SYARIKAT BEKALAN AIR SELANGOR SDN BHD

syarikat bekalan air selangor sdn bhd. project : drawing no : drawing title : drawn by : shahrul designed : sat note : approved : lpl details of mild ...

0 downloads 59 Views 719KB Size
NOTES : 1. FOR LEGEND, ABBREVIATIONS AND GENERAL NOTES, SEE DWG NO:. SYA / STD / 001. 2. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED. 3. THICKNESS OF TAPERS AND BENDS SHALL FOLLOW SCHEDULE OF STEEL PIPES FITTINGS THICKNESS. 4. FID REFERS TO FINISHED INTERNAL DIAMETER AFTER LINING. 5. MS PIPE SPECIALS SHALL BE DESIGNED IN ACCORDANCE TO BS EN 534:1990 6. FLANGES SHALL BE DESIGNED TO PN 16 7. FLANGES SHALL BE IN ACCORDANCE TO BS 4504 TABLE 16/11

REV. DESCRIPTION ALL MS FITTINGS 600mm DIA. AND LESS SHALL 1 BE OF FLANGE ENDED

DATE JULY 2007

SYARIKAT BEKALAN AIR SELANGOR SDN BHD JALAN PANTAI BAHARU, 59200, KUALA LUMPUR. TEL NO : 03 - 2088 5400 FAX NO : 03 - 2088 5373

PROJECT :

DRAWING TITLE : DETAILS OF MILD STEEL PIPES, BENDS AND CONCENTRIC TAPERS DRAWN BY : SHAIFUL

DESIGNED : SAT

CHECKED : HS

APPROVED : LPL

SCALE : NTS

DATE : OCT 2005

DRAWING NO :

SYA / MS / STD / 001 / REV. 1

NOTE : 1. FOR LEGEND, ABBREVIATIONS AND GENERAL NOTES, SEE DWG. NO: SYA/STD/001. 2. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED. 3. O.D REFERS TO OUTER DIAMETER. 4. THICKNESS OF TEE AND BENDS SEE SCHEDULE OF STEEL PIPES/ FITTINGS THICKNESS. 5. FLANGES SHALL BE IN ACCORDANCE TO BS 4504 TABLE 16/11

REV.

DESCRIPTION

DATE

1

ALL TEES BELOW 600 DIA. TO BE USED FLANGE JOINT

JULY 2007

SYARIKAT BEKALAN AIR SELANGOR SDN BHD JALAN PANTAI BAHARU, 59200, KUALA LUMPUR. TEL NO : 03 - 2088 5400 FAX NO : 03 - 2088 5373

PROJECT :

DRAWING TITLE : DETAILS OF MILD STEEL TEES DRAWN BY : SHAHRUL

DESIGNED : SAT

CHECKED : HS

APPROVED : LPL

SCALE : NTS

DATE : OCT 2005

DRAWING NO :

SYA / MS / STD / 002 / REV. 1

NOTE : 1. FOR LEGEND, ABBREVIATION AND GENERAL NOTES, SEE DWG NO:. SYA/STD/001. 2. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED. 3. THE OUTSIDE DIAMETER OF PIPE SHALL MEAN THE EXTERNAL DIAMETER OF STEEL PIPE BEFORE COATING.

REV. REVISED BY DESCRIPTION 0 LPL/HS Original drawing. 1

To remove the details of sleeve joint for pipe below 700mm dia. and replace with flange joint details.

YHH

DATE OCT. `05 08 APR `11

SYARIKAT BEKALAN AIR SELANGOR SDN BHD JALAN PANTAI BAHARU, 59200, KUALA LUMPUR. TEL NO : 03 - 2088 5400 FAX NO : 03 - 2088 5373

PROJECT :

DRAWING TITLE : DETAILS OF JOINTS (SHEET 1 OF 2) DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED : KTT

APPROVED : SS

SCALE : NTS

DATE : JUNE 2011

DRAWING NO :

SYA / MS / STD / 003 / REV.1

NOTE : 1. FOR LEGEND, ABBREVIATION AND GENERAL NOTES, SEE DWG NO:. SYA/STD/001. 2. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED. 3. THE OUTSIDE DIAMETER OF PIPE SHALL MEAN THE EXTERNAL DIAMETER OF STEEL PIPE BEFORE COATING.

REV.

DESCRIPTION

DATE

SYARIKAT BEKALAN AIR SELANGOR SDN BHD JALAN PANTAI BAHARU, 59200, KUALA LUMPUR. TEL NO : 03 - 2088 5400 FAX NO : 03 - 2088 5373

PROJECT :

DRAWING TITLE : DETAILS OF JOINTS (SHEET 2 OF 2) DRAWN BY : SHAHRUL

DESIGNED : SAT

CHECKED : HS

APPROVED : LPL

SCALE : NTS

DATE : OCT 2005

DRAWING NO :

SYA / MS / STD / 004

NOTE : 1. FOR LEGEND, ABBREVIATION AND GENERAL NOTES, SEE DWG NO. SYA/STD/001. 2. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED. 3. MASS CONCRETE GRADE 20/25. 2 4. ALLOWABLE BEARING PRESSURE = 75 KN/M. 2

5. TEST PRESSURE FOR THRUST BLOCKS IS BASED ON 100m HEAD OF WATER. 6. DIMENSIONS OF THRUST BLOCKS TO BE INCREASED IF ACTUAL BEARING PRESSURE IS FOUND TO BE LESS THAN 75 KN/M. 7. DIMENSIONS 'A' OF THRUST BLOCK TO BE ADJUSTED BY THE S.O. IF NECESSARY TO SUIT TRENCH WIDTH.

REV.

DESCRIPTION

DATE

SYARIKAT BEKALAN AIR SELANGOR SDN BHD JALAN PANTAI BAHARU, 59200, KUALA LUMPUR. TEL NO : 03 - 2088 5400 FAX NO : 03 - 2088 5373

PROJECT :

DRAWING TITLE : DETAILS OF CONCRETE THRUST BLOCK AND ANCHOR BLOCK. DRAWN BY : SHAHRUL

DESIGNED : SAT

CHECKED : HS

APPROVED : LPL

SCALE : NTS

DATE : OCT 2005

DRAWING NO :

SYA / MS / STD / 005