT8 12.12.25 p150

20

630

VD4/ZS8 12.06.20 p150

25

630

VD4/ZS8 12.06.25 p150

20

1250

VD4/ZS8 12.12.20 p150

25

1250

VD4/ZS8 12.12.25 p150

20

630

VD4/Z8 17.06.20 p150

25

630

VD4/Z8 17.06.25 p150

20

1250

VD4/Z8 17.12.20 p150

25

1250

VD4/Z8 17.12.25 p150

20

630

25

630

VD4/ZT8 17.06.25 p150

1250

VD4/ZT8 17.12.20 p150

25

W = P = u/l = ø =

46

VD4/ZT8 17.06.20 p150

20 16

24

Circuit-breaker type

1250

VD4/ZT8 17.12.25 p150

630

VD4/Z8 24.06.16 p210

20

630

VD4/Z8 24.06.20 p210

25

630

VD4/Z8 24.06.25 p210

16

1250

VD4/Z8 24.12.16 p210

20

1250

VD4/Z8 24.12.20 p210

25

1250

VD4/Z8 24.12.25 p210

16

630

VD4/ZT8 24.06.16 p210

20

630

VD4/ZT8 24.06.20 p210

25

630

VD4/ZT8 24.06.25 p210

16

1250

VD4/ZT8 24.12.16 p210

20

1250

VD4/ZT8 24.12.20 p210

25

1250

VD4/ZT8 24.12.25 p210

16

630

VD4/ZS8 24.06.16 p210

20

630

VD4/ZS8 24.06.20 p210

25

630

VD4/ZS8 24.06.25 p210

16

1250

VD4/ZS8 24.12.16 p210

20

1250

VD4/ZS8 24.12.20 p210

25

1250

VD4/ZS8 24.12.25 p210

Width of the switchgear. Pole horizontal centre distance. Distance between bottom and top terminal. Diameter of the isolating contact.

Standard fittings of withdrawable circuit-breakers for ZS8.4 switchgear The basic versions of the withdrawable circuit-breakers are three-pole and fitted with: – EL type manual operating mechanism – mechanical signalling device for closing springs charged/ discharged – mechanical signalling device for circuit-breaker open/closed – closing pushbutton – opening pushbutton – operation counter – set of ten circuit-breaker open/closed auxiliary contacts Note: with the group of ten auxiliary contacts supplied as standard and the

3

2

maximum number of electrical applications, three break contacts (signalling circuit-breaker open) and four make contacts (signalling circuit-breaker closed) are available.

1

– lever for manually charging the closing springs incorporated in the operating mechanism for VD4/Z8 and VD4/ZT8, external with rotary movement for VD4/ZS8 – isolating contacts – racking in/out lever (the quantity must be defined according to the number of pieces of apparatus ordered) VD4/ZS8 (Preussen Elektra-EON version) – device for closing spring charging, with the door closed, by means of a removable rotary crank handle outside the operating mechanism and the switchgear – Harting 64-pin socket with mechanical interlock which prevents traverse of the circuit-breaker when the plug is not inserted in the socket – interlock with the door which prevents the spring charging lever when the circuit-breaker is closed – interlock with the door and Harting 64 pin socket which prevents door closing when the plug is not inserted in the socket.

Caption 1) Spring charging device with rotary crank handle 2) Harting 64 plus socket with mechanical interlock which prevents traverse when the socket is not inserted 3) Door - socket - spring charging device interlock (only VD4/ZS8 version)

VD4/Z8 - VD4/ZT8 – Harting 64-pin socket with mechanical interlock which prevents traverse of the circuit-breaker when the plug is not inserted in the socket.

47

2. Selection and ordering Withdrawable circuit-breakers

Withdrawable circuit-breakers for UniSwitch switchgear (CBW type unit) and UniMix switchgear P1/E type unit) (24 kV)

Circuit-breaker

VD4/US 24

Standards

VD4/US 24

(3)

(4)

UniSwitch (unit CBW type) •







UniMix (unit P1/E type) –







IEC 62271-100 •







VDE 0671; CEI EN 62271-100- File 7642 •







Rated voltage

Ur [kV] 24

24

24

24

Rated insulation voltage

Us [kV] 24

24

24

24

Ud (1 min) [kV] 50

50

50

50 125

Withstand voltage at 50 Hz Impulse withstand voltage

Up [kV] 125

Rated frequency Rated normal current (40 °C)

(1)

Rated breaking capacity (rated symmetrical short-circuit current)

Rated short-time withstand current (3 s)

(2)

125

125

fr [Hz] 50-60

50-60

50-60

50-60

Ir [A] 630

1250

630

1250

16 (20)

(5)

16 (25)

(5)

16

16

Isc [kA] 20 (25)

(5)

20 (25)

(5)

20

20



– (5)

16 (25)

(5)

16

16

Ik [kA] 20 (25)

(5)

20 (25)

(5)

20

20

25

25

40 (50)

(5)

40 (50)

(5)

40

40

Ip [kA] 50 (63)

(5)

50 (63)

(5)



— Operation sequence

25

16 (20) –

Making capacity

25

[O - 0.3 s - CO - 15 s - CO] •

50

50



63

63







Opening time

[ms] 33 ... 60

33 ... 60

33 ... 60

33 ... 60

Arcing time

[ms] 10 ... 15

10 ... 15

10 ... 15

10 ... 15

Total breaking time

[ms] 43 ... 75

43 ... 75

43 ... 75

43 ... 75

Closing time

[ms] 60 ... 80

60 ... 80

60 ... 80

60 ... 80

P P

Maximum overall dimensions

H W

D

Weight Standardised table of dimensions Operating temperature Tropicalization Electromagnetic compatibility (1) (2) (3) (4) (5)

48

H [mm] 680

680

680

680

W [mm] 653

653

653

653

D [mm] 742

742

742

742

Pole distance P [mm] 210

210

210

210

[kg] 125

125

125

125

000047

000047

000047

- 5 ... + 40

- 5 ... + 40

- 5 ... + 40

IEC: 60068-2-30, 60721-2-1 •







IEC 62271 •







1VCD 000047 [°C] - 5 ... + 40

Rated current guaranteed with withdrawable circuit-breaker installed in switchgear with 40 °C ambient temperature The value and duration of the rated short-time withstand current depends on the switchgear. See the specific catalogues of the UniSwitch and UniMix switchgear The top shutter activation wheels of the UniSwitch switchgear (CBW unit) are mounted and adjusted by the manufacturer of the UniSwitch switchgear The top shutter activation wheels of the UniMix switchgear (P1/E unit) are available on request The values in brackets refer to the 12 kV rated voltage.

Withdrawable c.-breaker for UniSwitch switchgear (CBW type unit) and UniMix switchgear (P1/E type unit) Ur

kV

24

Isc

kA

Rated uninterrupted current (40 °C) [A] UniSwitch CBW

UniMix P1/E

P=210

P=210

u/l=310

u/l=310

ø=35

ø=79 630 630

VD4/US 24.06.20 p210

630

VD4/US 24.06.25 p210 VD4/US 24.12.16 p210

Circuit-breaker type

16

630

(1)

20

630

(1)

25



16

1250

(1)

1250

20

1250

(1)

1250

VD4/US 24.12.20 p210

25



1250

VD4/US 24.12.25 p210

VD4/US 24.06.16 p210

(1) Isc 25 kA at 12 kV. P = Horizontal centre distance between poles. u/l = Distance between top and bottom terminal. Ø = Diameter of the isolating contacts.

Standard fittings of withdrawable circuit-breakers for UniSwitch and UniMix switchgear The basic versions of the withdrawable circuit-breakers are three-pole and fitted with: – EL type manual operating mechanism – mechanical signalling device for closing springs charged/ discharged – mechanical signalling device for circuit-breaker open/closed – closing pushbutton – opening pushbutton – operation counter – set of ten circuit-breaker open/closed auxiliary contacts Note: with the group of ten auxiliary contacts supplied as standard and the maximum number of electrical applications, three break contacts (signalling circuit-breaker open) and four make contacts (signalling circuit-breaker closed) are available.

– lever for manually charging the closing springs – isolating contacts – cord with connector (plug only) for auxiliary circuits, with striker pin which does not allow the plug to be inserted into the socket if the rated current of the circuit-breaker is different from the rated current of the panel – racking-in/out lever (the quantity must be defined according to the number of pieces of apparatus ordered) – locking electromagnet in the truck. This prevents the circuit-breaker being racked into the panel with the auxiliary circuits disconnected (plug not inserted in the socket).

49

2. Selection and ordering Withdrawable circuit-breakers

General characteristics of withdrawable circuit-breakers for UniSec switchgear

Circuit-breaker

VD4/SEC IEC 62271-100 •

Standards

VDE 0671; CEI EN 62271-100- File 7642 •

Rated voltage

Ur [kV] 24

Rated insulation voltage

Us [kV] 24

Withstand voltage at 50 Hz

Ud (1 min) [kV] 50

Impulse withstand voltage

Up [kV] 125

Rated frequency Rated normal current (40 °C)

fr [Hz] 50-60 Ir [A] 630 - 1250

(1)

16

Rated breaking capacity (rated symmetrical short-circuit current)

Isc [kA] 20 25 16

Rated short-time withstand current (3 s)

Ik [kA] 20 25 40

Making capacity

Ip [kA] 50 63

Opening time

[O - 0.3 s - CO - 15 s - CO] •

Opening time

[ms] 33 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 43 ... 75

Closing time

[ms] 60 ... 80 P P

Maximum overall dimensions

W [mm] 653 H

D [mm] 742 W

Weight Standardised table of dimensions Operating temperature Tropicalization Electromagnetic compatibility

H [mm] 743

D

Pole distance P [mm] 210 [kg] 133 1VCD 000190 [°C] - 5 ... + 40 IEC: 60068-2-30, 60721-2-1 • IEC 62271 •

(1) Rated current guaranteed with withdrawable circuit-breaker installed in switchgear with 40 °C ambient temperature.

