Remote Diagnostics

Remote Diagnostics. SIMATIC S7-1500 ... Overview/setting for which interfaces of the station the web server access is enabled ƒ Setting is also availa...

0 downloads 164 Views 2MB Size
Remote Diagnostics ….With TIA Portal Restricted © Siemens AG 2016

siemens.tld/FACE 2016

• Local Diagnostics

3

• Remote Diagnostics

10

• Simatic Teleservice

17

Unrestricted © Siemens AG 20XX Page 2

24.06.2016

Prasad K. Raverkar / DF FA S SUP

Local Diagnostics

Local Diagnostics With TIA Portal

e.g. SIMATIC S7-1500 System diagnostics - Settings System diagnosis Activated by default Can not be deactivated

Reduced configuration range Page 4

24.06.2016

Prasad K. Raverkar / DF FA S SUP

SIMATIC S7-1500 System diagnostics – New Concept ƒ System diagnostics integrated in the firmware of the PLC ƒ User blocks as in S7-300/400 are no longer necessary

ƒ Diagnostics are also available in operation mode STOP of the PLC

ƒ Removal of alarm configuration (setup of the alarms, alarm attributes)  less configuration effort, is done by the system

FB49, DB49 DB50, FC49

Display Display for each PLC ƒ Each S7-1500 PLC with display ƒ Two different sizes depending on the PLC-Type ƒ 2.4“ for PLC S7-1516 ƒ 1.36“ for PLC S7-1511/1513 ƒ PLC can operate without display ƒ Can be plugged or removed during operation ƒ Display in 2 languages (menu and error/alarm texts) ƒ Language can be switched during operation

Display Display for with every S7-1500 ƒ Access to order number, firmware version and serial number of all modules ƒ For commissioning phase (e.g. assigning IP-address, station name) ƒ For diagnostics

start screen

state

diagnostics

Display Status information of the S7-1500 CPU

Color of the status information

green

orange

red

white

Meaning RUN, RUN with alarm

STOP

FAULTED Connection startup, connection between PLC and display is lost

SIMATIC S7-1500 Display configuration The display language can be switched between 8 different languages

As additional protection mechanism a password could be enabled for the entries via the display. Read-only functionalities can still be executed. Entries can only be performed at the display when the correct password is entered.

Remote Diagnostics

Remote Diagnostic with Integrated Web server

© Siemens AG 2012. All Rights Reserved.

SIMATIC S7-1500 Define Web server Access ƒ Overview/setting for which interfaces of the station the web server access is enabled 1 1

ƒ Setting is also available in the properties of each interface 2

2

SIMATIC S7-1500 Define Web server Access

SIMATIC S7-1500 Define Web server Access

ƒ Browser displays the content of the SIMATIC memory card on the "File browser" website. ƒ You can read and edit the log files generated by the CPU without having to run STEP 7.

Web server : Location independent remote diagnostics Integrated Web Server ƒ Access to system, process messages as well as identification data ƒ System diagnostics of all projected modules, centralized & decentralized ƒ Communication diagnostics of parameters, statistics, connection status ƒ Access to process data by using tag tables and freely definable tag lists ƒ User defined web pages in the PLC File Browser ƒ Access by using web server via filebrowser for bidirectional data communication in .csv format

Simple acquisition of process values and system status

SIMATIC Apps on Mobile

https://play.google.com/se ttings?hl=en

Page 15

24.06.2016

Prasad K. Raverkar / DF FA S SUP

SIMATIC S7-1200 S7-1200 App (iPhone Application)

S7-1200 App Version 1.0

Start S7-1200 App … Page 16

24.06.2016

List of users PLC’s Prasad K. Raverkar / DF FA S SUP

Teleservice Option

Simatic TeleService

Why TeleService?

Benefits: Low-cost, easy-to-handle solution for TeleService specially tuned to industrial automation Shorter response times for services

ƒ No need for specialists to be constantly on-call on site ƒ No travel expenses for service calls ƒ Industrial SIMATIC standard ƒ Support for specific SIMATIC services ƒNo configuring needed for communication from PG/PC to the CPU Unrestricted © Siemens AG 20XX Page 18

24.06.2016

Prasad K. Raverkar / DF FA S SUP

Why TeleService?

SIMATIC TeleService • TeleService adapter • TeleService software • Function blocks (FBs) for remote maintenance, remote coupling

Adapter TeleService Adapter II Bus connection MPI Profibus PPI

Analog

ISDN

x x x

x x x

PROFINET Industrial Ethernet

TeleService Adapter IE Analog

ISDN

x x

x x

Unrestricted © Siemens AG 20XX Page 19

24.06.2016

Prasad K. Raverkar / DF FA S SUP