50

Withdrawable circuit-breaker for UniSec switchgear Ur

Isc

kV

kA

Rated uninterrupted current (40 °C) [A] P=210 u/l=310

Circuit-breaker type

ø=79 16

24

630

VD4/SEC 24.06.16 p210

20

630

VD4/SEC 24.06.20 p210

25

630

VD4/SEC 24.06.25 p210

16

1250

VD4/SEC 24.12.16 p210

20

1250

VD4/SEC 24.12.20 p210

25

1250

VD4/SEC 24.12.25 p210

P = Horizontal centre distance between poles. u/l = Distance between top and bottom terminal. Ø = Diameter of the isolating contacts.

Standard fittings of withdrawable circuit-breakers for UniSec The basic versions of the withdrawable circuit-breakers are three-pole and fitted with: – EL type manual operating mechanism – mechanical signalling device for closing springs charged/ discharged – mechanical signalling device for circuit-breaker open/closed – closing pushbutton – opening pushbutton – operation counter – set of ten circuit-breaker open/closed auxiliary contacts Note: with the group of ten auxiliary contacts supplied as standard and the maximum number of electrical applications, three break contacts (signalling circuit-breaker open) and four make contacts (signalling circuit-breaker closed) are available.

– lever for manual loading of the closing spring built into the operating mechanism – isolating contacts – cord with connector (plug only) for auxiliary circuits, with striker pin which does not allow the plug to be inserted into the socket if the rated current of the circuit-breaker is different from the rated current of the panel – racking-in/out lever (the quantity must be defined according to the number of pieces of apparatus ordered)

51

2. Selection and ordering Optional accessories

The accessories identified with the same number are alternative to each other.

1 Shunt opening release (-MO1)

2 Additional shunt opening release (-MO2)

This allows remote opening control of the apparatus. The release can operate both in direct and alternating current. This release is suitable for both instantaneous and permanent service. In the case of instantaneous service, the minimum current impulse time must be 100 ms. Checking functionality and continuity is only possible using the STU device (accessory 21).

Like the shunt opening release described above, this allows remote opening control of the apparatus and can be supplied by a circuit completely separate from the release (-MO1). It keeps all the electrical and operating characteristics of the shunt opening release. Checking functionality and continuity is only possible using the STU device (accessory 21).

Characteristics Un

24 - 30 - 48 - 60 - 110 - 125 - 220 - 250 V–

Un

48 - 60 - 110 - 120...127 - 220...240 - V~ 50 Hz

Un

110 - 120 - 127 - 220 - 240 - V~ 60 Hz

Operating limits

70 … 110 % Un

Power on inrush (Ps)

DC 200 W; AC = 200 VA

Inrush duration

approx. 100 ms

Continuous power (Pc)

DC = 5 W; AC = 5 VA

Opening time

40...60 ms

Closing time

(1)

(2)

Insulation voltage (1) (2)

Valid for -MO1 e -MO2. Valid for -MC.

52

40...80 ms 2000 V 50 Hz (for 1 min)

3 Opening solenoid (-MO3)

4 Shunt closing release (-MC)

The opening solenoid (-MO3) is a special release with demagnetisation to be combined with an overcurrent protection relay of the self-supplied type. It is located in the operating mechanism (in the left side piece) and is not alternative to the additional shunt opening release (-MO2). It is not available for 40 and 50 kA circuit-breakers. Should the application of this accessory be required, specify the request at the time of order since subsequent application by the customer is not possible.

This allows remote closing control of the apparatus. The release can operate both in direct and alternating current. This release is suitable both for instantaneous and permanent service. In the case of instantaneous service, the minimum current impulse time must be 100 ms. Use of the permanently supplied release is recommended to carry out the electrical anti-pumping function. It keeps all the electrical and operating characteristics of the shunt opening release. Checking functionality and continuity is only possible using the STU device (accessory 21).

Note: for combination with the protection relays, please ask for the document: Data sheet 1VCD600854.

53

2. Selection and ordering Optional accessories

5 Undervoltage release (-MU)

The undervoltage release is available in the following versions: 5A Undervoltage release with power supply branched on the supply side. 5B Undervoltage release with electronic time delay - KT (0.5 - 1 - 1.5 - 2 - 3s) (power supply branched on the supply side). This device is set at 0.5s (for adjustment, please see the Electric Circuit Diagram chapter). Characteristics Un

24 - 30 - 48 - 60 - 110 - 125 - 220 - 250 V–

Un

48 - 60 - 110 - 120 - 127 - 220...240 V~ 50 Hz

Un

110 - 120...127 - 220...240 V~ 60 Hz

Operating limits

The undervoltage release opens the circuit-breaker when there is notable lowering or lack of its power supply. It can be used for remote trip (by means of normally closed type pushbuttons), lock on closing or to control the voltage in the auxiliary circuits. The circuit-breaker can only close with the release supplied (the closing lock is made mechanically). The release can operate both in direct and alternating current. Note As an alternative to the undervoltage release, an additional shunt opening release (-MO4) with the same electrical and operating specifications as shunt opening release (-MO1) can be installed on request. Warning! Installation of the additional shunt opening release (-MO4) requires a special mounting plate for releases. Moreover, application (-MO4) must be requested at the time of order and not afterwards.

54

– circuit-breaker opening: 35-70% Un – circuit-breaker closing: 85-110% Un

Power on inrush (Ps)

DC 200 W; AC = 200 VA

Inrush duration

approx. 100 ms

Continuous power (Pc)

DC = 5 W; AC = 5 VA

Opening time

60...80 ms

Insulation voltage

2000 V 50 Hz (for 1 min)

5a Electronic time delay device (-KT)

6 Undervoltage release mechanical override

The electronic time delay device must be mounted externally in relation to the circuit-breaker. It allows release trip delay with established and adjustable times. The use of the undervoltage release is recommended in order to prevent trips when the power supply network of the release may be subject to cuts or voltage drops of short duration. If it is not supplied, circuit-breaker closing is disabled. The time delay device must be combined with an undervoltage release for d.c. Rated voltage of the undervoltage release must be within the selected range of working of the time-delay device.

This is a mechanical device which allows the undervoltage release trip to be temporarily excluded. It is always fitted with electrical signalling. Should the application of this accessory be required, specify the request at the time of order since subsequent application by the customer is not possible.

Characteristics of the time-delay device

Un

24...30 - 48 - 60 - 110...127 - 220...250 V–

Un

48 - 60 - 110...127 - 220...240 - V~ 50/60 Hz

Adjustable opening time (release + time delay device): 0.5-1-1.5-2-3 sec

55

2. Selection and ordering Optional accessories

7 Circuit-breaker auxiliary contacts (-BB1; -BB2; -BB3)

General characteristics Insulation voltage according to VDE 0110 standard. Group C

660 V a.c. 800 V d.c.

Rated voltage

24 V ... 660 V a.c.

Test voltage

2 kV 50 Hz (for 1 min)

Rated overcurrent

10 A

Number of contacts

5

Contact run

6 mm ... 7 mm

Activation force

26 N

Resistance

3 mΩ

Storage temperature

–20 °C ... +120 °C

Operating temperature

–20 °C ... +70 °C

Contact overtemperature

20 K

Number of cycles

30.000

Unlimited breaking capacity if used with 10 A fuse in series

Electrical signalling of circuit-breaker open/closed can be provided with a set of 15 auxiliary contacts as an alternative to the 10 provided as standard. Note With the group of ten auxiliary contacts supplied as standard and the maximum number of electrical applications, three break contacts (signalling circuit-breaker open) and five make contacts (signalling circuit-breaker closed) are available. With the group of 15 auxiliary contacts, according to the electrical applications required, the following are available: – for fixed circuit-breakers: thirteen auxiliary contacts, differently divided between break contacts and make contacts according to the figure selected of the electrical diagram; – for withdrawable circuit-breakers, since the plug of the auxiliary circuits has a limited number of poles: five break contacts (signalling circuit-breaker open) and five make contacts (signalling circuit-breaker closed).

Electrical characteristics Un

Rated current

Breaking capacity

220 V a.c.

Cosj = 0.7

2.5 A

25 A

380 V a.c.

Cosj = 0.7

1.5 A

15 A

500 V a.c.

Cosj = 0.7

1.5 A

15 A

660 V a.c.

Cosj = 0.7

1.2 A

12 A

1 ms

10 A

12 A

15 ms

10 A

12 A

50 ms

8A

10 A

200 ms

6A

7.7 A

1 ms

8A

10 A

24 V d.c.

60 V d.c.

110 V d.c.

220 V d.c.

56

15 ms

6A

8A

50 ms

5A

6A

200 ms

4A

5.4 A

1 ms

6A

8A

15 ms

4A

5A

50 ms

2A

4.6 A

200 ms

1A

2.2 A

1 ms

1.5 A

2A

15 ms

1A

1.4 A

50 ms

0.75 A

1.2 A

200 ms

0.5 A

1A

8 Transient contact (-BB4)

9 Position contact (-BT3)

This contact closes momentarily (duration > 30 ms) on circuitbreaker opening controlled remotely with a shunt opening release. The indication is not provided when opening is manual and local. In fact, a contact (–BB11) is activated by the manual pushbutton and cuts off the transient contact closure (–BB4). The transient contact is activated directly from the main operating shaft when the indication is provided only on actual opening of the main circuit-breaker contacts.

This contact is used, together with the locking magnet in the operating mechanism (-RL1) to prevent remote closing during traverse into the unit. It is only supplied for the withdrawable version circuit-breakers for UniGear ZS1 switchgear and PowerCube modules. It cannot be supplied when the transmitted contacts are requested in the truck (-BT1; -BT2).

10 Transmitted contacts in the truck (-BT1; -BT2)

Transmitted contacts of the withdrawable circuit-breaker (installed in the circuit-breaker truck - only for VD4/P withdrawable circuit-breaker). These contacts are either in addition or as an alternative to the position contacts (for signalling circuit-breaker racked out) located in the unit. They also carry out the function of the position contact (-BT3).

57

2. Selection and ordering Optional accessories

11 Motor operator (-MS)

12 C ontact for signalling closing spring charged/ discharged (-BS2)

This carries out automatic charging of the circuit-breaker operating mechanism closing spring. After circuit-breaker closing, the geared motor immediately recharges the closing springs. In the case of a power cut or during maintenance work, the closing spring can be charged manually in any case (by means of the special crank handle incorporated in the operating mechanism).

This consists of a microswitch which allows remote signalling of the state of the circuit-breaker operating mechanism closing pring. The following signals are possible: – contact open: signalling spring charged – contact closed: signalling spring discharged. The two signals must be used for circuits which have the same power supply voltage.

Characteristics Un

24...30 - 48...60 - 110...130 - 220...250 V–

Un

100...130 - 220...250 V~ 50/60 Hz

Operating limits

85 … 110% Un ≤ 40 kA

50 kA (*)

DC = 600 W; AC = 600 VA DC = 200 W; AC = 200 VA

DC = 900 W; AC = 900 VA DC = 350 W; AC = 350 VA

Charging time

0,2 s

0,2 s

Charging time

6-7 s

6-7 s

Insulating voltage

2000 V 50 Hz (for 1 min)

2000 V 50 Hz (for 1 min)

Power on inrush (Ps) Rated power (Pn)

(*) Not available for versions with motorized truck.

58

Protections and locks Various mechanical and electromechanical locking and protection devices are available.

13 Opening and closing pushbutton protection

14 Opening and closing pushbutton padlock

The protection only allows the opening and closing pushbuttons to be operated using a special tool.

The device allows the opening and closing pushbuttons to be locked using a maximum of three padlocks (not supplied): ø 4 mm. Also prevents closing using remote control. This lock is available in two versions: 14A Possibility of padlocking both the pushbuttons without distinction 14B Separate padlocking of the opening and/or closing pushbutton. N.B. Lock 14A prevents closure by remote control; lock 14B does not prevent closure by remote control.

59

2. Selection and ordering Optional accessories

15 Key lock in open position

16 Locking magnet on the operating mechanism (-RL1)

The lock is activated by a special circular lock. Different keys (for a single circuit-breaker) are available, or the same keys (for several circuit-breakers). To activate the lock, keep the opening pushbutton pressed down, turn the key and remove it. With the key removed, the opening pushbutton automatically remains in the pressed position preventing local manual closing and remote electrical closing.

Only allows activation of the command with the electromagnet supplied.

60

Characteristics Un

24 - 30 - 48 - 60 - 110 132 - 220 - 250 V–

Un

48 - 60 - 110 - 120 ... 127 220 ... 240 V~ 50/60 Hz

Operating limits

85 … 110% Un

Power on inrush (Ps)

DC 250 W; AC = 250 VA

Continuous power (Pc)

DC = 5 W; AC = 5 VA

Inrush duration

150 ms

Insulating voltage

2000 V 50 Hz (for 1 min)

17 Locking magnet on the truck (-RL2)

18 Interlock for fixed circuit-breaker

Compulsory accessory for the withdrawable versions for UniGear ZS1 switchgear and PowerCube modules, to prevent circuit-breaker racking into the switchgear with the auxiliary circuit plug disconnected. The plug also makes the anti-insertion lock for a different rated current. Special striker pins do not allow insertion of the plug in the socket if the rated current of the circuit-breaker is lower than the rated current of the panel. Note: on request, a specific version for the circuitbreakers for ZS8.4 switchgear is available.

Device for fixed circuit-breakers which are converted into withdrawable ones by the customer. It allows a mechanical lock to be made, by the customer, which prevents rackingout/in with the circuit-breaker closed and prevents circuitbreaker closing during translation. Note: The device must be requested when ordering since it must be assembled and tested in the factory.

Characteristics Un

24 - 30 - 48 - 60 - 110 - 125 127 - 132 - 220 - 240 V–

Un

24 - 30 - 48 - 60 - 110 - 125 - 127 220 - 230 ... 240 V~ 50/60 Hz

Operating limits

85 … 110% Un

Nominal power (Pn)

DC 250 W; AC = 250 VA

Continuous power (Pc)

DC = 5 W; AC = 5 VA

Inrush duration

150 ms

Insulating voltage

2000 V 50 Hz (for 1 min)

61

2. Selection and ordering Optional accessories

19 M echanical interlock with the door

20 M otorised truck (-MT)

This device prevents circuit-breaker racking-in when the switchgear door is open. It is only provided for circuitbreakers used in switchgear UniGear ZS1 and PowerCube modules, fitted with a special actuator on the door.

It allows racking-in and racking-out of the circuit-breaker in the switchgear to be carried out remotely, (only for circuitbreaker in withdrawable version for UniGear ZS1 and ZS8.4 switchgear and PowerCube modules). Characteristics

62

Un

24 - 30 - 48 - 60 - 110 - 220 V–

Operating limits

85 … 110% Un

Nominal power(Pn)

40 W

21 STU Shunt Test Unit

Due to the particular construction of these releases, checking the functionality of the shunt closing (-MC) and opening (-MO1, -MO2) releases is not possible with dedicated relays (e.g. TCS Test Control Supervision, CCC Control Coil Continuity) or with the REF control and protection unit. The only device able to carry out a check of the functionality is the STU device. Please contact us if you want to carry out this control with devices other than STU. This device can be combined with the shunt opening release (-MO1; -MO2) or with the shunt closing release (-MC) to check functionality and continuity.

The control/monitoring Shunt Test Unit allows the continuity of releases with a rated operating voltage between 24 V and 250 V (AC and DC) to be checked, as well as the functionality of the electronic circuit of the release. Checking continuity is carried out cyclically with an interval of 20 seconds between one test and the next. The unit has optical signals by means of LEDs on the front. In particular the following information is indicated: – POWER ON: power supply present – (-MO) TESTING: test being carried out – TEST FAILED: signal following a failed test or in the absence of auxiliary power supply – ALARM: signal after three failed tests. Two relays and a changeover are also available on board the unit, which allow remote signalling of the following two events: – failure of a test (resetting is carried out automatically when the alarm stops) – failure of three tests (resetting is only carried out by means of the manual - RESET – from the front of the unit). There is also a manual - RESET – button on the front of the unit. Characteristics Un

24 ... 250 V AC/DC

Maximum interrupted current

6A

Maximum interrupted voltage

250 V AC

63

3. Specific product characteristics

Resistance to vibrations

Galvanisation is carried out in accordance with UNI ISO 2081 Standards, classification code Fe/Zn 12, with a thickness of 12x10-6 m, protected by a conversion layer mainly consisting of chromates in compliance with the UNI ISO 4520 Standard. These construction characteristics mean that the whole VD4 series of circuit-breakers and its accessories comply with climate graph 8 of the IEC 60721-2-1 and IEC 60068-2-2 (Test B: Dry Heat / IEC 60068-2-30 (Test Db: Damp Heat, cyclic) Standards.

Altitude The VD4 circuit-breakers are designed to satisfy high levels of resistance to stresses caused by mechanical vibrations. Many versions are able to satisfy both the approval criteria of the major International Shipping Registers (DNV, Lloyd’s Register, RINA) and the qualification criteria of the International Seismic Standards (IEEE 344, IEEE 323 and IEC 60980). For the versions approved by the shipping registers, please contact us.

Tropicalization

VD4 circuit-breakers are manufactured in compliance with the strictest regulations regarding use in hot-humid-saline climates. All the most important metal components are treated against corrosive factors according to UNI EN 12500 Standards environmental class C.

64

The insulating property of air decreases as the altitude increases, therefore this must always be taken into account for external insulation of the apparatus (the internal insulation of the interrupters does not undergo any variations as it is guaranteed by the vacuum). The phenomenon must always be taken into consideration during the design stage of the insulating components of apparatus to be installed over 1000 m above sea level. In this case a correction coefficient must be considered, which can be taken from the graph on the next page, built up on the basis of the indications in the IEC 62271-1 Standards. The following example is a clear interpretation of the indications given above.

Graph for determining the Ka correction factor according to the altitude Example • Installation altitude 2000 m • Operation at the rated voltage of 12 kV • Withstand voltage at power frequency 28 kV rms • Impulse withstand voltage 75 kVp • Ka factor obtained from graph = 1.13.

kA 1,50

m=1

Ka = e m (H – 1000)/8150 1,40

Considering the above parameters, the apparatus will have to withstand (under test and at zero altitude, i.e. at sea level): – withstand voltage at power frequency equal to: 28 x 1.13 = 31.6 kVrms – impulse withstand voltage equal to: 75 x 1.13 = 84.7 kVp.

1,30

From the above, it can be deduced that for installations at an altitude of 2000 m above sea level, with 12 kV service voltage, apparatus must be provided with 17.5 kV rated voltage, characterised by insulation levels at power frequency of 38 kVrms with 95 kVp impulse withstand voltage.

1,10

1,20

1,00 1000

1500

2000

2500

3000

3500

4000 H

H = altitude in metres; m = value referred to power frequency and the lightning impulse withstand voltages and those between phases.

Anti-pumping device The EL operating mechanism of VD4 circuit-breakers (in all versions) is fitted with a mechanical anti-pumping device which prevents re-closing due to either electrical or mechanical commands. Should both the closing command and any one of the opening commands (local or remote) be active at the same time, there would be a continuous succession of opening and closing commands. The anti-pumping device avoids this situation, ensuring that each closing operation is only followed by an opening operation and that there is no other closing operation after this. To obtain a further closing operation, the closing command must be released and then re-launched. Furthermore, the anti-pumping device only allows circuitbreaker closure if the following conditions are present at the same time: – operating mechanism spring fully charged – opening pushbutton and/or shunt opening release (-MO1/-MO2) not activated – circuit-breaker open.

65

3. Specific product characteristics

REF 601 protection Device

On request, the REF 601 switchgear protection device is available for protection of the installations, which requires an auxiliary power supply for its operation unlike the previous PR512 which was a self-supplied release. The REF 601 has protections and trip curves in accordance with the IEC 255-3 Standard. It sees to the protection function against overload (51), against instantaneous and delayed short-circuit (50-51) and against instantaneous and delayed homopolar ground fault (50N and 51N). It also detects the second harmonic component to prevent unwarranted tripping on connection of a transformer (68). The unit has 3 inputs from current sensors of the type with Rogowsky coil, one input from external toroidal CT and from the keyboard 4 rated currents can be set: 40, 80, 250 and 1250 A. If the unit is connected to 3 current sensors, the 50N and 51N protection functions are carried out with the vectorial sum of the phase currents; if only 2 current sensors are used, then the external toroidal current transformer must be provided for functions 50N and 51N. The external toroidal current transformer can be with openable core or closed and with any transformation ratio as long with a 1 A secondary current. The ABB current sensors of the type with Rogowsky coil provided for REF 601, are only suitable for installation on MV insulated cables.

66

The characteristics of the device are: - trip precision - wide adjustment ranges - single and simultaneous adjustment of the three phases - no limitation (due to the current sensors) to the rated breaking capacity and at the short-time withstand current of the circuit-breaker - pushbuttons for local electrical operation of the circuitbreaker (opening and closing pushbutton - 5 distinct indicators: “relay in operation”, “relay in trip threshold”, “relay tripped”, “relay tripped due to exceeding phase current”, “relay tripped due to exceeding ground fault current” - interface consisting of an LCD display and of “arrow” keys, “enter” and “esc” for easier navigation inside the “measurement”, “data recording”, “event recording”, “settings”, “configuration” and “test” menus - three user levels: “operator” (only display, with free access, by keeping this key pressed for at least 5 sec.), “configurator” (like the previous one, but also with permission to set the protection parameters, i.e. times and thresholds, and communication, if present - access limited by a password), “administrator” (like the previous ones, but also with permission to set the password and configure the basic settings of the device, such as the rated current access limited by a password) - continual display of the current on the most highly loaded phase and of the round current - recording of the value of the currents which caused the device to trip - storage of the number of openings carried out by the device - event log (storage of the parameters described above in the last 5 trips of the device) in a non-volatile memory - curves “ß = 1” or “ß = 5” and curve “RI” specific for the Belgian market (only REF 601 IEC) - circuit-breaker opening by means of an undervoltage release (only REF 601 CEI) - version, on request, with RS485 4-wire serial communication - MODBUS RTU full duplex protocol - multi-voltage feeder 24 … 240 V a.c.- d.c

Environmental protection programme

Spare parts

VD4 circuit-breakers are manufactured in accordance with the ISO 14000 Standards (Guidelines for environmental management). The production processes are carried out in compliance with the Standards for environmental protection in terms of reduction in energy consumption as well as in raw materials and production of waste materials. All this is thanks to the medium voltage apparatus manufacturing facility environmental management system. Assessment of the environmental impact of the life cycle of the product, obtained by minimising energy consumption and overall raw materials of the product, became a concrete matter during the design stage by means of targeted selection of the materials, processes and packing. This is to allow maximum recycling at the end of the useful life cycle of the apparatus.

– – – – – – – – – – – – – – – – – – – –

Shunt opening release Additional shunt opening release Undervoltage release Time delay device for undervoltage release Shunt closing release Spring charging geared motor with electrical signalling of spring charged Contact signalling geared motor protection circuit-breaker open/closed Contact signalling closing spring charged/discharged Transient contact with momentary closing during circuitbreaker opening Circuit-breaker auxiliary contacts Locking electromagnet on the operating mechanism Position contact of the withdrawable truck Contacts signalling connected/isolated Opening solenoid Key lock in open position Isolation interlock with the door Protection for opening pushbutton Protection for closing pushbutton Locking electromagnet on the withdrawable truck Set of six isolating contacts.

Ordering For availability and to order spare parts, please contact our Service department, specifying the circuit-breaker serial number.

67

4. Overall dimensions Fixed circuit-breakers 450

VD4

20

kA

20

kA

31.5

12

25

4XM12 PROF.25

12

kA

20

475

20

20 2XM10 PROF.20

14 97

77.5

170

28

236 49 25

56

A 310

1600

32

A

599

kV

435

Isc

kV

17.5

237.5

Ir

12

16

Ur

95

248

1VCD000050

56 31

TN

28

345*

400 150

250

45 150

DETAIL A SCALE 1 : 2 . 5

44* 114

12

409 424

22

12

160

(*) Fixing interchangeability with previous series (345 x 400).

Fixed circuit-breakers 450

VD4

M12 PROF.25

31.5

kA

475

kA

22

28 49

25

DETAIL A SCALE 1:2

56

kA

25

77.5

kA

20

205

16

115

217.5

A 461

1250

16

A

22

A

kV

630

236

345*

28 45

400

250 409

150

150

424

(*) Fixing interchangeability with previous series (345 x 400).

12

22

160

68

2xM10 PROF.18

kV

170

Isc

17.5

45

32

95

31

Ir

12

435

Ur

248

7405

56

TN

44* 114

12

Fixed circuit-breakers 570

VD4

kA

25

kA

31.5

kA

22

kA

20

475

16

115

22

296

28 49

25

DETAIL A SCALE 1:2 24

A

205

1250

77.5

A 461

630

M12 PROF. 25

A

31

kV

56

kV

17.5

217.5

Isc

12

45

2XM10 PROF.20

95

16

Ir

32

308

170

Ur

7406

435

TN

44 *

345 *

28 45

520

250

114

12

409 210

210

424

12

22

160

(*) Fixing interchangeability with previous series (345 x 520).

Fixed circuit-breakers 570

A

40

kA

M12x25 deep

eep

x18 d

M10

11

1600

11

A

475

A 310

kV

1250

A (1:4) 77.5 24

171

238

56

435

Isc

17.5

11

589

Ir

kV

16

Ur

12

95 308

1VCD003282

30

TN

11

VD4

296

28 49

45

520 210

250

44 * 114

409

210

422

12

12

160

26

345 *

28

(*) Fixing interchangeability with previous series (345 x 650).

69

4. Overall dimensions Fixed circuit-breakers 700

VD4

1600

A

40

kA

11

A

M10x18 deep

A

11

kV

1250

310

17.5

M12x25 deep

24 77.5

171

238

56

475

435

Isc

kV

11

589

Ir

12

11

95

373

30

Ur

1VCD003285

16

TN

36

28

361

49

45

250

28

650

25 275

114

345 *

44

422

12

275

12

22

213

(*) Fixing interchangeability with previous series (345 x 650).

Fixed circuit-breakers 700

VD4

32

kA

31.5

kA

475

kA

25

77.5 24

20

205

kA

217.5

16

115

461

A

14

1250

16

A

49 25

345 *

28

45

650

250 409 424

275

275

22

12

213

(*) Fixing interchangeability with previous series (345 x 650).

70

22

DETAIL A SCALE 1 : 2

28

236

M12 PROF. 25

22

A

kV

630

2XM 10 PROF. 18

97

Isc

17.5

45

kV

170

Ir

12

435

Ur

95

373

1VCD000051

56 31

TN

44 * 114

12

Fixed circuit-breakers

A

20

kA kA

31.5

kA

Isc

kV

17.5

kV

2000

A

2500

A

40

kA

25

345 * 45

650

44 *

250

114

409

12

424 275

275

20

20

2XM10 PROF.20 12

12

28

213

20

Ir

28 49

12

Ur

361

7408

20

VD4 TN

24

78

25

616

A

2500

475

2000

310

A

599

1600

32

A

237

kV

31

kV

17.5

16

Isc

12

95

95

170

Ir

373

435

Ur

7408

56

TN

2500A

1600-2000A

700

VD4

4XM12 PROF.25

12

22

DETAIL A SCALE 1:2

(*) Fixing interchangeability with previous series (345 x 650).

Fixed circuit-breakers

7407

Ur

12

kV

Ir

2500

A

20

kA

308

A

2000

A

20

kA

25

kA

31.5

kA

40

kA

310

616 475

296

28 49

25

28

520

345 * 45

44 *

250 409

12

2XM10 deep 20

424 210

210 160

20

20

4XM12 deep 25

20

12

Isc

1600

12

12-17.5 kV

24

7407

Ur

77.5

TN

Ir

599 170

VD4

237.5

kA

16

40

31

kA

32

435

kA

31.5

A

56

25

2500A 95

95

20

TN

Isc

1600-2000A

570

VD4

12

22

DETAIL A SCALE 1:2

(*) Fixing interchangeability with previous series (345 x 650).

71

4. Overall dimensions Fixed circuit-breakers 373

12 28

49 361

5 th 2 dep

474

A (1:4)

4xM 12

2.5

24

77.5

25

20

12

310 635

kA

A

237

kA

50

171

kA

40

30

31.5

16

kA

20

kA

25

pth

A (**)

20

de

4000

0 M1 2x

Isc

kV kV A

20

32

Ir

12 17.5 3150

20

307

435

Ur

1VCD000149

56

TN

424 95

20

VD4

142 345*

28 45

650

250

44* 114

409

700 275

275

12

22

213

(*) Fixing interchangeability with previous series (345 x 650). (**) With forced ventilation.

Fixed circuit-breakers 600

VD4

kA

20

A

50

20

2.5

28

165

28

210

12

22

31

172

142 404 428

520

210

2.5

77.5

171

237

56

116

135

40

72

20

20

2000

32

24

A

12

1600

74 12

A

475

kV

1250

310

17.5

2xM10 deep 20

435

Isc

kV

610

Ir

12

4xM12 deep 25

459 130

300

16

Ur

323

1VCD003440

30

TN

156

Fixed circuit-breakers 750

kA

20

A

50

20

A

2500

12

2000

20

475

A

78

24

24

1600

20

310

A

74

610

1250

2xM10 deep 20

32

237

kV

30

17.5

171

Isc

kV

16

Ir

12

4xM12 deep 25

435

Ur

1VCD003441

130

56

TN

459 398 375

12

VD4

28

116

69.5

28

165 30.5

2.5

2.5

135

270

689

225

64.7

404 31

12

275

22

275

24

428

Fixed circuit-breakers

Isc

50

kA

74 32

20

A (*)

12

3150

20 20

475

30 435

2.5

116

30.5

172

28

165

69.5

28

689

270 404

31

275

2.5

24

171

237

56

135

24

Ir

189

130

12

kV

375

310

kV

17.5

4xM12 deep 25 2xM10 deep 20

636

12

Ur

189

118

1VCD003443

240

16

TN

459 398

20

750

VD4

64.5

225 24

428

275

12

22

12

(*) 4000 A with forced ventilation.

73

4. Overall dimensions Fixed circuit-breakers 570

VD4

1250

A

16

kA

20

kA

25

kA

2XM10 PROF.20

M12 PROF.25

115 22

22

DETAIL A SCALE 1:2

296

28 49

25

24

77.5

170

282.5

435 56

Isc

32

22

A

475

630

45 A

310

kV

631

24

31

Ur

16

7409

Ir

95 308

TN

M12

345*

28

45

250 409 424

520 210

39* 114

12

210 160

(*) Fixing interchangeability with previous series (345 x 520).

Fixed circuit-breakers 700

VD4

A

16

kA

20

kA

25

kA

115 45

77.5

170

56

282.5

16

Isc

22

1250

32

475

A

Ir

310

kV

630

631

24

M12 PROF.25

A

31

Ur

2XM10 PROF.18

435

7410

22

95

373

TN

28 49

25

28

45

424

275

12

22

213

(*) Fixing interchangeability with previous series (345 x 650).

74

250 409

650 275

345 *

24

361

44 * 114

12

DETAIL A SCALE 1:2

Fixed circuit-breakers 700

VD4

kA

361

28 49

25

28

345 * 45

250

44 * 114

409

650

424

275

20

275

20

2XM10 DEEP 20

20

12

12

213

20

kA

31,5

56

25

661

kA

Isc

475

kA

20

24

16

310

A

77.5

A

2500

647

A

2000

Ir

95

282.5

kV

1600

31

24

16

Ur

170

7411

95

435

TN

2500A

1600-200A 373

22

4XM12 DEEP 25

DETAIL A SCALE 1:2

(*) Fixing interchangeability with previous series (345 x 650).

Fixed circuit-breakers 570

VD4 1VCD000172

Ur

24

Ir

1250

A

Isc

31.5

kA

95

308

85 4XM12 DEEP25

kV

2XM10 DEEP 20 40

12

310

32

72

TN

475 77.5

282.5

16

24

17 0

72 DETAIL A SCALE 1 : 2

296

28 49

M12

28

210

250 344.5 *

520

25

45

114 39*

409

210

424 160

22

435

56

31

12

647

22

75

4. Overall dimensions Fixed circuit-breakers 784

VD4

A

2000

A

31.5

kA

R16

612 482.5 305

15.5

571

57.9

Isc

245

28 49

28 786

275

275

87.5

A

1600

Ir

104.5

kV

1250

328

36

876

1VYN300901-LT

Ur

31.17

TN

331 447

478.5

470

76

22

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules 492

VD4/P

303

kA

98 35 628 71

38

18

19.5

14

24

340 503 531

4

76

kA

31.5

35

kA

25

260

20

15

154

kA

205

A

16

618 31

1250

62.5

28

10

A

28

79

kV

630

121

91

17.5

36

19

Isc

kV

1250A

124

56 16

Ir

12

630A

36

42.5

213

Ur

7412

624.5

TN

234 49

25

501 490 456

383 416

53

438

150

662

48

38

121

124

609

55

150

320 370

Withdrawable circuit-breakers for PowerCube modules 636

35 310

688

691

71

38

280 165

25

320

18

14

650

19.5

653

21.5

76

kA

4

31.5

303

359.5

640

370

626

383

550

416

53

642 210

210

55

kA

36

111

kA

25

16

16

28

213

A 31

1250

111

62.5

56

A

36

119

630

119

28

38

kV

688

kV

17.5

691

Isc

12

4

Ir

230

49

589

Ur

7420

48

TN

44

8

VD4/W

77

4. Overall dimensions Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules 636

40

kA

28

37

688

A

36

17

62.5

303

79

A

1600

28

310

1250

30

kV

49

111

71

25

18

19.5

21.5

14

320

650

359.5

640

370

626

383

552 210

38

76

280 4

214 4

653

165

56

Isc

kV

17.5

230

16

Ir

12

688

Ur

1VCD003284

691

TN

125

44

8

VD4/P

416

210

53

587

55

640

38

53

640

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules 842

A

40

kA

303

37

165

76

640

275

55 38

320 359.5

416

750

587

25

383

806

53

38

370

836

275

19.5

14

850

21.5

853

4

4

213

280

56

71

78

8

1600

688

A

17

79

kV

1250

111

310

17.5

36

119

230

16

Isc

kV

30

Ir

12

688

Ur

144 49 28 28

1VCD003286

691

TN

122

VD4/P

53

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules

kV

36

Ur Ir

8 688

19.5

21.5

25

320 359.5

650

17.5

kV

640

2000

A

626

40

14

4

4

653

kV

370 383 416

550

kA

38

53

640

210

210

111

38

53

119

587

55

Isc

7415

79

310

71 165

kA

213

kA

31.5

303

36

76

kA

25

280

A 31

A

2000

12

17

28

VD4/P TN

119

kV

1600 20

Isc

28

16

17.5

111 62.5

49

688

Ir

12

230

56

Ur

7415

691

TN

122

636 44

VD4/P

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules 842

A

71

836 806

40

kA

Ø19.5

320 359.5 370

34

53

640

750 275

383 416

275

55

Isc

25

111

A

119

2000

21.5

76

kV

Ir

14

850

38

17.5

853

kV

587

12

4

7416

53

Ur

8

165

VD4/P TN

38

280

kA

16

kA

31.5

213

25

310

A kA

303

36

31

2000

28

36

688

1600

119 110 62.5

230 28

79

kV

20 Isc

kV

17.5

56

Ir

12

49

691

Ur

144

7416

688

TN

122

VD4/P

79

4. Overall dimensions Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules 842

40

kA

109

8 688

kA

303

36

280

213

14

4

4

853

71

19.5

kA

31.5

21.5

25

165

kA

62.5

38

76

A

20

17

111

310

kV

2500

31

17.5

56

Isc

kV

28 28

16

Ir

12

119

230

49 36

691

Ur

144

7417

688

TN

152

VD4/P

25

320 359.5

850

370

836

383

806

416

750

53

640

275

38

53

111

119

55

587

275

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules

2000

A

50

kA

36

433 20

688

A

19.5

26

14

14

21.5

653

4

605

12

4

76

165

19

213

280

56

478

1600

16

122

A

111 28

79

kV

1250

116

310

17.5

135

691

Isc

kV

119

28

16

Ir

12

25

220 165

30

Ur

636 44

1VCD003444

688

TN

10

VD4/P

25 320

650

359.5

640

34

626

80

12

23

4

303

360

590

29

590

210

49.5

383 416

550

210

4

370

53

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules 842

A

50

kA

28

116

433

36 20

688

2000

16

26 165

853

14

4

4

25

19.5

12

4

805 14

21.5

76

19

213

280

56

478

A

111

122

1600

135

119

25

79

kV

28

310

17.5

217.5

165

691

Isc

kV

144

16

Ir

12

30

Ur

1VCD003445

688

TN

10

VD4/P

320 370

850

359.5

836

34

806

416

750

53

590

275

275

12

22

4

303

360

590

29

49.5

383

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules VD4/P

10

152

433 688

691

109

310

36 20

478

16

14

19.5 76

26

25

21.5 4

853

165

280 19

12

805 14

320 370 359.5

850 34

836

49.5

383 417

812

590

750

275

275

303 12

22

kA

213

50

16

29

Isc

111

28

360

A

119

25

4

kV

2500

28

30

17.5

Ir

217.5

164 115

136

688

kV

143

56

12

4

Ur

842

1VCD003446

590

TN

81

4. Overall dimensions Withdrawable circuit-breakers for PowerCube modules 842

50

kA

20 433

26

19,5

165 4

25

21,5

805 853 850 836 806

14

12

4

76

19

213

280

56

478

742

36

732

Isc

152

A (*)

109

3150

28

310

Ir

165 116 28

135

16

130

742

kV

119 111

240

678

17.5

Ur

25

30

16

kV

730

12

129

10

361

1VCD003596

30

TN

118

VD4/W

370 34 750

275 29

4

320 359,5

49,5

383 416,5

53

590 275

22

(*) 4000 A with forced ventilation.

12

4

303

360

590

189

Withdrawable circuit-breakers for UniGear ZS1 switchgear

kV

17.5

kV

Ir

3150

A (*)

Isc

50

kA

111

240

28

16

130 116 28

135

118

12

36 109

433 733

742

20

19.5

26 76

165

19

213

280

56

478

678

16

30

730

310

Ur

25

361 165

1VCD003447

152

TN

10

842

VD4/P

850 836 806

25

21.5 4

4

12

805 853

14

320 370 359.5

34

29

750

590

275

(*) 4000 A with forced ventilation.

82

22 12

4

303

360

589

189

49.5

383 416

275

4

53

Withdrawable circuit-breakers for UniGear ZS1 switchgear

2 166

732

4

356 853

14

850 836 806 750

275

19.5

76

kA

21.5

40

109

kA

165

kA

31.5

149

kA

25

310

20

86

52

280

A (*)

4

3150

19

kV

17

30

17.5

93

28 36

214

Isc

kV

56

Ir

12

730

Ur

1VCD000153

17kV

12kV

16

TN

111

373.5

49

10

842

VD4/P

53

303 320

25

360 370 382

34

275

416 640 16

4

12

189

22

(*) 4000 A with forced ventilation.

39

96

587

55

8

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules 44

7413

Ur

24

kV

49

28

630

A

36

28

1250

A

16

kA

20

kA

25

kA

1250A

770

16

31

325

72

213

38

197

775

770

56

71

210

13.5

4

4

653

25

320

650 641

370

610

458

383

303

210

53

79

79

98

800

35

55 119

19

35

36

747

Isc

23

48

310

TN

Ir

119 19

232

20

630A

636

VD4/P

83

4. Overall dimensions Withdrawable circuit-breakers for UniGear ZS1 switchgear 842

A

16

kA

20

kA

25

kA

56

Isc

28 28

48 790

1250

49 36

7 3

71

38

25

4

4

72

213

5

197

A

1250A

23

19

310

kV

630

119

232

325

24

770 31 16

Ur

775

7414

Ir

630A 144

TN

20

VD4/P

853

14

320 370 383

850

458

836

303

805

98

35

55

35

747

36

53

119

19

79

275 79

275

53

800

Withdrawable circuit-breakers for UniGear ZS1 switchgear 1600-2000A

842 141

7418

Ur

24

kV

49

30

1600

A

36

28

2000

A

2500

A

16

kA

20

kA

834

16

197

31

810

853

14

25

4

4

72

kA

345

kA

31.5

233

25

56

Isc

(1)

817

Ir

310

TN

2500A

119

233 20

VD4/P

320 370 383 303

850 836

46 53

458

805 785

132

275

52

119

55

79

732

275

(1) The rated uninterrupted current of 2300 A is guaranteed with natural ventilation. The rated uninterrupted current of 2500 A is guaranteed with forced ventilation.

84

Withdrawable circuit-breakers for UniGear ZS1 switchgear 636

kA

49 28 36

20

31.5

28

48 770

A

Isc

310

kV

1250

23

19

35

24

Ir

232

71

653

4

4

72

197

213

326

16

56 31

Ur

119

44

775

1VCD000173

770

TN

79

VD4/P

13.5

25

320 303

53

370

650

383

641

458

610 800

210

19

119

55

747

210

Withdrawable circuit-breakers for UniGear ZS1 switchgear 842

834

109

310 345 14

4

853

25

320

46

370

850

383 303

836 805

458

53

787 275

55

275

119

kA 31

31.5

Isc

28 28

56

A

36

16

3150

Ir

49

233

A

734

kV

2700

52

24

817

Ur

233

141

810

1VCD000177

4

TN

166

VD4/P

85

4. Overall dimensions Withdrawable circuit-breakers for PowerCube modules 842

kA

40

kA

166

742

kA

31.5

4

4

356 853

14

850 836

275

640

55

29

16 8

12

22

4

94

38

382 416

275

587

86

320 360

34

302

(*) 4000 A with forced ventilation.

303 25

370

806 750

189

19.5

76

165

25

52

109

kA

149

20

310

A (*)

280

3150

86

36

19

kV

30

17.5

17

111

92

17kV

12kV

28

214

Isc

kV

125

230

56

Ir

12

730

Ur

144 49

1VCD000152

16

TN

10

VD4/W

53

Withdrawable circuit-breakers for ZS8.4 switchgear 531

12

kV

Ir

630

A

20

kA

25

kA

4

260

510

Isc

52

563

Ur

303

205

1VCD000092

35

TN

91

VD4/Z8

503

53

548 150

495

55

150

Withdrawable circuit-breakers for ZS8.4 switchgear 531 486 455

503

563 153

kA

91

25

205

kA

Isc

260

A

20

4

kV

630

510

12

Ir

52

195 380

486 150

150

53

640

55

1VCD000093

Ur

584

TN

303

35

VD4/ZT8

87

4. Overall dimensions Withdrawable circuit-breakers for ZS8.4 switchgear 531 486 455

A

20

kA

25

kA

86

153

260

510

Isc

4

69 503

195 380

486 150

53

640

67

584

55

150

563

kV

630

5

12

Ir

52

524

Ur

303

205

1VCD000091

35

TN

91

VD4/ZS8

Withdrawable circuit-breakers for ZS8.4 switchgear 531 486 455

kA

25

kA

86

153

260

514

Isc

4

69

195

503

380 637

486

67

88

150

55

583

150

53

563

A

20

524

kV

1250

52

98

12

Ir

35

1VCD000133

Ur

205

TN

303

5

VD4/ZS8

Withdrawable circuit-breakers for ZS8.4 switchgear 531

VD4/Z8

52

A

1250

A

20

kA

25

kA

563

630

84

kV

260

Isc

kV

17.5

205

Ir

12

35

Ur

303

1VCD000137

507

TN

503 150

53

495

55

150

Withdrawable circuit-breakers for ZS8.4 switchgear 530 486 455

kA

25

kA

563

A

20

503

195 383

486 150

153

1250

52

98

A 205

630

260

kV

4

Isc

kV

17.5

514

Ir

12

303

53

637

150

55

Ur

1VCD000134

583

TN

35

VD4/ZT8

89

4. Overall dimensions Withdrawable circuit-breakers for ZS8.4 switchgear 681 636

24

kV

Ir

630

A

16

kA

20

kA

25

kA

611

86

325

524

563

Isc

52

680

Ur

303

3

310

1VCD000088

35

TN

91

VD4/ZS8

4

69 653 636

195 380

210

67

583

55

210

53

640

Withdrawable circuit-breakers for ZS8.4 switchgear 681

24

kV

Ir

630

A

16

kA

20

kA

25

kA

325

563

Isc

52

680

Ur

303

3

35

1VCD000089

310

TN

91

VD4/Z8

90

53

210

640

55

583

210

4

653

Withdrawable circuit-breakers for ZS8.4 switchgear 681

A

16

kA

20

kA

25

kA

325

Isc

563

kV

1250

84

24

Ir

35

1VCD000138

Ur

52

677

TN

303

310

VD4/Z8

210

53

4

653

640

587

55

210

Withdrawable circuit-breakers for ZS8.4 switchgear 681 636

VD4/ZT8

kA

25

kA

680

20

Isc

563

kA

310

16

611

325

A

653 636 210

4

kV

630

35

24

Ir

52

195 380

210

53

640

55

1VCD000090

Ur

585

TN

303

3

91

4. Overall dimensions Withdrawable circuit-breakers for ZS8.4 switchgear 681 636

VD4/ZT8 24

kV

Ir

1250

A

16

kA

20

kA

25

kA

611

325

563

677

Isc

52

84

Ur

303

35

1VCD000136

310

TN

210

4

653 636

195 380

210

53

587

55

640

Withdrawable circuit-breakers for ZS8.4 switchgear 681 636

VD4/ZS8

A

16

kA

20

kA

25

kA

86

325

524

Isc

611

4

69 653 636

195 380 640

67

92

210

55

587

210

53

563

kV

1250

52

84

24

Ir

35

Ur

303

310

1VCD000135

677

TN

Withdrawable circuit-breakers for UniSwitch and UniMix switchgear

A

1250

A

16

kA

20

kA

25

kA

A

48

38

325

Isc

35

kV

630

435,5

24

121

310

1VCD000047

Ur

1250A

570

35

TN

Ir

630A

626

VD4/US

25

4

13,5

653 650

320 370

23

210

303

210

36.3

383 53

742

55

DETAIL A SCALE 1 : 2

Withdrawable circuit-breakers for UniSec switchgear

42

35

38

653 650

210±1

14

210±1

25

320 370 383 303 415 648 ±1.5 742

23 36.3

kA

3

25

A

739

kA

435±1

20

Isc

18

kA

1250A

41

79

A

16

35

1250

Ir

4

A 310±1

kV

630

325±1

24

121±1

53

DETAIL A SCALE 1 : 2

55

1VCD000190

Ur

149 45°

TN

630A

626±1 604

VD4/SEC

93

4. Overall dimensions

Withdrawable circuit-breakers for UniGear ZS2 switchgear and PowerCube modules (36 kV) 842

VD4 kV

1250

A

1600

A

2000

A

31.5

kA

Ir

776

853

125

198

480

953

Isc

Ø "A"

973

36

956

1VYN300901-KG

Ur

380

TN

4

880

460

4 53

736 275

736

275

94

Breaker type

Ø A mm

VD4 36.12.32

35

VD4 36.16.32 - VD4 36.20.32

79

5. Electric circuit diagram

State of operation represented The diagrams shows the following conditions: – Circuit-breaker open and connected (only withdrawable circuit-breaker) – Circuits de-energized – Closing springs discharged

Graphical symbols for electric diagrams Thermal effect

Mass, frame

Capacitor (general symbol)

Passing make contact closing momentarily during release

Electromagnetic effect

Conductors in shielded cable (two conductors shown)

Motor (general symbol)

Closing position contact (limit switch)

Timing

Connection of conductors

Rectifier with two half-waves (bridge)

Opening position contact (limit switch)

Pushbutton control

Terminal or clamp

Make contact

Power circuit-breaker with automatic opening

Key control

Socket and plug (female and male)

Break contact

Control coil (general symbol)

Earth (general symbol)

Resistor (general symbol)

Change-over break before make contact

Lamp (general symbol)

95

5. Electric circuit diagram

Electric circuit diagram of fixed circuit-breakers 1VCD 400046 The electric circuit diagram given in this section regards the fixed circuit-breakers with breaking capacity up to 40 kA.

96

97

5. Electric circuit diagram

98

Caption = Reference number of diagram figure. = See the note indicated by the letter. * -BB1,..2-3 = Circuit-breaker auxiliary contacts. -BB4 = Circuit-breaker auxiliary passing contact with momentary closing during opening. -BB6 = Contact for the undervoltage release de- energized electrical signal -BB11 = Contact to interrupt the –BB4 signal during the manual opening operation -BM = STU Test unit for supervision of shunt opening release and shunt closing release winding continuity (see note D). = Spring-charging motor limit contacts. -BS1 = Limit contacts for signalling closing springs -BS2 charged/discharged. -MO1 = First shunt opening release (see note D). -MO2 = Second shunt opening release (see note D). -MO3 = Opening solenoid for release outside the circuitbreaker. -MO4 = Third shunt opening release (see note D). -MC = Shunt closing release (see note D). -MS = Motor for closing spring charging (see note C). -MU = Undervoltage release (see note B). -QB = Circuit-breaker accessories. -RL1 = Locking magnet. If de-energized, it mechanically prevents circuit-breaker closing (it is possible to limit its consumption by connecting a delayed pushbutton in series to enable the operation). = Pushbutton or contact for circuit-breaker closing. -SC -SO = Pushbutton or contact for circuit-breaker opening. -XB = Terminal box for the circuit-breaker circuits. -XB2...16 = Accessory connectors.

Description of figures = Motor circuit for closing spring charging (see note Fig. 1 C). Fig. 2 = Shunt closing release (anti-pumping is carried out mechanically) (see note D). = Locking magnet. When de-energised, it Fig. 3 mechanically prevents circuit-breaker closing. It is possible to limit consumption by connecting a delay pushbutton in series to enable the operation. = Instantaneous undervoltage release (see note B). Fig. 5 = Circuit of third opening release with continuous Fig. 6 control of the winding (see note D). Fig. 7 = Circuit of the first shunt opening release with possibility of continuous control of the winding (see note D). Fig. 9 = Circuit of the second shunt opening release with possibility of continuous control of the winding (see note D). Fig. 10 = Opening solenoid for release outside the circuitbreaker. Fig. 26 = Electrical signalling of closing springs charged and discharged. Fig. 30 = Circuit-breaker auxiliary passing contact with momentary closing during circuit-breaker opening. = Available circuit-breaker auxiliary contacts. Fig. 31 Fig. 32 ÷ 35 = Available circuit-breaker auxiliary contacts. It is possible to have one of these figures. The standard configuration is figure 32. = Contact for the undervoltage release deFig.60 energized electrical signal. Fig. 70 to 73 = Available auxiliary contacts of the circuit-breaker. One of these figures can be obtained.

99

5. Electric circuit diagram

Selection of the figures Description

Figures Notes

-MS

Spring charging motor

1

C

-MC

Shunt closing release

2

D

-MO1

Shunt opening release

7

D

-MU

Undervoltage release

5

B

-MO2

Additional shunt opening release

9

D

-BB1 -BB2

Set of 10 circuit-breaker auxiliary contacts

31

Set of 5 extra circuit-breaker auxiliary contacts 3C-20

32

Set of 5 extra circuit-breaker auxiliary contacts 5C

33

Set of 5 extra circuit-breaker auxiliary contacts 2C-30

34

Set of 5 extra circuit-breaker auxiliary contacts 50

35

-BB3

Notes: C = normally open contact with circuit-breaker open 0 = normally closed contact with circuit-breaker open -RL1

Locking magnet on operating mechanism

3

-BB4

Transient contact

30

-BS2

Contact for signalling closing spring charged/discharged

26

-MO3

Opening solenoid for release outside the circuit-breaker

10

F

-MO4

Third shunt opening release

6

D

100

Incompatibility The combination of circuits given in the figures below are not possible on the same circuit-breaker: 32-33-34-35 Notes A) The circuit-breaker is only fitted with the accessories specified in the order acknowledgement. To draw up the order, please consult this catalogue. B) The undervoltage release can be supplied for power supply branched on the supply side of the circuit-breaker or from an independent source. Circuit-breaker closing is only possible with the undervoltage release energized (the lock on closing is made mechanically). In the case where there is the same power supply for the shunt closing and undervoltage releases and automatic circuitbreaker closing is required on return of the auxiliary voltage, a delay of 50ms must be introduced between the moment of consent to the undervoltage release and energization of the shunt closing release. Incompatible with -MO4. C) Check the auxiliary circuit power to verify the possibility of starting several motors for charging the closing springs at the same time. To prevent excessive consumption the closing springs must be charged manually before energizing the auxiliary circuit. D) The circuit for controlling the shunt opening release winding continuity must only be used for this purpose. It is possible to use the STU Test Unit to check continuity of the various release. E) When fig. 06 is required, contact -BB3 (41-42) of fig. 32-33 is not available and figs. 34-35 cannot be supplied. When fig. 09 is required, contact -BB1 (43-44) of fig. 31 is not available.

Electric circuit diagram of fixed circuit-breakers 1VCD 400099 The electric circuit diagram given in this section regards the fixed circuit-breakers with breaking capacity up to 50 kA.

101

5. Electric circuit diagram

102

103

5. Electric circuit diagram

Caption = Reference number of diagram figure. = See the note indicated by the letter. * -BB1,..2-3 = Circuit-breaker auxiliary contacts. -BB4 = Circuit-breaker auxiliary passing contact with momentary closing during opening. -BB6 = Contact for the undervoltage release deenergized electrical signal. -BB11 = Contact to interrupt the –BB4 signal during the manual opening operation. -BM = STU Test unit for supervision of shunt opening release and shunt closing release winding continuity (see note D). = Spring-charging motor limit contacts. -BS1 = Limit contacts for signalling closing springs -BS2 charged/discharged. -MO1 = First shunt opening release (see note D). -MO2 = Second shunt opening release (see note D). -MO4 = Third shunt opening release (see note D). -MC = Shunt closing release (see note D). -MS = Motor for closing spring charging (see note C). -MU = Undervoltage release (see note B). -QB = Circuit-breaker accessories. -RL1 = Locking magnet. If de-energized, it mechanically prevents circuit-breaker closing (it is possible to limit its consumption by connecting a delayed pushbutton in series to enable the operation). = Pushbutton or contact for circuit-breaker closing. -SC = Pushbutton or contact for circuit-breaker -SO opening. = Terminal box for the circuit-breaker circuits. -XB -XB2...16 = Accessory connectors.

104

Description of figures Fig. 1 = Motor circuit for closing spring charging (see note C). = Shunt closing release (anti-pumping is carried out Fig. 2 mechanically) (see note D). Fig. 3 = Locking magnet. When de-energised, it mechanically prevents circuit-breaker closing. It is possible to limit consumption by connecting a delay pushbutton in series to enable the operation. Fig. 5 = Instantaneous undervoltage release (see note B). = Circuit of third opening release with continuous Fig. 6 control of the winding (see note D). = Circuit of the first shunt opening release with Fig. 7 possibility of continuous control of the winding (see note D). Fig. 9 = Circuit of the second shunt opening release with possibility of continuous control of the winding (see note D). Fig. 26 = Electrical signalling of closing springs charged and discharged. Fig. 30 = Circuit-breaker auxiliary passing contact with momentary closing during circuit-breaker opening. Fig. 31 = Available circuit-breaker auxiliary contacts. Fig. 32 ÷ 35 = Available circuit-breaker auxiliary contacts. It is possible to have one of these figures. The standard configuration is figure 32. Fig. 60 = Contact for the undervoltage release deenergized electrical signal. Fig. 70 to 73 = Available auxiliary contacts of the circuit-breaker. One of these figures can be obtained.

Selection of the figures Description

Figures Notes

-MS

Spring charging motor

1

C

-MC

Shunt closing release

2

D

-MO1

Shunt opening release

7

D

-MU

Undervoltage release

5

B

-MO2

Additional shunt opening release

9

D

-BB1 -BB2

Set of 10 circuit-breaker auxiliary contacts

31

Set of 5 extra circuit-breaker auxiliary contacts 3C-20

32

Set of 5 extra circuit-breaker auxiliary contacts 5C

33

Set of 5 extra circuit-breaker auxiliary contacts 2C-30

34

Set of 5 extra circuit-breaker auxiliary contacts 50

35

-BB3

Notes: C = normally open contact with circuit-breaker open 0 = normally closed contact with circuit-breaker open -RL1

Locking magnet on operating mechanism

3

-BB4

Transient contact

30

-BS2

Contact for signalling closing spring charged/discharged

26

-MO3

Opening solenoid for release outside the circuit-breaker

10

F

-MO4

Third shunt opening release

6

d

Incompatibility The combination of circuits given in the figures below are not possible on the same circuit-breaker: 32-33-34-35 Notes A) The circuit-breaker is only fitted with the accessories specified in the order acknowledgement. To draw up the order, please consult this catalogue. B) The undervoltage release can be supplied for power supply branched on the supply side of the circuit-breaker or from an independent source. Circuit-breaker closing is only possible with the undervoltage release energized (the lock on closing is made mechanically). In the case where there is the same power supply for the shunt closing and undervoltage releases and automatic circuitbreaker closing is required on return of the auxiliary voltage, a delay of 50ms must be introduced between the moment of consent to the undervoltage release and energization of the shunt closing release. Incompatible with -MO4. C) Check the auxiliary circuit power to verify the possibility of starting several motors for charging the closing springs at the same time. To prevent excessive consumption the closing springs must be charged manually before energizing the auxiliary circuit. D) The circuit for controlling the shunt opening release winding continuity must only be used for this purpose. It is possible to use the STU Test Unit to check continuity of the various release. E) When fig. 06 is required, contact -BB3 (41-42) of fig. 32-33 is not available and figs. 34-35 cannot be supplied. When fig. 09 is required, contact -BB1 (43-44) of fig. 31 is not available.

105

5. Electric circuit diagram

Electric circuit diagram of withdrawable circuit-breakers 1VCD 400047 The electric circuit diagram given in this section regards the withdrawable circuit-breakers with breaking capacity up to 40 kA. For withdrawable circuit-breakers with motorized truck, see diagram 1VCD400048. For circuit-breaker of ZS8.4 switchgears the following diagrams are available: 1VCD400080 Standard version 1VCD400085 Version with motorized truck.

106

107

5. Electric circuit diagram

108

109

5. Electric circuit diagram

Caption = Reference number of diagram figure. = See the note indicated by the letter. * -BB1,..2-3 = Circuit-breaker auxiliary contacts. -BB4 = Circuit-breaker auxiliary passing contact with momentary closing during opening. -BB6 = Contact for the undervoltage release deenergized electrical signal. -BB11 = Contact to interrupt the –BB4 signal during the manual opening operation, -BD = Enclosure door position contact. -BM = STU Test Unit for checking winding continuity of the shunt opening and closing release (see note D). = Spring-charging motor limit contacts. -BS1 -BS2 = Limit contact for signalling closing springs charged/discharged. -BT1 = Contacts for electrical signalling of circuitbreaker in connected position (see note E). = Contacts for electrical signalling of circuit-BT2 breaker in isolated position (see note E). -BT3 = Circuit-breaker position contact, open during the circuit-breaker isolation run. -MO1 = First shunt opening release (see note D).

-MO2 -MO3

= Second shunt opening release (see note D). = Opening solenoid for release outside the circuit-breaker. -MO4 = Third shunt opening release (see note D). -MC = Shunt closing release (see note D). = Motor for closing spring charging (see note C). -MS = Undervoltage release (see note B). -MU -QB = Circuit-breaker accessories. -RL1 = Locking magnet. If de-energized, it prevents mechanical closing of the circuit-breaker (it is possible to limit its consumption by connecting a delayed pushbutton in series to enable the operation). -RL2 = Locking magnet (on the truck). If de-energized, it prevents mechanical connection and isolation of the circuit-breaker (it is possible to limit its consumption by connecting a delayed pushbutton in series to enable the operation). = Pushbutton or contact for circuit-breaker -SC closing. = Pushbutton or contact for circuit-breaker -SO opening. -XB = Connector for the circuit-breaker circuits. -XB2...16 = Accessory connectors.

Selection of the figures Description

Figures

Notes

-MS

Closing spring charging motor

1

C

-MC

Shunt closing release

2

D

-MO1

Shunt opening release

7

D

-MU

Undervoltage release

5

B

-MO2

Additional shunt opening release

9

D-F

-RL2

Locking magnet on the truck

8

-BB4

Auxiliary passing contact

30

-BS2

Contact for signalling closing spring charged/discharged

26

-MO3

Opening solenoid for release outside the circuit-breaker

10

F

-MO4

Third shunt opening release

6

D-F

110

F

Selection of the figures Set of 10 circuit-breaker auxiliary contacts

Set of 5 other circuit-breaker auxiliary contacts

Circuit-breaker connected isolated contact

Position contact for withdrawable circuit-breakers

Locking magnet on the operating mechanism

-BB1 -BB2

-BB3

-BT1 -BT2

-BT3

-RL1

X X

X

X X

X X

X X

X X

X

X

X

X

3-4 31-32-52

31-32-33-34 33-34-51

F

32

F

31 / 51

E-F

32 / 51

E-F

X

3 / 31 / 51

E-F-G

X

3 / 32 / 51

E-F-G

4 / 33

E-F-G

X

X

4 / 34

E-F-G

X

X

X

4 / 33 / 52

E-F-G

X

X

X

4 / 34 / 52

E-F-G

Incompatibility The circuits given in the figures below cannot be supplied at the same time in the same circuit-breaker:

31

X

X

X

Notes

X

X X

Figures

4-31-32 51-52

3-33-34 5-6

Notes A) The circuit-breaker is only fitted with the accessories specified in the order acknowledgement. To draw up the order, please consult the present catalogue. B) The undervoltage release can be supplied for power supply branched on the supply side of the circuit-breaker or from an independent source. Circuit-breaker closing is only possible with the undervoltage release energized (the lock on closing is made mechanically). In the case where there is the same power supply for the closing and undervoltage releases and automatic circuit-breaker closing is required on return of the auxiliary voltage, a delay of 50ms must be introduced between the moment of consent to the undervoltage release and energization of the shunt closing release. Incompatible with -MO4.

C) Check the power available on the auxiliary circuit to verify the possibility of starting several motors for charging the closing springs at the same time. To prevent excessive consumption the closing springs must be charged manually before energizing the auxiliary circuit. D) The circuit for controlling the shunt opening release winding continuity must only be used for this purpose. It is possible to use the STU Shunt Test Unit to check continuity of the winding. E) The contacts for electrical signalling of circuit-breaker in the connected and isolated position (-BT1 and -BT2) shown in fig. 51 or 52 are located in the circuit-breaker truck F) When fig. 10 is requested, contact -BB3 31-32 indicated of fig. 32-34 is not available. When fig. 30 is requested, contact -BB3 (53-54) indicated of fig. 32-34 is not available. When fig. 9 is requested, contact -BB1 (43-44 indicated) of fig. 31-32-33-34 is not available. When fig. 06 is required, contact -BB3 (terminals 41-42) of figs. 32 and 34 is not available. G) Fig. 3 is supplied when fig. 31 or 32 is requested. Fig. 4 is supplied when fig. 33 or 34 is requested (in this case it is compulsory to supply the -BT3).

111

5. Electric circuit diagram

Electric circuit diagram of withdrawable circuit-breakers 1VCD 400100 The electric circuit diagram given in this section regards the withdrawable circuit-breakers with breaking capacity up to 50 kA. For withdrawable circuit-breakers with motorized truck, see diagram 1VCD400102.

112

113

5. Electric circuit diagram

114

115

5. Electric circuit diagram

Caption = Reference number of diagram figure. = See the note indicated by the letter. * -BB1,..2-3 = Circuit-breaker auxiliary contacts. -BB4 = Circuit-breaker auxiliary passing contact with momentary closing during opening. -BB6 = Contact for the undervoltage release de- energized electrical signal -BB11 = Contact to interrupt the –BB4 signal during the manual opening operation, -BD = Enclosure door position contact. -BM = STU Test Unit for checking winding continuity of the shunt opening and closing release (see note D). -BS1 = Spring-charging motor limit contacts. -BS2 = Limit contact for signalling closing springs charged/discharged. -BT1 = Contacts for electrical signalling of circuit- breaker in connected position (see note E). -BT2 = Contacts for electrical signalling of circuit- breaker in isolated position (see note E). -BT3 = Circuit-breaker position contact, open during the circuit-breaker isolation run.

-MO1 -MO2 -MO4 -MC -MS -MU -QB -RL1

= First shunt opening release (see note D). = Second shunt opening release (see note D). = Third shunt opening release (see note D). = Shunt closing release (see note D). = Motor for closing spring charging (see note C). = Undervoltage release (see note B). = Circuit-breaker accessories. = Locking magnet. If de-energized, it prevents mechanical closing of the circuit-breaker (it is possible to limit its consumption by connecting a delayed pushbutton in series to enable the operation). -RL2 = Locking magnet (on the truck). If de-energized, it prevents mechanical connection and isolation of the circuit-breaker (it is possible to limit its consumption by connecting a delayed pushbutton in series to enable the operation). -SC = Pushbutton or contact for circuit-breaker closing. -SO = Pushbutton or contact for circuit-breaker opening. -XB = Connector for the circuit-breaker circuits. -XB2...16 = Accessory connectors.

Selection of the figures Description

Figures

Notes

-MS

Closing spring charging motor

1

C

-MC

Shunt closing release

2

D

-MO1

Shunt opening release

7

D

-MU

Undervoltage release

5

B

-MO2

Additional shunt opening release

9

D-F

-RL2

Locking magnet on the truck

8

-BB4

Auxiliary passing contact

30

-BS2

Contact for signalling closing spring charged/discharged

26

-MO4

Third shunt opening release

6

116

F D-F

Selection of the figures Set of 10 circuit-breaker auxiliary contacts -BB1 -BB2

Set of 5 other circuit-breaker auxiliary contacts -BB3

Circuit-breaker connected isolated contact -BT1 -BT2

Position contact for withdrawable circuit-breakers -BT3

Locking magnet on the operating mechanism -RL1

Figures

Notes

31

F

32

F

X

31 / 51

E-F

X

32 / 51

E-F

X

3 / 31 / 51

E-F-G

X X

X

X X

X

X X

X X

X

X

3 / 32 / 51

E-F-G

X

X

4 / 33

E-F-G

X

X

4 / 34

E-F-G

X

X

X

4 / 33 / 52

E-F-G

X

X

X

4 / 34 / 52

E-F-G

X X

X

X X

X

Incompatibility The circuits given in the figures below cannot be supplied at the same time in the same circuit-breaker: 3-4 31-32-52

31-32-33-34 31-34-51

4-31-32 51-52

3-33-34 5-6

Note A) The circuit-breaker is only fitted with the accessories specified in the order acknowledgement. To draw up the order, please consult the apparatus catalogue. B) The undervoltage release can be supplied for power supply branched on the supply side of the circuit-breaker or from an independent source. Circuit-breaker closing is only possible with the undervoltage release energized (the lock on closing is made mechanically). In the case where there is the same power supply for the closing and undervoltage releases and automatic circuit-breaker closing is required on return of the auxiliary voltage, a delay of 50ms must be introduced between the moment of consent to the undervoltage release and energization of the shunt closing release. Incompatible with -MO4

C) Check the power available on the auxiliary circuit to verify the possibility of starting several motors for charging the closing springs at the same time. To prevent excessive consumption the closing springs must be charged manually before energizing the auxiliary circuit. D) The circuit for controlling the shunt opening release winding continuity must only be used for this purpose. It is possible to use the Shunt Test Unit to check continuity of the winding. E) The contacts for electrical signalling of circuit-breaker in the connected and isolated position (-BT1 and -BT2) shown in fig. 51 or 52 are located in the circuit-breaker truck F) When fig. 9 is required, contact -BB1 (terminals 41-42) of figs. 31-32-33-34 is not available. When fig. 30 is required, contact -BB3 (terminals 53-54) of figs. 32 and 34 is not available. When fig. 06 is required, contact -BB3 (terminals 41-42) of figs. 32-34 is not available. G) Fig. 3 is supplied when fig. 31 or 32 are required. Fig. 4 is supplied when fig. 33 or 34 are required (in this case, it is obligatory for -BT3 to be supplied).

117

ABB S.p.A. Power Products Division Unità Operativa Sace-MV Via Friuli, 4 I-24044 Dalmine Tel.: +39 035 6952 111 Fax: +39 035 6952 874 e-mail: [email protected]

ABB AG Calor Emag Medium Voltage Products Oberhausener Strasse 33 Petzower Strasse 8 D-14542 Glindow D-40472 Ratingen Phone: +49(0)2102/12-1230, Fax: +49(0)2102/12-1916 E-mail: [email protected] www.abb.com

The data and illustrations are not binding. We reserve the right to make changes without notice in the course of technical development of the product. © Copyright 2012 ABB. All rights reserved.